Resolving TIA Portal Multiuser Check-in Crash on Project Server

David Krause12 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving TIA Portal Multiuser Check-in Crash on Project Server

Multiuser engineering in TIA Portal (V15.1 through V19) relies on a centrally hosted project server that all editors commit changes into. When the TIA Portal client crashes during the Check-in action—most often with large HMI delta sets—the local session becomes locked, the carry-over objects pile up, and follow-up commits fail until the project is rebuilt. This reference documents the root causes, the official Siemens fix path (109971630 - TIA Portal crashes when compiling the PLC), and a field-proven archive/restore recovery that resolves the lock without losing committed work.

Symptom signature: TIA Portal terminates with an unhandled exception during Check-in. Compiling the PLC, Download to device, Start Simulation, and Multiuser Check-in all trigger the same fault because each action forces an implicit compile of the affected PLC and HMI targets.

1. Problem Description

The failing installation in this case was TIA Portal V17 Update 5 on Windows 10 Pro 22H2, hosted against a SIMATIC Project Server running inside a Windows Server 2019 virtual machine. The engineering workstation connected to the server over a corporate VPN tunnel. The project contained:

  • 1 master HMI (Comfort Panel TP1500, WinCC Comfort/Advanced V17)
  • 5 secondary HMIs (TP700/TP1200, WinCC Comfort/Advanced V17)
  • 6 SIMATIC S7-1500 PLCs (CPU 1515-2 PN, firmware V2.9)
  • ~3,200 HMI tags, ~280 screens, shared text lists and graphics lists

Small check-ins (one or two HMI screens, a single tag rename) completed without issue. The crash was reproducible when the editor attempted to commit a delta set covering five or more screens, a text list regeneration, or any cross-HMI tag rename that propagated through the master HMI into the secondary panels. The exception was raised inside the WinCC compile service (S7WCComp.exe) and the TIA Portal shell (S7TGTOPX.exe) exited with code 0xC0000005 (access violation) followed by Windows Error Reporting entry Application Error 1000.

2. Why the Crash Happens: Root Cause Analysis

Siemens' official knowledge base entry 109971630 identifies the root cause as a defect in the TIA Portal compile pipeline when an implicit compile is triggered as part of a higher-level action. The defect is independent of the network path; it is observable on a local server, but VPN latency, MTU fragmentation, and RPC retransmits amplify the symptoms because the multiuser backend (MS-SQL based project server) hands a stale handle back to the client when the implicit compile aborts.

Three contributing factors stack on top of the compile defect:

Factor Mechanism Where it shows up
Implicit compile during Check-in Every Check-in rebuilds the affected PLC and HMI before committing. The compile defect in 109971630 terminates the process mid-write. S7WCComp.exe event log entry, then TIA Portal exit
Cross-HMI master/secondary overlay When screens are copied from the master to secondary HMIs, deleted objects from earlier overlays remain as carry-over objects in the local session cache. Local session folder grows past 2 GB, compile times exceed 90 s
VPN path to the project server VM Non-routable discovery traffic (PROFINET DCP, broadcast from TIA Portal device discovery) is dropped or delayed by the VPN, extending the implicit compile window. Compile starts, RPC keepalive stalls, SQL transaction times out after 120 s
Important: The compile defect is not caused by the VPN. Removing the VPN tunnel resolves secondary symptoms (RPC timeouts, broadcast drops) but does not fix the crash. Apply the Siemens hotfix described in 109971630 first, then address the network and overlay hygiene.

3. Confirming the Fault: Diagnostic Procedure

Run the following checks in order before applying a fix. Each step isolates one contributing factor.

  1. Capture the Windows application event: Open eventvwr.msc and read Windows Logs → Application. The crash produces Application Error event ID 1000 with faulting module S7WCComp.dll or TDKeyNote.dll, exception code 0xC0000005. Note the offset address and TIA Portal build number (Help → About).
  2. Reproduce on a local server: Copy the server project to a local directory, open it as a server project on the same subnet, and attempt the same Check-in. If the local copy crashes, the issue is the compile defect (109971630) and not the VPN.
  3. Measure implicit compile duration: In TIA Portal, open the local session and force a compile of the master HMI (right-click → Compile → Software (rebuild all)). A successful compile under 60 s is normal. A compile that exceeds 120 s before the crash indicates carry-over object bloat.
  4. Inspect the local session folder: Navigate to %LOCALAPPDATA%\Siemens\Automation\ProjectServer\<ProjectName>\<SessionID>. A folder larger than 2 GB or with more than 60 000 files points to carry-over object accumulation from repeated cross-HMI overlays.
  5. Validate the VPN path: From the engineering workstation, run Test-NetConnection -ComputerName <server-VM> -Port 4410 (the default SIMATIC Project Server TCP port). Also test UDP 49152–65535 for PROFINET DCP if device discovery is required during compile. Dropped packets or latency above 80 ms RTT increase crash probability.

4. Primary Fix: Apply the Siemens Hotfix from 109971630

The supported resolution from Siemens is documented in entry 109971630:

  1. Open the Siemens Industry Online Support entry and identify the affected TIA Portal version and update level.
  2. Download the matching hotfix package (for example, TIA Portal V17 Update 6 HF01 or V18 Update 2 depending on your installed base).
  3. Close all TIA Portal instances and the TIA Portal Help System.
  4. Run the hotfix installer with administrator rights. The installer patches S7WCComp.dll, TDKeyNote.dll, and S7TGTOPX.exe in the TIA Portal installation directory.
  5. Reboot the workstation and re-open the multiuser project. Verify the build number in Help → About reflects the hotfix.
  6. Perform a single Check-in on a 1-screen delta to confirm the crash no longer reproduces before resuming production work.
License and project integrity: The hotfix does not alter project data. Re-license the workstation with the existing TIA Portal license key after the patch; floating licenses on the license server are unaffected.

5. Secondary Recovery: Archive and Restore the Locked Local Session

Even after the hotfix is applied, an already-locked local session cannot be salvaged. Use the archive/restore path to recover the committed work and clear the carry-over objects.

  1. Identify the last good server revision: In TIA Portal, switch to the Server Project View, right-click the project, and select Manage Versions. Note the version number that existed before the crashing Check-in.
  2. Open a clean local session on the previous good version: Open → Open project from server, choose that revision, and create a new local working session. This local session is guaranteed not to contain the corrupt carry-over objects.
  3. Archive the project locally: With the clean local session open, choose Project → Archive. Select User-defined path and target a folder with at least 5 GB free. The archive operation strips the local session metadata, leaving only the canonical project content. .zap17 (V17), .zap18 (V18), or .zap19 (V19) is produced.
  4. Restore the archive on the server: On the server VM (or via RDP/console, not over the VPN), start TIA Portal and choose Project → Retrieve. Point at the archive. This rebuilds the multiuser server project from scratch with no carry-over residue.
  5. Re-create a new local session: From the engineering workstation, open the server project, create a fresh local session, and re-apply any in-flight edits that were not yet committed. Check in small deltas (one screen, one tag) until confidence in the hotfix is established.

6. Eliminate the VPN as a Variable

The VPN is rarely the root cause but is a frequent amplifier. If the crash persists after the hotfix and the archive/restore cycle, validate the network path:

  • TCP 4410 (SIMATIC Project Server) must be open bidirectionally.
  • TCP 102 (S7 communication) is required for online operations during compile.
  • UDP 49152–65535 may be required for PROFINET DCP device discovery if the implicit compile needs to resolve the PLC online.
  • RDP port 3389 is recommended for a console session into the server VM during heavy Check-in operations to bypass the VPN for the SQL transaction path.

Set the VPN MTU to 1380 bytes or lower to avoid fragmentation of the multiuser RPC packets. Enable TCP keepalives at 30 s with a 60 s interval on the VPN client. A common field finding is a stateful firewall silently dropping the RPC retransmits after 120 s; check the VPN appliance logs for asymmetric flows.

7. Long-Term Fix: Refactor to HMI Common Connection and PLC Proxy

For projects with one master HMI and several secondary HMIs that share most screens, the sustainable fix is to remove the screen-overlay workflow. The master/secondary overlay mechanism is what creates the carry-over objects that bloat the local session.

7.1 HMI Common Connection (WinCC Comfort/Advanced and WinCC Unified)

The HMI Common Connection feature lets multiple HMI devices share a single PLC connection defined once at the project level. Open the project in TIA Portal, select Options → HMI Common Connection, add the participating HMIs, and define the connection once. Each HMI then references the common connection by name instead of carrying its own copy. This reduces the compile surface because tag consistency checks run once per connection rather than once per HMI.

7.2 PLC Proxy (HMI ↔ PLC proxy via WinCC Unified or S7-1500 OPC UA server)

For projects where the HMIs only need read access to a subset of PLC tags, expose the PLC data through an OPC UA server on the S7-1500 CPU (firmware V2.5 and above) and have the HMIs subscribe to the OPC UA tags. The OPC UA path is stateless from the HMI compile perspective, which removes the implicit compile dependency between HMI and PLC targets. This is the most robust long-term architecture for large multiuser projects because the HMI and PLC can be compiled and Checked-in independently.

7.3 Move secondary HMIs to a separate single-user project

If only one engineer maintains the secondary HMIs, split the master HMI and the secondary HMIs into separate single-user projects, linked by a PLC proxy device in the secondary project. The single-user project has no SQL server backend, no carry-over objects, and no Check-in collision. This is the architecture adopted in the field case that produced this article.

8. Multiuser Server Project Best Practices

Practice Reason Implementation
Keep Check-in deltas under 5 changed objects Reduces implicit compile time and the window for the 109971630 crash Stage work in small commits
Run TIA Portal on the server VM via console, not over VPN Eliminates VPN RPC timeout as a contributing factor RDP 3389 with clipboard and printer redirection disabled
Keep local session folder under 1 GB Avoids carry-over object bloat Archive and restore quarterly
Update TIA Portal to the latest hotfix Ensures 109971630 and related defects are patched Subscribe to Siemens IONews for TIA Portal
Use WinCC Unified OPC UA instead of S7 tag direct mapping Decouples HMI and PLC compile Expose tags on the S7-1500 OPC UA server
Validate the project on a local server before deploying to the multiuser server Catches compile defects on a controlled path Local server on 10.x subnet, identical TIA Portal build

9. Verification After the Fix

After applying the hotfix and rebuilding the server project from the archive, verify the fix in the following sequence:

  1. Open the restored server project and create a new local session.
  2. Modify one screen on the master HMI. Compile. Check in. Confirm successful commit and no crash.
  3. Modify one tag on a secondary HMI. Compile. Check in. Confirm success.
  4. Perform a cross-HMI edit: rename a tag, propagate to master and one secondary, compile both, check in. This is the original failing scenario. Confirm success.
  5. Force an implicit compile by initiating a Download to device. Confirm the compile completes without terminating TIA Portal.
  6. Inspect Windows Logs → Application for new Application Error 1000 events. None should be present.
  7. Check the local session folder size after the cycle. It should remain under 1 GB.

10. Troubleshooting Matrix

Symptom Likely Cause Fix
Crash on Check-in of HMI delta Compile defect from 109971630 Apply TIA Portal hotfix, archive and restore
Compile hangs at 95% then TIA Portal exits Implicit compile aborts on stale handle Same hotfix; check VPN RPC keepalive
Local session cannot be opened after crash Corrupt local session metadata Archive from a clean prior server revision, restore on server
Check-in succeeds locally but fails over VPN SQL transaction timeout on VPN Use RDP into the server VM for heavy Check-ins, raise RPC timeout on VPN
Cross-HMI tag rename crashes on secondary HMI Carry-over object from master overlay Refactor to HMI Common Connection or split to single-user project with PLC proxy
Application Error 1000 faulting module S7WCComp.dll Known defect Update to the TIA Portal build referenced in 109971630

11. Frequently Asked Questions

What is the SIMATIC Project Server default TCP port?

The SIMATIC Project Server listens on TCP port 4410 for client connections. TCP 102 is required for S7 online communication, and UDP 49152–65535 is used for PROFINET DCP discovery. Open all three ranges on the VPN for full TIA Portal multiuser functionality.

Can I recover a local session that was crashed during Check-in?

No. Once the TIA Portal process exits during Check-in, the local session is locked and cannot be opened. Open the prior good server revision as a new local session, archive the project, restore the archive on the server, and re-create the local session. Work that was committed before the crash is preserved in the server version history.

Does the VPN cause the TIA Portal crash, or is it the TIA Portal itself?

The crash is a TIA Portal compile defect documented in Siemens 109971630. The VPN is an amplifier because RPC timeouts extend the implicit compile window, but the crash will also reproduce on a local server. Apply the hotfix first, then address VPN MTU and firewall rules.

Which TIA Portal versions are affected by 109971630?

Siemens documents the affected versions in the entry itself; the entry covers V17 and V18 at the time of writing, with hotfixes shipped in the corresponding Update HF packages. V19 and later include the fix in base. Check the entry for the exact build numbers and corresponding Update level for your installed TIA Portal.

Should I keep using the multiuser server or switch to single-user projects?

If more than one engineer is committing changes to the same HMI simultaneously, the multiuser server is the only supported workflow. If a single engineer is the only one editing a group of HMIs, split those HMIs into a single-user project and link them with a PLC proxy or HMI common connection. The single-user project eliminates the SQL server, the Check-in commit, and the carry-over object accumulation.

What are carry-over objects in a TIA Portal local session?

Carry-over objects are device-level items (screens, tags, text lists) that were deleted in the editor view but persist in the local session cache. They are created when screens or tags are copied between HMI devices and then partially deleted. The cache grows with every overlay until it exceeds the implicit compile time budget, at which point the compile aborts and the Check-in crashes.

How large should a single Check-in delta be?

Keep each Check-in under 5 changed objects: one screen, one tag rename, one text list edit. Smaller deltas compile in under 60 s and complete the SQL transaction well within the 120 s RPC timeout window. Larger deltas are the documented crash trigger for 109971630.

Back to blog