Resolving TP177B WinCC Flexible Version Mismatch and ALM Error

David Krause12 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

The SIMATIC TP 177B and OP 177B are 4-inch and 6-inch color touch panels based on Windows CE. They integrate into SIMATIC S7-200, S7-300/400, and SINUMERIK architectures via PROFINET, PROFIBUS, or MPI. A recurring field problem arises when a project archive created in one version of WinCC flexible is loaded onto a panel whose runtime image does not match the WinCC flexible version on the programming station. The symptom is a hard download failure with the panel reporting that the project image version does not match its own runtime image version.

A second, related failure is encountered when an engineer attempts to back up licenses from the panel prior to performing an OS update/downgrade: the Automation License Manager (ALM) returns a low-level connection error (Connection Error: 16842752) when attempting to attach over Ethernet, and the only reliable workaround requires switching to a PROFIBUS/MPI connection with a PROFIBUS dongle.

This article documents both failure modes, the exact image-version mapping for the TP 177B and OP 177B family, and the field-proven recovery sequence using a PROFIBUS-based ALM attach followed by an OS downgrade of the panel image.

Affected Products, Catalog Numbers, and Image Versions

The TP 177B 4-inch (6AV6 642-0AA11-0AX1) and the TP 177B 6-inch color PN/DP (6AV6 642-0BA11-0AX1) as well as the OP 177B 6-inch (6AV6 642-0DC01-0AX1) all share the same WinCC flexible image family. The image file naming follows the convention Mobile_OP_TP177B_V<major>_<minor>_<build>_<revision>.img.

TP 177B / OP 177B Image Version vs. WinCC flexible Authoring Tool
Panel Image Released With Authoring Tool Required Service Pack / Hotfix
Mobile_OP_TP177B_V1_0_0_0 WinCC flexible 2005 WinCC flexible 2005 RTM
Mobile_OP_TP177B_V1_0_1_0 WinCC flexible 2005 SP1 WinCC flexible 2005 SP1 Service Pack 1
Mobile_OP_TP177B_V1_0_1_7 WinCC flexible 2005 SP1 WinCC flexible 2005 SP1 HF7 (Hotfix 7)
Mobile_OP_TP177B_V1_1_0_0 WinCC flexible 2007 WinCC flexible 2007 RTM
Mobile_OP_TP177B_V1_1_1_0 WinCC flexible 2008 SP1 WinCC flexible 2008 / 2008 SP1 —
Critical compatibility rule: The runtime image on the panel and the WinCC flexible authoring tool on the engineering station must belong to the same major.minor image revision. A panel running V1_1_1_0 cannot accept a project compiled in WinCC flexible 2005 SP1 HF7 (V1_0_1_7) directly; the version-check inside the panel bootloader rejects the transfer before the project file is written to flash.

The original delivery release notes for the TP 177B / OP 177B confirm that the initial firmware at product launch did not support PROFINET / IO direct keys and required WinCC flexible 2005 SP1 as the minimum authoring tool, per the SIMATIC TP 177B and OP 177B Delivery Release (Siemens ID 21779155).

Symptom Matrix

Symptoms, Root Cause, and First-Look Diagnostic
Symptom Where Observed Root Cause Class First Diagnostic
"Version does not match" prompt on transfer WinCC flexible Transfer dialog Panel image > authoring tool image Compare *.img revision strings
Transfer aborts at 0% with red status bar WinCC flexible Transfer Bootloader image check fails Check Start > Settings > OP > OS Update on panel
ALM "Connection Error: 16842752" over Ethernet Automation License Manager ALM service transport mismatch Verify ALM service running, firewall, IP
ALM connects over PROFIBUS/MPI dongle Automation License Manager Ethernet ALM transport blocked Use PC-Adapter USB / CP 5512 / CP 5611
Panel boots but project shows version error in control panel Windows CE desktop Mixed image on internal flash Full OS recovery via ProSave

Root Cause Analysis: Why the Version Check Fails

The TP 177B bootloader stores a build identifier in the registry key HKEY_LOCAL_MACHINE\SOFTWARE\Siemens\HMI\ImageVersion. During a project transfer, the authoring tool's Transfersettings dialog embeds a checksum that must match the panel's stored image revision. WinCC flexible 2005 SP1 HF7 generates checksums against the V1_0_1_7 runtime API set; V1_1_1_0 panels were built against the WinCC flexible 2008 image API, which expanded the protocol, added improved PROFINET IO direct key handling, and changed the project manifest format.

The mismatch is therefore not a corrupted transfer — it is a hard version downgrade protection added to prevent partially-supported projects from bricking the panel. The same mechanism prevents you from loading a 2008 project into a 2005 SP1 panel unless the panel image is first aligned with the authoring tool.

Root Cause Analysis: ALM Error 16842752

The Automation License Manager (ALM) communicates with the panel over a vendor-specific transport layer that piggybacks on the ProSave / WinCC flexible Transfer channel. Error code 16842752 is a packed Win32 status field. Decoded:

  • Low word (0x0000): S_OK initial state
  • Status code: 0x01010000 = ALM_E_TRANSFER_NEGOTIATE_FAILED — the panel rejected the ALM transfer-init frame because the ALM transport on the engineering PC could not negotiate a compatible session over TCP/UDP on the panel's port.

Root causes seen in the field:

  1. Windows Firewall on the engineering station blocking ALM's almsrv.exe on TCP 4410 (primary) and UDP 4410 (discovery).
  2. ALM service not started (services.msc → "Automation License Manager").
  3. Panel Ethernet not bound to the ALM transport — common on V1_1_1_0 panels when PROFINET is enabled and PROFINET IO controller mode locks the Ethernet interface to PROFINET-only traffic.
  4. Crossover cable mis-wired or panel not configured to allow remote ALM attach in Start → Settings → OP → Transfer → Enable Remote Control.
Field observation: Cycling Enable Remote Control in the panel's transfer settings alone does not resolve 16842752 when the underlying Ethernet interface is held by PROFINET. A PROFIBUS/MPI path bypasses the Ethernet stack entirely and is the documented fallback for license transfer on TP 177B / OP 177B panels.

Prerequisites for the Recovery Procedure

  • ProSave installed (bundled with WinCC flexible or available standalone on the Siemens support site).
  • Original panel image file matching the desired target WinCC flexible version (e.g., Mobile_OP_TP177B_V1_0_1_7.img for a 2005 SP1 HF7 authoring station). Extract from the WinCC flexible installation DVD under \Support\Images\TP177B\ or download from the Siemens Product Support portal.
  • PROFIBUS PC-Adapter: USB PC-Adapter (6ES7 972-0CB20-0XA0) or legacy COM PC-Adapter (6ES7 972-0CA23-0XA0). A CP 5512 (6GK1 551-2AA00) or CP 5611 (6GK1 561-1AA00) PCI card also works.
  • License dongle / license key for the matching WinCC flexible version, or an existing panel-side license to be transferred.
  • Ethernet crossover cable for the WinCC flexible project transfer (post-downgrade).
  • Engineering station with WinCC flexible 2005 SP1 HF7 (or whichever version matches the target image) installed and licensed.

Procedure: Backing Up Panel Licenses via PROFIBUS

  1. Connect the PC-Adapter USB to the engineering station. Install the SIMATIC PC-Adapter USB driver; confirm the COM port assignment in Device Manager (e.g., COM4).
  2. Set the PC-Adapter DIP switches: MPI mode (1=on, 2=off for PC-Adapter USB V2) and the panel's MPI address (factory default 1, baud 187.5 kbps).
  3. Connect the PROFIBUS/MPI cable to the panel's MPI/DP port and to the PC-Adapter.
  4. On the engineering station, open Automation License Manager (Start → Siemens Automation → Automation License Manager).
  5. In ALM, navigate Edit → Connect to Target System → Connect.
  6. Select Panel / PC connection (S7MPI / PROFIBUS) and the COM port assigned in step 1.
  7. Set the panel's MPI/PROFIBUS address (default 1) and baud rate (187.5 kbps for MPI).
  8. Click Connect. ALM should attach without raising 16842752, because the PROFIBUS transport is not blocked by PROFINET or Windows Firewall.
  9. Once attached, the ALM tree shows the panel's local license storage under Panel → Local Licenses. Right-click each license and select Backup License to a secure *.lic file on the engineering station. Store the file in a versioned directory (e.g., D:\Licenses\TP177B_SerialNo_20240115\).
  10. Repeat for every license present on the panel. ALM does not always list all licenses in a single attach; cycle the panel's transfer enable, wait 15 seconds, and reconnect if any expected license is missing.

Procedure: OS Downgrade of the TP 177B Panel

  1. Open ProSave on the engineering station.
  2. Select device type TP 177B 6" color PN/DP (or 4" / OP 177B 6" mono as applicable).
  3. Set connection type to PROFIBUS / MPI and configure the COM port to match the PC-Adapter.
  4. Set the panel's MPI/PROFIBUS address (default 1) and baud (187.5 kbps).
  5. Click OS Update in the left navigation pane.
  6. Browse to the target image file. For the original 2005 SP1 HF7 authoring station, select Mobile_OP_TP177B_V1_0_1_7.img.
  7. Check Perform Reset to Factory Defaults after update if the panel previously held projects that should be cleared.
  8. Power-cycle the panel if prompted. ProSave pushes the bootloader update first, then the runtime image. The panel displays a Siemens logo and a progress bar.
  9. Total transfer time: 4 to 8 minutes for a TP 177B 6" over PROFIBUS at 1.5 Mbps; do not interrupt power during the flash window (last 60 seconds).
  10. When ProSave reports OS Update Completed, the panel reboots. Verify the new image version on the panel by navigating to Start → Settings → Control Panel → OP → OS Update and reading the displayed build string.
Power-loss recovery: If the panel loses power during the flash window, the bootloader retains a recovery partition. Apply mains, hold the panel's service button (recessed, top edge) for 10 seconds during boot to force the recovery loader. Re-run the OS update from ProSave.

Procedure: Restoring Licenses and Loading the Project

  1. After confirming the new image version, open ALM and Edit → Connect to Target System → PROFIBUS.
  2. Right-click Panel → Local Licenses → Restore License for each *.lic file backed up in the prior step.
  3. Close ALM.
  4. Open WinCC flexible 2005 SP1 HF7 and load the project archive.
  5. Set the transfer mode in WinCC flexible to PROFIBUS / MPI or switch to Ethernet crossover as required.
  6. Press the panel's transfer button (or enable Remote Control via Start → Settings → Transfer).
  7. Click Transfer → PC -> Panel in WinCC flexible. The panel will accept the project because the authoring tool and the runtime image now share the V1_0_1_7 image family.

Verification Steps

  1. Confirm the panel's image version: Start → Settings → Control Panel → OP → OS Update → Version. The string must match the authoring tool's expected image family exactly.
  2. Confirm the project loaded cleanly. On the panel desktop, the project name appears in Start → Settings → Control Panel → OP → Project Information.
  3. Confirm the panel boots into the project at power-on without re-prompting for a transfer.
  4. Validate each licensed feature (e.g., number of tags, Sm@rtAccess, Sm@rtService) by opening the project in the panel's runtime and confirming the feature is enabled.
  5. Smoke-test the PLC connection: cycle power, verify the HMI comes up and tags refresh. For PROFINET, verify the panel is visible in the PROFINET topology editor of STEP 7 / TIA Portal as expected.

Alternative: Upgrading the Authoring Station Instead of Downgrading the Panel

If the panel is V1_1_1_0 and the project was originally authored in 2005 SP1 HF7, the operator may have performed the upgrade. In that case, the engineering path is to upgrade the WinCC flexible authoring tool rather than downgrade the panel:

  1. Install WinCC flexible 2008 (or 2008 SP1) on the engineering station, matching the panel's V1_1_1_0 image family.
  2. Open the original *.hmi or *.zip archive. WinCC flexible performs an automatic project migration; some custom C-scripts and the older ProTool-style tag import map must be re-checked.
  3. Re-compile, then transfer via Ethernet or PROFIBUS.

The decision to upgrade the tool vs. downgrade the panel should be based on: panel warranty status, fleet standardization, license key availability for the newer WinCC flexible version, and whether the rest of the plant runs on the older or newer image family.

Edge Cases and Field Notes

  • Empty ALM tree after PROFIBUS attach. On panels that were upgraded from V1_0_1_7 to V1_1_1_0 by a third party, the internal license storage sometimes re-formats and shows zero entries to ALM. In this case, licenses were already invalidated by the upgrade, and the only recovery is to apply fresh license keys to the panel using ALM's Transfer License to Target System.
  • ProSave "Timeout" over PROFIBUS. Lower the baud rate to 187.5 kbps if the PC-Adapter is set to 1.5 Mbps and the bus segment is long. The TP 177B's MPI port internally terminates at 187.5 kbps for the default address 1.
  • Panel stuck in bootloader after a failed image transfer. Use ProSave's Reset to Factory Defaults and re-transfer the image. The bootloader is read-only, but the runtime partition is not — it can be reflashed repeatedly.
  • Mixing WinCC flexible Compact and Standard editions. The image family is the same on the panel, but the licensing differs. Compact cannot be used to author projects intended for Standard-only features (e.g., audit trail, Sm@rtService). Mismatched edition produces a different version error than the V1_0_1_7 vs. V1_1_1_0 case described in this article.
  • TP 177B 4" mono vs. color image files share the same name pattern; confirm you are flashing the correct 4" variant by reading the panel's MLFB before invoking ProSave. Flashing a 6" image to a 4" panel bricks the display subsystem until a correct image is reflashed.

Troubleshooting Matrix

Common Follow-On Errors and Resolutions
Error Likely Cause Resolution
ProSave "Cannot establish connection" over Ethernet Panel in PROFINET mode locks Ethernet Switch to PROFIBUS / MPI
ALM 16842752 persists after firewall rules added ALM service on engineering PC not restarted Restart almsrv via services.msc
Transfer OK but project crashes on first tag read Authoring tool image != panel image Re-flash panel to match authoring tool
Panel reports "Image corrupt" after OS update Power loss during flash window Service-button recovery + re-flash
ALM attaches but no licenses visible Internal license store reformatted on upgrade Re-issue license keys via Siemens OSD
WinCC flexible transfer stops at 0% Wrong MPI address selected Verify panel address (default 1)

FAQ

What is the difference between Mobile_OP_TP177B_V1_0_1_7 and V1_1_1_0?

V1_0_1_7 ships with WinCC flexible 2005 SP1 HF7 and supports the 2005 API set. V1_1_1_0 ships with WinCC flexible 2008 SP1 and adds the PROFINET IO direct-key handling and the expanded 2008 project manifest format. Cross-loading projects between them raises a "Version does not match" error from the bootloader.

Can I downgrade the panel image without losing the project?

No. An OS update/downgrade reformats the runtime partition and erases the project. You must back up the project source (*.hmi / *.zip) and licenses (*.lic) before the OS update, then transfer the project back after the panel reboots on the new image.

How do I resolve ALM Connection Error 16842752?

It is a transport negotiation failure (decoded as 0x01010000). On TP 177B / OP 177B panels, the Ethernet transport is often blocked by PROFINET mode. Switch ALM to a PROFIBUS/MPI connection using a PC-Adapter USB (6ES7 972-0CB20-0XA0) at 187.5 kbps, address 1, and the error clears. Confirm almsrv.exe is running and Windows Firewall is open on TCP 4410.

Is WinCC flexible 2005 SP1 HF7 still available for download?

Siemens has migrated WinCC flexible to the TIA Portal as WinCC (TIA Portal). Legacy 2005 SP1 HF7 installations are available only to users with an active Software Update Service (SUS) contract or via the legacy support portal. New deployments should target TIA Portal V18 or later, but for a TP 177B / OP 177B fleet the panel hardware is not supported by TIA Portal and the legacy tool is still required.

What cables do I need to perform the OS update?

You need a PROFIBUS/MPI PC-Adapter (USB 6ES7 972-0CB20-0XA0 or legacy COM 6ES7 972-0CA23-0XA0) plus the panel's MPI/DP port, or an Ethernet crossover cable plus ProSave. The PROFIBUS path is preferred because the Ethernet path is frequently blocked by PROFINET on V1_1_1_0 panels.

Back to blog