Problem Description
When two Windows PCs are configured with WinCC V6.0 (or WinCC V6.0 SP3) and SIMATIC NET PC software, a common commissioning failure is the inability of an OPC client on PC2 to enumerate or browse the OPCServer.WinCC instance exposed by PC1. The OPC server does not appear in the client-side "Add OPC Server" dialog of the SIMATIC NET configuration tool, the WinCC Explorer, or any external OPC client such as OPC Scout, even though both stations are reachable on the network and the WinCC runtime is running locally on PC1.
The failure mode is consistent: the DCOM server enumeration handshake never completes, the OPCEnum service returns no remote servers, and the user is unable to add PC1's WinCC runtime as a remote OPC DA source in PC2's WinCC project. Because classic OPC DA depends entirely on COM/DCOM for both enumeration and runtime data transfer, the root cause is almost always in the COM security layer, the SIMATIC NET OPC security add-on, or the Windows firewall state of the involved stations.
Architecture and Protocol Stack
WinCC V6.0 implements the OPC Data Access 1.0/2.0/3.0 specification using COM (Component Object Model) and DCOM (Distributed Component Object Model) as the transport. Unlike OPC UA, which is message-oriented over TCP and HTTP, OPC DA relies on:
-
OPCEnum (service name
OPCEnum, display name "OPC Server Enumerator") for server discovery viaIRemoteServerover DCOM. -
DCOM activation and call-back for both the initial
IOPCServerList::EnumClassesOfCategoriescall and the subsequentIUnknownmarshaling into the client process. - Windows RPC (port 135 + dynamic ephemeral range) as the underlying transport. The RPCSS service must be running on both stations.
For each WinCC project running on PC1, the WinCC runtime registers an OPC DA 3.0 server under the ProgID OPCServer.WinCC. Because these are COM in-process servers hosted by CCOPCSvr.exe, every client connection results in a DCOM activation of that executable inside the security context of the configured launch user.
Reference: WinCC V6.0 Communication Manual, section "Configuring WinCC Stations for OPC" (Siemens entry ID 21320307).
Prerequisites
Before changing any DCOM configuration, verify the following baseline. Missing prerequisites are responsible for the majority of "OPC server not found" failures reported in the field.
| Component | Required State on PC1 (Server) | Required State on PC2 (Client) |
|---|---|---|
| Operating system | Windows XP SP2 or Windows Server 2003 (for full DCOMCNFG security panel); Windows 7 / Server 2008 R2 supported by WinCC V6.0 SP3 hotfix matrix | Same as PC1 |
| WinCC | V6.0 SP3 or later, project running, runtime active | V6.0 SP3 or later, project open in WinCC Explorer |
| SIMATIC NET | PC software version compatible with WinCC V6.0 (e.g., SIMATIC NET V6.4); OPC server component installed | PC software version matching PC1; OPC client component installed |
| Network | Static IP, ping reachable from PC2, NetBIOS over TCP/IP enabled if using computer names | Same subnet, name resolution of PC1 (hosts file, WINS, or DNS) |
| User accounts | Local or domain user with consistent credentials on both PCs (mandatory for DCOM pass-through authentication) | Identical username/password OR same domain user used to launch OPC client |
| Services | RPCSS = Automatic, OPCEnum = Manual (started on demand), WinCC Runtime = Automatic, S7DOS / SIMATIC NET service = Automatic | RPCSS = Automatic, OPCEnum = Manual, SIMATIC NET service = Automatic |
| Windows Firewall | File and Printer Sharing exception enabled; COM/DCOM exception enabled OR explicit TCP 135 + dynamic RPC ports opened | Same |
Root Cause Analysis
Five distinct failure paths account for nearly every reported "I cannot find OPCServer.WinCC in the network" scenario. They must be ruled out in order because each subsequent layer assumes the previous is healthy.
-
OPCEnum not running or unreachable. The client first queries
\\<PC1>\Root\CIMV2via WMI / DCOM to ask OPCEnum for the list of registered OPC DA servers. If theOPCEnumservice is stopped or blocked by the firewall, the enumeration returns an empty list — even thoughOPCServer.WinCCis correctly registered on PC1. -
DCOM access permissions on PC1 deny anonymous / interactive launch. By default, Windows restricts DCOM activation to the launching user. If the WinCC OPC server application is configured to "run as the launching user" or "interactive user" without the appropriate access/launch permissions for the remote user account, IRRPCE returns
E_ACCESSDENIED(HRESULT 0x80070005). -
SIMATIC NET OPC security not configured. SIMATIC NET installs an additional access-control layer in the registry path
HKLM\SOFTWARE\SIEMENS\SIMATIC NET\OPCS\Securitythat gates the COM activation separately from the DCOMCNFG settings. Without this, even a correctly configured DCOMCNFG can still refuse the OPC connection. -
User context mismatch. DCOM uses NTLM / Kerberos to pass the calling security context to the remote server. If the client user is a local account on PC2 but a domain account is required on PC1, the activation fails with
CO_E_FAILEDTOAUTHENTICATE(HRESULT 0x8000401A). - Windows firewall or anti-virus product blocking RPC dynamic ports. Even with the DCOMCNFG firewall exception for "COM/DCOM", third-party endpoint protection products frequently re-block the ephemeral range 49152–65535 (or 1024–5000 on XP/2003), preventing the marshaled interface transfer.
Solution — Server-Side DCOM Configuration (PC1)
Perform the following steps on the PC hosting the WinCC runtime (PC1, the OPC server). After each step, restart the WinCC runtime so it re-registers its COM objects.
- Open Component Services:
Start → Run → dcomcnfg(or viaControl Panel → Administrative Tools → Component Services). - Expand
Console Root → Component Services → Computers → My Computer. - Right-click
My Computer → Propertiesand confirm the COM Security tab is visible (it requires Windows XP SP2 or later). Configure the four machine-wide defaults:-
Access Permissions → Edit Limits: allow
ANONYMOUS LOGON,Everyone, and the specific domain / local user that PC2 uses. - Launch and Activation Permissions → Edit Limits: same accounts, full allow.
- Access Permissions → Edit Default: same accounts.
- Launch and Activation Permissions → Edit Default: same accounts.
-
Access Permissions → Edit Limits: allow
- Navigate to
DCOM Config. Locate the entry whose Application ID matches the WinCC OPC server (ProgIDOPCServer.WinCC). Right-click → Properties:- General tab: Authentication Level = None for testing; revert to Connect once verified.
- Location tab: enable "Run application on the following computer"; confirm "Run application on this computer" remains checked.
-
Security tab: customize all three sections (Launch & Activation, Access, Configuration) and grant full control to
Everyonefor first-pass testing. Lock down later. - Identity tab: select The interactive user for the typical scenario, or This user with a dedicated service account if the client runs headlessly.
-
Endpoints tab: select "Use any available" or "TCP/IP". Static endpoint configuration is recommended for firewall traversal — e.g., port 5000 with protocol
ncacn_ip_tcp.
- Repeat for the
OPCEnumCOM application (CLSID{13486D51-4821-11D2-A494-3CB306C10000}) — it must allow remote activation or remote enumeration will silently fail. - Restart the
OPCEnumservice and the WinCC Runtime service on PC1.
Everyone is acceptable only for bench testing. In production, restrict to the specific service account and document the change in the plant's cyber-security baseline.Solution — Client-Side DCOM Configuration (PC2)
- Open
dcomcnfgon PC2. - On
My Computer → Properties → COM Securitytab, under Default Security → Edit Default, ensure the same user accounts from the server side have Launch and Activation rights on the client as well. Some installations require both directions to be granted. - On
My Computer → Properties → Default Protocols, confirm "Connection-oriented TCP/IP" has been moved to the top of the property order list. - Add a static endpoint for
OPCEnumon PC2 so that the firewall rule for inbound 135 plus the chosen static port is sufficient.
Solution — SIMATIC NET OPC Security Configuration
The SIMATIC NET OPC add-on enforces an additional access-control list stored in the registry. Without populating it, even a perfectly configured DCOM layer will refuse the activation. Configure on PC1:
- Open SIMATIC NET Configuration Console (
Start → Programs → SIMATIC NET → Configuration Console). - Navigate to
PC Station → Applications → OPC. - Right-click the OPC entry → Properties → Security (on older localizations the menu reads "OPC Settings" or "OPC Properties"; on older builds the Security tab is not present at all — in that case the SIMATIC NET hotfix must be applied).
- Click Add and enter
ANONYMOUS LOGON(German:ANONYME ANMELDUNG). Grant Read, Write, and Execute. - Repeat for the domain / local account used on PC2. Click Apply.
- Restart the SIMATIC NET OPC service (
S7OPCSXorOPC.SimaticNET, depending on SIMATIC NET version).
SIMATIC NET OPC Server; V6.4 and later split it into S7DOS Helper, OPC.SimaticNET, and S7OPCSX. Verify with sc query | findstr /i "opc s7 simatic".Verification with OPC Scout
OPC Scout is shipped with SIMATIC NET and is the canonical loopback / cross-machine validation tool. Always validate the configuration in this order before re-opening the WinCC Explorer:
- On PC1, start OPC Scout (
Start → Programs → SIMATIC NET → OPC Scout). ConfirmOPC.SimaticNETappears in the local server list and reads a known WinCC tag. This proves the server side is healthy. - On PC2, start OPC Scout. In the OPC Scout dialog, click ... next to "OPC Server" and choose Network. The list must show the WinCC runtime on PC1 with ProgID
OPCServer.WinCC. - Double-click the remote server entry; add a tag, click Read. A numeric / boolean value matching the runtime confirms end-to-end OPC DA functionality.
- If PC2 cannot see PC1, fall back to Direct Connection: enter the ProgID and the hostname as
\\PC1\OPCServer.WinCC. If this works but network enumeration does not, the failure is in OPCEnum, not in DCOM authentication. - Repeat with both stations restarted and logged in with the same domain user.
Troubleshooting Matrix
| Symptom | Likely Cause | Diagnostic Command / Location | Corrective Action |
|---|---|---|---|
| Remote OPC server list is empty in OPC Scout | OPCEnum stopped or firewall blocks TCP 135 |
sc \\PC1 query OPCEnum; telnet PC1 135
|
Set OPCEnum startup to Automatic; open firewall exception for 135 and dynamic RPC range |
| "Access denied" HRESULT 0x80070005 when connecting | DCOM launch permission missing for remote user | DCOMCNFG → OPCServerWinCC → Security tab | Add remote user with full Launch & Activation and Access rights |
| Server visible in OPC Scout but adding tags fails | SIMATIC NET OPC security missing ANONYMOUS LOGON | SIMATIC NET Configuration Console → OPC → Security | Add ANONYMOUS LOGON with full rights; restart SIMATIC NET OPC service |
| Works locally on PC1 but not from PC2 | Client-side DCOM default launch permissions | DCOMCNFG on PC2 → My Computer → COM Security → Edit Default | Add ANONYMOUS LOGON to client-side launch defaults |
| Works from PC2 using local admin account, fails with operator account | User context mismatch / Kerberos delegation not configured |
whoami /all on both stations; Event Viewer Security log |
Use identical domain user; or enable "Use any authentication level" in DCOMCNFG |
Connection succeeds but tags return OPC_QUALITY_BAD with LastKnownValue
|
Subscription / async read-back lost — common on Panels (RT) and constrained OPC UA sessions | OPC Scout → Monitor; WinCC Channel Diagnostics | Check Max Items per Subscription, network MTU, multicast filters |
| WinCC host name resolves on PC1 but not PC2 | WINS / DNS not synchronized; NetBIOS disabled |
nslookup PC1; nbtstat -a PC1
|
Add static entry in %SystemRoot%\system32\drivers\etc\hosts on PC2 |
| OPC server registration visible in registry but absent in DCOMCNFG | WinCC runtime not started, so COM apartment not created | WinCC Explorer → Active → Start Runtime | Start runtime; wait 30 s; refresh DCOMCNFG |
Modernization Path — OPC UA over WinCC 7.x / TIA Portal WinCC
The configuration footprint described above exists because WinCC V6.0 relies exclusively on COM/DCOM. From WinCC V7.0 onward and across the TIA Portal WinCC Professional / Comfort / RT families, OPC UA is available as a first-class server with built-in certificate-based security, binary TCP transport on port 4840, and discovery URLs of the form opc.tcp://<host>:4840. Migrating to OPC UA eliminates every DCOM configuration step and the firewall complexity.
Known caveats observed on WinCC Professional / Panel RT OPC UA servers:
- The discovery URL
opc.tcp://<hostname>:4840must resolve to a routable IPv4 address. Hostname-based discovery requires a working DNS or hosts entry on the client; otherwise the client falls back toLastKnownValuewith qualityUncertainand reduced operation count. - The server enforces a maximum items-per-subscription. Older Panel RT firmware rejects requests larger than 64 items per
CreateSubscription. If the client batches 300 items, the server silently reduces the operation count. Adjust the subscription size on the OPC UA client side (UA Expert, Kepware, or SIMATIC NET OPC UA client). - Certificate trust must be established on first connect: copy the WinCC OPC UA server certificate into the client's trusted-certificate store under
%ProgramData%\OPC Foundation\CertificateStores\UA Applications\certs(or the SIMATIC NET equivalent). Without this, every call returnsBadCertificateUntrusted(HRESULT 0x801A0000 in the UA mapping).
References: Siemens Industry Online Support; OPC Foundation — What is OPC?
Firewall and Port Reference
| Port | Protocol | Direction | Purpose |
|---|---|---|---|
| 135 | TCP | Inbound / Outbound | RPC endpoint mapper (mandatory) |
| 49152–65535 | TCP | Inbound / Outbound | Dynamic RPC range (Windows Vista / 7 / Server 2008 default) |
| 1024–5000 | TCP | Inbound / Outbound | Dynamic RPC range (Windows XP / 2003 default) |
| 5000 (recommended static) | TCP | Inbound | OPCEnum static endpoint to avoid dynamic range |
| 4840 | TCP | Inbound | OPC UA binary (modern WinCC only) |
| 137 / 138 | UDP | Both | NetBIOS name resolution (optional but helpful) |
Safety and Operational Notes
Everyone full-control permissions is a known attack vector (e.g., CVE-2003-0813, CVE-2004-0116, MS05-012, MS05-043). Never deploy a WinCC V6.0 station with permissive DCOM settings on a network segment reachable from corporate IT, OT-DMZ, or the internet. Place the stations on an isolated OT subnet, behind a Layer-3 firewall with explicit port rules, and restrict DCOM access to the documented service account only.OPCServer.WinCC changes between major versions, and stale registry entries will cause the enumeration to succeed while tag access fails.FAQ
Why does OPCServer.WinCC appear locally but never remotely?
Because remote enumeration requires the OPCEnum service on the server, both DCOM and SIMATIC NET OPC security grants for the remote user, and at least one open RPC port (typically TCP 135 plus a dynamic port). When any of these three is missing, local access still works because it uses an in-process COM call rather than DCOM activation.
Do I still need DCOM if I upgrade to WinCC V7.4 with OPC UA?
No. OPC UA uses TCP/4840 with binary or HTTPS transport and X.509 certificate trust; DCOM is not used. However, OPC DA connections inside the same project still depend on DCOM unless you explicitly convert all DA tags to UA tags.
What user account should the WinCC OPC server run as?
Use a dedicated domain service account that is a member of the local SIMATIC NET and WinCC user groups on both stations. Identical credentials on PC1 and PC2 eliminate the Kerberos / NTLM fallback failures that produce E_ACCESSDENIED errors during DCOM activation.
How do I confirm OPCEnum is the actual blocker?
Run telnet PC1 135 from PC2. A blank screen confirms the RPC endpoint mapper is reachable. Then run sc \\PC1 query OPCEnum and confirm the service state is RUNNING. If the telnet succeeds but OPC Scout shows no remote servers, the failure is in OPCEnum registration or the SIMATIC NET security add-on, not in DCOMCNFG.
Can an OPC UA client read more than 64 items from a Panel RT OPC UA server?
Older Panel RT firmware caps the maximum items per CreateSubscription at 64. If the client requests 300 items, the server reduces the operation count and the extra items return Uncertain — LastKnownValue. Reduce the batch size in the OPC UA client (UA Expert, SIMATIC NET UA client) to 64 or fewer and re-test.