Resolving WinCC Flexible Runtime License Version Mismatch

David Krause11 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Description

A common field failure on SIMATIC Panel PC installations (for example, an OP12 panel with a PCU50 industrial PC) is the inability to authorize a WinCC flexible Runtime after the engineering station used a newer configuration software than the available license. The panel either refuses to start, logs a license error, or runs in trial/demo mode and stops after the timeout elapses.

Typical symptoms reported by maintenance engineers:

  • Error message: "No valid WinCC flexible Runtime license was found" when the PC RT service starts.
  • Error message: "The Runtime version does not match the license" after retransfer of a project.
  • Successful compilation and download in WinCC flexible 2008 ES, but authorization fails because the installed Automation License Manager holds a 2007 Runtime license key.
  • Message "No matching upgrade license keys were found" when running the upgrade wizard with the wrong source/target license pair.

This article documents the version compatibility matrix, the underlying legal and technical restrictions, and the four supported recovery paths.

Root Cause: Configuration Software and Runtime Coupling

WinCC flexible ties the Configuration Software (CS) version used to compile the project, the Runtime (RT) version installed on the target, and the license key version checked by the Automation License Manager. The three values must agree within tightly constrained rules.

Hard rule: The major revision of the Runtime must match the major revision of the Configuration Software that produced the project. A project compiled by CS 2008 will not run on a Runtime 2007, regardless of which license is installed.

Siemens differentiates between major versions (2005, 2007, 2008, 2008 SP2) and Hotfix levels (HF1, HF2, HF3, HF4, etc.) within a major version. The hotfix level only loosely affects licensing:

Scenario CS Version RT Version License Result
Match (recommended) 2007 HF3 2007 HF3 2007 RT Authorizes, runs
Hotfix offset 2007 HF3 2007 HF2 2007 RT Authorizes, runs in most cases
Major mismatch 2008 2007 2007 RT Fails - license rejected
Major mismatch 2007 2008 2008 RT Fails - license rejected
Downgrade via "Save as" 2008 (saved as 2007) 2007 2007 RT Authorizes if re-imported into CS 2007 and recompiled

Versioning Model and Hotfix Behavior

From WinCC flexible 2007 Hotfix 3 onward, Siemens introduced a narrow compatibility window: a 2007 HF3+ Runtime can boot and execute a project compiled by an earlier 2007 hotfix level (HF1 or HF2) and even run with a 2005 Runtime license. This is documented in the German release note:

"Ab dem Hotfix 3 ist eine 'WinCC flexible 2007 Runtime' auch mit einem Lizenz Key der 'WinCC flexible 2005 Runtime' ablauffähig. Hierfür muss das Hotfix 3 oder höher auf dem Runtimesystem installiert sein. Die Nutzung des Lizenz Keys aus der Vorgängerversion ist ausschließlich für Test- bzw. Inbetriebnahmezwecke gedacht."

Translation: From Hotfix 3 onward, a WinCC flexible 2007 Runtime will execute with a 2005 Runtime license key, provided Hotfix 3 or higher is installed on the Runtime system. Use of the prior-version license key is permitted exclusively for test and commissioning purposes.

The downrev-license path is an engineering concession only. Siemens explicitly states it must not be used in production. OEMs supporting long-life equipment must treat the policy as a constraint, not a loophole.

The same hotfix leniency does not extend across major versions. A 2008 project will not run on a 2007 Runtime, and a 2007 RT license cannot authorize a 2008 RT installation.

Impact on OP12 with PCU50

The SIMATIC PCU50 (PC Unit 50) is the backplane-mounted industrial PC supplied with early SIMATIC Panel PCs and is typically loaded with Windows XP Embedded or Windows Embedded Standard 2009. The OP12 is the 12-inch operator panel connected to the PCU50. The WinCC flexible PC Runtime is installed on the PCU50's operating system, while the project is compiled in the engineering station and transferred to the PCU50 over Ethernet or PROFIBUS.

Failure mode in this topology:

  1. Engineer builds the project in WinCC flexible 2008 ES on the development PC.
  2. Project compiles successfully and transfers to the PCU50 without error.
  3. On startup, the PC Runtime cannot find a valid license because the only available license key was purchased for WinCC flexible 2007 Runtime (often an older delivery or a reused license from a 2007 fleet).
  4. Runtime enters countdown mode or refuses to launch.

The license is independent of the panel hardware - the OP12 has no role in license validation. The PCU50 is the host that runs the RT and stores the license key, typically under C:\Program Files\Siemens\Automation\WinCC flexible\WinCC flexible 2008\RT\License\ or the equivalent 2007 path.

Solution Path 1: Exchange the Runtime Package with Siemens

If the unopened Runtime media or backup is still available and within the Siemens exchange policy window, it can be returned and replaced with the correct major version.

  1. Locate the original WinCC flexible Runtime DVD or downloaded installer that was never opened (license card must be intact).
  2. Contact your Siemens regional sales or the Siemens Industry Online Support hotline for an RMA/return.
  3. Provide the original license number and proof of purchase; Siemens will issue a 2008 Runtime for a service fee.
  4. Install the new Runtime on the PCU50, transfer the original 2008 license key to the Automation License Manager, and start the project.
The Runtime media must be unopened. A used or partially installed media cannot be exchanged because the binding between the license key and the media has been activated.

Solution Path 2: Purchase a 2007 to 2008 Upgrade Package

The standard OEM-supported recovery is to purchase a version upgrade license. The Automation License Manager supports an in-place upgrade of an existing key when a matching upgrade key is present.

Parameter Value
Source license WinCC flexible 2007 Runtime, 2048 PowerTags (or matching tag count)
Required upgrade key WinCC flexible 2007 to 2008 Runtime Upgrade, same tag class
Source identifier CoL (Certificate of License) number on the original USB stick or license card
Target identifier CoL number on the upgrade delivery

Step-by-Step Upgrade Procedure

  1. Install the new WinCC flexible 2008 Runtime on the PCU50 (do not uninstall 2007 first - the Automation License Manager can hold both keys simultaneously during transition).
  2. Insert the upgrade license USB dongle (or run the license transfer) on the target PC so the new upgrade key is written to the local hard drive. The default location is C:\Program Files\Siemens\Automation\Automation License Manager\Bin\almsrvx.exe managed store, or the dedicated C:\Siemens\License\ folder if configured.
  3. Open Automation License Manager from Start → Siemens Automation → Automation License Manager.
  4. Confirm that both the original 2007 license and the upgrade license are visible in the list. If only the upgrade license is listed, transfer the 2007 license to the local drive first using License → Transfer with the original USB stick.
  5. Select the original 2007 Runtime license in the license list. Do not select the upgrade key.
  6. From the menu, select License → Upgrade License.
  7. Choose the matching upgrade license from the drop-down list. Tag count, type (PC Runtime vs. Panel Runtime), and major version must match exactly.
  8. Click Upgrade. The original 2007 key is replaced in the local license store with an upgraded 2008 key that retains the original CoL lineage.
  9. Remove the upgrade USB dongle; the upgraded license remains on the hard drive.
  10. Restart the WinCC flexible Runtime service and verify the project starts.
Troubleshooting the "No matching upgrade license keys were found" error: this message means the Automation License Manager cannot pair the selected source key with an upgrade key that has the same tag count, runtime class, and major version. Verify: (a) the upgrade key is in the local store, not on a remote license server, (b) the tag count matches (e.g. 2048 PowerTags upgrade to 2048 PowerTags), and (c) the upgrade is for the correct product line (PC Runtime upgrade will not pair with a Panel Runtime source).

Solution Path 3: Downrev the Project to 2007

If a 2008 upgrade license is not procurable, the project itself can be rolled back to a 2007-compatible source tree. This path requires the engineer to have both CS 2008 and CS 2007 installed (or virtualized).

  1. Open the project in WinCC flexible 2008.
  2. Use Project → Save As Version and select WinCC flexible 2007 as the target. The Save As process strips features introduced after 2007 and renames internal references.
  3. Open WinCC flexible 2007 on the same machine (or a VMware image).
  4. Open the just-saved 2007 project file. The project will be upgraded internally by the 2007 CS to its native format.
  5. Recompile the project in 2007 CS. The resulting Runtime file matches the 2007 license family.
  6. Transfer the recompiled project to the PCU50. The 2007 license authorizes the Runtime.
Features that did not exist in 2007 (for example, certain 2008-only controls, libraries, or screen templates) will be removed or downgraded silently during the Save As. Verify all screens, scripts, and alarms after the downrev. Use a diff tool against the backup of the original 2008 project.

Solution Path 4: Multi-Version Engineering Workstation via VMware

Many OEMs support long-life PC Runtime installations across multiple WinCC flexible versions. The practical approach is to run each major CS version in an isolated Windows XP or Windows 7 virtual machine:

  1. Create one VMware Workstation or VMware Player VM per CS version (2005 SP1, 2007, 2008 SP2).
  2. Disable license borrowing or transfer the license between host and VM using Automation License Manager remote view.
  3. Compile the project inside the matching VM to guarantee the binary Runtime file is signed against the correct CS version.
  4. Transfer the compiled RT file to the physical PCU50 or any other Runtime target.

This eliminates the Save As round-trip and gives the engineer a clean CS for each major revision when supporting legacy equipment.

Hotfix Compatibility Decision Matrix

CS HF Level RT HF Level Compatible? Notes
2007 HF1 2007 HF1 Yes Baseline match
2007 HF2 2007 HF3 Yes RT newer than CS works
2007 HF3 2007 HF2 Yes CS newer than RT works
2007 HF4 2007 HF1 Conditional Test for graphics or script regressions
2008 (any HF) 2007 (any HF) No Major version mismatch
2008 SP1 2008 Conditional SP level must match between CS and RT

Verification Procedure

After applying any of the four solution paths, run the following verification sequence on the PCU50:

  1. Open Automation License Manager on the PCU50 and confirm the correct major version Runtime license is listed as valid (green check) in the local store.
  2. Verify the installed Runtime version: navigate to Start → Programs → Siemens Automation → WinCC flexible → About on the PCU50. Confirm the major version matches the project.
  3. Start the Runtime from the start menu or the auto-start service. Observe the splash screen - it should not show a license countdown.
  4. Log in as the operator and exercise at least one screen change, one alarm, and one tag write to confirm full functionality.
  5. Reboot the PCU50 cold (power cycle) and confirm the Runtime starts in authorized state without manual intervention.
  6. Check the WinCCflexibleRT.log in the Runtime install directory for any E00xx license error codes. A clean log is the strongest verification.

Common License Error Codes and Fixes

Error Code / Message Meaning Fix
No matching upgrade license keys were found Source/upgrade tag count or class mismatch Re-check tag count, verify upgrade is for same product class (PC RT vs. Panel)
License is for an older version Major version mismatch Apply Solution Path 2 or Path 3
License server not reachable Network dongle / license server down Restore network or move license locally
Invalid license signature License store corruption Re-transfer license, re-activate via ALM
Runtime in demo mode, 14 days remaining No valid key present Transfer the correct key or remove demo counter via valid license

Preventive Recommendations for OEMs

  • Tag the license asset. Record the CoL number, major version, and tag count in the project documentation. Storing the CoL in the HMI project header avoids field surprises.
  • Bundle CS and RT versions per machine. Deliver the engineering PC with the exact CS version that matches the RT license installed on the target fleet.
  • Maintain a VMware library. Keep at least CS 2005, 2007, 2008 SP2, and TIA Portal WinCC images to recompile any legacy project that comes back for service.
  • Procure upgrade keys during PC RT rollout, not after. Lead time for upgrade packages is several weeks; plan for it during the initial bill of materials.
  • Avoid relying on the HF3 downrev license workaround in production. Treat it as a commissioning emergency stop-gap only.

FAQ

Will a WinCC flexible 2007 Runtime license authorize a project compiled with CS 2008?

No. The Configuration Software and Runtime major versions must match. A 2008-compiled project requires a 2008 Runtime and a 2008 (or upgraded) license. Hotfix offsets within a major version are tolerated, but major version crossings are rejected by the Automation License Manager.

Can I use a 2005 Runtime license with a 2007 HF3+ Runtime?

Yes, but only for test and commissioning. Siemens' release note for 2007 HF3 explicitly allows booting a 2007 HF3+ Runtime with a 2005 RT license key, but states the arrangement is exclusively for Inbetriebnahme and test purposes. Do not deploy this combination in production equipment.

What does "No matching upgrade license keys were found" mean when running the ALM upgrade wizard?

It means the Automation License Manager cannot pair the selected source key with an upgrade key that has the same product class (PC Runtime vs. Panel Runtime), tag count (e.g. 2048 PowerTags), and major version lineage. Verify both keys are in the local store and that the upgrade is a same-class, same-count upgrade to the correct target major version.

Is the OP12 panel involved in license validation on a PCU50?

No. The OP12 is a passive display/operator panel driven by the PCU50. All license checks are performed by the WinCC flexible PC Runtime and the Automation License Manager running on the PCU50's Windows Embedded operating system.

Can I run multiple WinCC flexible CS versions on the same engineering PC?

Yes. Siemens supports side-by-side installation of different major versions. Many OEMs run each CS major version in a dedicated VMware Workstation image to avoid DLL conflicts and to keep a clean license state for each fleet generation. The compiled Runtime file can then be transferred to any physical PCU50 or PC-based Runtime host.