Resolving WinCC OPC Quality Code 8 with Softing INAT OPC Server and Pilz Safety PLCs
When integrating a Softing (formerly INAT) OPC Server Ethernet with Siemens SIMATIC WinCC to read data from a Pilz Safety System (PSS), the SCADA runtime may continue to display stale or last-known values for a tag even though the underlying QualityCode has degraded to 0x08 (OPC_QUALITY_BAD_COMM_FAILURE). This article documents the root cause of the discrepancy between the OPC quality flag and WinCC's tag status evaluation, and provides engineering-validated solutions for surfacing the fault to operators in graphics, logging, and alarms.
1. Problem Description
A common field scenario reported on multiple Pilz-WinCC integration projects is the following sequence:
- The WinCC server is configured to use the OPC channel and connects to the local Softing INAT OPC-Server Ethernet instance as a Data Access (DA) client.
- The INAT OPC server is bound to a Pilz PSS PLC over Ethernet (e.g. PSS 4000 with Ethernet/IP, Modbus/TCP, or Profinet, depending on the Pilz gateway).
- The operator pulls the network cable on the Pilz PLC side or the PLC is powered off.
- The INAT OPC server detects the lost connection within its configured watchdog/timeout window (typically 1–5 seconds) and updates the
QualityCodeof every cached item to0x08. - WinCC receives the new quality code on the next update cycle. Hovering over the tag in the Graphics Designer shows a tooltip with the value
8, but WinCC does not fire "Evaluate tag status" actions, output mappings, or connection-loss color animations on the object. - A direct VBS read of
HMIRuntime.Tags("Tag_1").QualityCodereturns8, butHMIRuntime.Tags("Tag_1").Stateremains0(OK) because the WinCC channel driver (OPC) still reports an active session to the OPC server. - Result: the HMI displays a value that is potentially minutes or hours old, with no visual or audible indication of the loss of communication.
For comparison, when an integrated S7 channel driver is used directly between WinCC and a SIMATIC S7 PLC, WinCC injects a sentinel string "- No connection to the PLC" into the tag value tooltip as soon as the driver detects the CP/PLC link down. This is the behavior operators expect, and its absence under OPC is the principal complaint.
2. Root Cause Analysis
WinCC has two completely independent mechanisms for surfacing tag health to the HMI application layer:
| Mechanism | What it observes | What it triggers | Example |
|---|---|---|---|
| Driver connection status | The state of the WinCC channel driver session to the data source (e.g. the OPC server process, the S7 ISO-on-TCP connection, the MPI bus). | Tooltip sentinel ("- No connection to the PLC"), QualityCode override to 0x0C/0x1C, color animation, alarm if configured. |
S7 driver reports "PLC not reachable". |
| OPC item QualityCode | The OPC-DA quality stamp assigned to each item by the server (Softing INAT) for the individual read. | Only visible to scripts (VBS / C-ODK) that explicitly query QualityCode. Not consumed by "Evaluate tag status". |
QualityCode = 0x08 from INAT server. |
The OPC channel driver in WinCC treats the OPC server process as the unit of failure, not the device behind the OPC server. As long as the OPC server process is running and accepting reads, WinCC assumes the link is healthy. The QualityCode returned per item is treated as a data attribute, not a connection attribute, and is not propagated to the higher-level state machine used by "Evaluate tag status".
This is by design in the classic WinCC V7 OPC channel and in TIA Portal's WinCC RT Professional OPC channel: the OPC specification defines quality codes as per-item, while WinCC's tag status evaluation is per-channel-connection. A mismatch is unavoidable unless bridged explicitly by user code.
3. OPC DA Quality Code Reference
The OPC-DA 2.05a / 3.00 specification defines the lower byte of the Quality word as a 4-bit Quality field and a 4-bit Substatus field. Code 0x08 decodes as follows:
| Hex | Quality bits | Substatus | Name (OPC DA spec) | Meaning |
|---|---|---|---|---|
| 0x08 | 0000 (Bad) | 1000 | OPCS_QUALITY_BAD_COMM_FAILURE | Communications failure detected. No communication with the underlying device. |
| 0x0C | 0000 (Bad) | 1100 | OPCS_QUALITY_BAD_DEVICE_FAILURE | Device failure detected. The device is physically present but reporting internal fault. |
| 0x14 | 0001 (Uncertain) | 0100 | OPCS_QUALITY_UNCERTAIN_LAST_USABLE | Value not refreshed within configured update interval; last usable value retained. |
| 0x1C | 0011 (Good/Local override) | 1100 | OPCS_QUALITY_GOOD_LOCAL_OVERRIDE | Value has been overridden by operator input. |
| 0xC0 | 1100 (Good) | 0000 | OPCS_QUALITY_GOOD | Normal, in-service value. |
Softing INAT OPC-Server Ethernet sets 0x08 on all items mapped to a controller whose primary connection handle (the one the server has registered with the Pilz PSS communication stack) has entered DISCONNECTED state. The server's internal diagnostics log records the transition with the device IP, slot, and timestamp; this is documented in the Softing OPC-Server Ethernet handbook (PDF).
4. Softing INAT OPC-Server Ethernet Architecture
The INAT OPC-Server (rebranded under Softing as the OPC-Server Ethernet, part number families 1101-1000 through 1101-9999 depending on driver bundle) acts as a protocol bridge between the Ethernet-attached PLC and any OPC DA client on the host. For Pilz systems, the relevant protocol modules are:
- Pilz PSS 3000/4000 (Modbus/TCP) — typically routed through the PSS gateway or a PNOZmulti m B1 with Ethernet module.
- Pilz PMC (Pilz Multi-Configurator) / SafetyBUS p — supported by Softing via the SafetyBUS p option.
- Pilz PSS 4000 with OPC UA server — modern PSS 4000 firmware exposes a native OPC UA server, which can be preferred over OPC DA when the WinCC client supports OPC UA.
Each PLC connection in the Softing OPC explorer has the following relevant parameters (see the handbook section "Device Configuration » Ethernet settings"):
| Parameter | Default | Recommended for safety systems | Effect on QualityCode |
|---|---|---|---|
| Polling interval | 500 ms | 200 ms | Shorter poll = faster transition to 0x08 after link loss. |
| Connection timeout | 3000 ms | 1000 ms | Time without successful response before the server marks the link down and rewrites all item qualities to 0x08. |
| Retry attempts | 3 | 5 | Reduces transient 0x14 (Uncertain) on noisy lines. |
| Item behavior on disconnect | Keep last value | Hold + raise quality | Quality must degrade to 0x08; the WinCC client will not change the value bytes on its own. |
5. Why "Evaluate Tag Status" Does Not Fire
In WinCC V7 and WinCC RT Professional, the "Evaluate tag status" property on a graphic object is bound to the tag's State attribute, not its QualityCode. The mapping performed by the WinCC channel is:
WinCC channel driver sees:
- OPC server process reachable? -> YES
- Last Read()/Write() returned ok? -> YES (server still answers)
- Item QualityCode returned by server -> 0x08 (per item)
Therefore:
- Tag.State = 0 (OK)
- Tag.QualityCode = 0x08 (BAD_COMM_FAILURE)
- Evaluate tag status condition = not triggered
The bridging only happens if the OPC channel itself returns an error, for example when the OPC server process is stopped (CoCreateInstance fails, or IOPCServer::GetStatus returns S_FALSE / disconnected). In that case WinCC sets State = 1 (connection error) and overrides QualityCode to 0x0C.
6. Solution A — System-Tag Polling with C-Script / VBS
The classic WinCC V7 method is to expose a single OPC item from the Softing server whose quality reflects the link state, and bind that item to an internal boolean "LinkUp" tag. The item is most often a "System Status" register that the server updates with a counter, or a read of any item from the device.
Step 1 — Add a heartbeat tag in Softing OPC Explorer
- Open the Softing OPC-Server Ethernet configuration.
- Add a new item under the Pilz device, e.g.
Device1.Heartbeat_Wordat a 16-bit register that is guaranteed to be present (e.g. a holding register that the PLC firmware cycles 0…65535). - Set the Softing item's update mode to "On demand" and configure the connection timeout to 1000 ms.
- Export/import the OPC tag list into WinCC using the OPC Scout or the WinCC OPC channel import wizard.
Step 2 — Create a WinCC internal boolean
In the WinCC Tag Management, add an internal tag PSS_Link_OK of type BOOL with initial value 0.
Step 3 — Schedule a Global Script to refresh the boolean
In WinCC V7, use the C-ODK scheduler (or a VBS action in a 1-second cyclic trigger). Example VBS in a global action:
' Global action, 1 s cycle
Dim oTag, q
Set oTag = HMIRuntime.Tags("Device1.Heartbeat_Word")
oTag.Read
q = oTag.QualityCode
If (q And &H00C0) = &H0000 Then ' lower 2 bits = 00 (Bad)
HMIRuntime.Tags("PSS_Link_OK").Write 0
Else
HMIRuntime.Tags("PSS_Link_OK").Write 1
End If
Bind the PSS_Link_OK tag to the "Evaluate tag status" condition on every relevant object, or use it as the trigger for an Analog alarm in the alarm logging.
7. Solution B — Bridge the QualityCode Through the OPC UA Channel
WinCC RT Professional (TIA Portal V16 and later) ships with a native OPC UA client channel. The Unified Automation OPC UA Extension for SIMATIC WinCC provides a fully spec-compliant UA client including subscription-based monitoring, with quality and StatusCode propagation that is consumed by WinCC's tag status evaluation.
When Softing INAT is replaced by the Softing OPC UA Server (a separate product line) or the native OPC UA server of the Pilz PSS 4000, the StatusCode Bad_CommunicationError (numeric 0x80050000) is automatically translated by the WinCC OPC UA channel into a tag error, and "Evaluate tag status" works out of the box.
Procedure:
- Open the TIA Portal project, navigate to Devices & Networks » HMI » Connections and add an OPC UA Client connection to the Softing / Pilz UA endpoint, e.g.
opc.tcp://192.168.10.20:4840. - In the security settings, select the appropriate certificate policy. For an isolated cell network, None is acceptable; for plant networks use Sign with a server-side certificate issued by the WinCC project CA.
- Import the namespace, drag the required nodes into the HMI tag table. The imported tags carry their original UA StatusCode mapping.
- Verify in the WinCC diagnostics window that disconnecting the Pilz PLC updates
QualityCodeto0x1C(good local override) is NOT raised, but the StatusCode mapping to WinCCState = 1is.
QualityCode directly must be ported to the WinCC RT Professional ODK UA API, where StatusCode is exposed on the ITagUA interface.8. Solution C — Direct QualityCode Polling in Graphics
For a small number of critical objects where the cost of Solution A (extra tag + script) is not justified, the QualityCode can be polled directly in the graphic object's property "Appearance / Flashing / Enable" with the following C-action:
// Returns 1 if tag quality is GOOD (0xC0..0xFF), else 0
{
DWORD q;
q = GetTagQualityCode(lpszPictureName, "Tag_1");
return ((q & 0xC0) == 0xC0) ? 1 : 0;
}
This C-action is invoked every time WinCC refreshes the picture (default 250 ms). The return value drives the "Appearance" background color of the value field, so a degraded link produces a red flashing box. Performance impact is negligible for under 50 such evaluated objects per picture.
9. Verification Procedure
After applying Solution A, B, or C, perform the following acceptance test on the integrated Pilz–Softing–WinCC stack:
- With the Pilz PLC online and healthy, verify in WinCC that all tags show
QualityCode = 0xC0andState = 0. Hover tooltip shows numeric value only. - Pull the network cable from the Pilz PLC. Wait one full connection-timeout interval (1000–5000 ms depending on configuration).
- Verify with VBS that
HMIRuntime.Tags("Device1.Heartbeat_Word").QualityCode = 0x08(or equivalent per Solution B). - Verify that
PSS_Link_OKtransitions to0within one scheduler cycle (1 s). - Verify that the "Evaluate tag status" condition on the target object evaluates to "Bad" and the configured appearance / alarm fires.
- Reconnect the cable. Verify that the Softing server transitions items back to
0xC0within one poll interval and thatPSS_Link_OKreturns to1with no manual intervention. - Check the WinCC diagnostics file
WinCC_Sys_for "OPC: Quality of tag … changed to BAD_COMMUNICATION" entries — these confirm the channel received the degraded quality..log
10. Troubleshooting Matrix
| Symptom | Likely cause | Diagnostic | Fix |
|---|---|---|---|
QualityCode stays at 0xC0 even after cable pull. |
Softing item set to "cached" or polling disabled. | OPC Scout: force read of the item and observe the code. | Set item update mode to "On demand" with a client poll, or "On change" if the PLC supports it. |
QualityCode 0x08 but WinCC State stays 0. |
Expected OPC DA behavior; not a bug. | VBS read of State and QualityCode separately. |
Apply Solution A, B, or C. |
WinCC State 1 but QualityCode still 0xC0. |
OPC server process crashed or COM call timed out; the cached quality is stale. | Restart the Softing OPC-Server service. | Wrap the service with the Softing watchdog or a Windows service recovery rule. |
QualityCode 0x14 (Uncertain) intermittently. |
Network jitter, switch spanning-tree reconvergence, or timeout too aggressive. | Wireshark capture on the Pilz PLC port; check for duplicate IP, broadcast storm. | Increase Softing connection timeout to 3000 ms; configure port-fast on the switch port. |
QualityCode 0x0C on some items only. |
Pilz PSS reports a per-module fault; the device is up but one slot is bad. | Read the PSS diagnostic buffer via PNOZmulti Configurator. | Resolve the module fault; this is correct behavior, not a WinCC issue. |
11. Best Practices for Pilz–WinCC OPC Integration
- Prefer OPC UA for greenfield. For new Pilz PSS 4000 installations, expose the native UA server and connect WinCC RT Professional via OPC UA. StatusCode propagation is spec-compliant and removes the need for the bridging logic described above.
- Keep a heartbeat tag. Even on UA integrations, retain at least one cyclical read used solely for the purpose of monitoring the link state from the WinCC side. This is invaluable during commissioning and FAT.
-
Configure explicit timeouts. Never leave the Softing server at its 3 000 ms default for safety systems. Set the connection timeout to 1 000 ms and the polling interval to 200 ms so that the propagation to
0x08happens within the operator's attention envelope. - Log quality transitions. Add a C-action in the scheduler that writes QualityCode changes to the WinCC user archive with timestamp. This gives you a permanent record for post-incident analysis without depending on the OPC server's local log.
-
Document the bridging layer. If you use Solution A, document the heartbeat item, the script, and the internal
PSS_Link_OKtag in the WinCC project notes. Future maintainers who only see the bridging boolean have no clue where it comes from. - Test the fail-state in FAT. Pull the network cable on the bench, not in the live plant. Operators will not tolerate learning that the HMI silently freezes values on a real fault.
12. Alternative Architectures
For sites that already run a modern SCADA suite (Ignition, FactoryTalk View SE, WinCC Unified), the OPC DA layer can be replaced with a direct OPC UA connection to the Pilz PSS 4000 OPC UA server. The Siemens TIA Portal documentation on using OPC in WinCC RT Professional describes the supported UA client profiles and the security policies. When the UA channel is configured with a 1 000 ms publishing interval and a 5 000 ms keep-alive, the WinCC tag state machine propagates Bad_CommunicationError within the keep-alive window, eliminating the manual bridging step.
For Pilz systems that must remain on OPC DA (e.g. PSS 3000 with no UA server, or where the SCADA vendor is locked to OPC DA), the Softing OPC-Server Ethernet remains the most widely deployed bridge. The QualityCode bridging solutions above are the standard mitigation in those environments.
What does OPC QualityCode 8 mean in WinCC?
QualityCode 8 (0x08) is OPCS_QUALITY_BAD_COMM_FAILURE. It indicates that the Softing INAT OPC-Server has lost contact with the underlying Pilz PLC but is still answering client reads. WinCC receives the value but does not change the displayed number; only the quality attribute is updated, which is why "Evaluate tag status" does not fire.
Why does WinCC show the tooltip "- No connection to the PLC" with S7 but not with OPC?
WinCC injects that tooltip text only when the channel driver itself reports a connection failure. The S7 driver does so as soon as the CP layer is unreachable. The OPC channel driver considers the OPC server process as the unit of failure; a missing device behind a running OPC server does not change the driver status, so the tooltip text is not emitted.
Can I read the OPC QualityCode directly in a WinCC VBS script?
Yes. Use HMIRuntime.Tags("YourTag").Read followed by HMIRuntime.Tags("YourTag").QualityCode. The value is the raw OPC quality word. A value whose upper two bits are 00 indicates a Bad quality; the lower 4 bits give the sub-status (8 = communications failure, 12 = device failure).
How fast does the Softing server set QualityCode to 0x08 after a cable pull?
With the default 3 000 ms connection timeout and 500 ms polling interval, the transition happens between 3 and 3.5 seconds after the last successful response. Lowering the timeout to 1 000 ms reduces this to roughly 1.0–1.5 seconds. The value is then held at 0x08 for every subsequent poll until the link is restored.
Should I migrate to OPC UA instead of patching OPC DA QualityCode bridging?
For new Pilz PSS 4000 projects, yes. OPC UA StatusCode is propagated through the WinCC OPC UA client channel into the tag state machine automatically, and you can subscribe with a 1 000 ms publishing interval for sub-second detection. For legacy PSS 3000 systems, OPC DA with the bridging script remains the realistic option.