Problem Summary
A bar graph inserted from the WinCC Professional V14 SP1 toolbox renders correctly at design time but becomes invisible in runtime once a real-typed process tag is bound to its value property. The defect reproduces on both the WinCC RT simulator and the physical HMI panel (Comfort Panel, TP/Comfort Unified, or PC-based runtime), regardless of whether the source PLC is an S7-1200, S7-1500, ET 200SP, or S7-300/400 connected via PROFINET or PROFIBUS. The same screen displays no bar fill, no scale labels, and no border even though the underlying tag polls without error in the HMI tag diagnostics view. Re-dragging the bar from the library restores visibility until the process tag is wired, indicating the issue is triggered by tag binding rather than by the screen object itself.
This defect is documented as resolved in the official TIA Portal V14 SP1 Update 2 release notes under the heading "Screens and screen objects." Engineers encountering the symptom in V14 SP1 GA (without Update 1 or later) must install Update 2 (or the cumulative Update 3) to restore bar, slider, and pointer-instrument rendering against multiplex and process tags.
Affected Software Versions
| Software Component | Version | Defect Status |
|---|---|---|
| TIA Portal V14 SP1 | 14.0.1.0 (GA) | Affected |
| TIA Portal V14 SP1 Update 1 | 14.0.1.1 | Affected |
| TIA Portal V14 SP1 Update 2 | 14.0.1.2 | Fixed |
| TIA Portal V14 SP1 Update 3 | 14.0.1.3 | Fixed (cumulative) |
| TIA Portal V14 SP1 Update 4 | 14.0.1.4 | Fixed |
| TIA Portal V14 SP1 Update 5 | 14.0.1.5 | Fixed |
| TIA Portal V14 SP1 Update 6 | 14.0.1.6 | Fixed |
| TIA Portal V14 SP1 Update 7 | 14.0.1.7 | Fixed |
| TIA Portal V15 / V15.1 / V16 | 15.x / 16.x | Not affected (different code base) |
14.0.1.x where x >= 2 for the fix to be present.Root Cause Analysis
The defect originates in the WinCC Professional V14 SP1 screen-object rendering pipeline. When a process tag of elementary type Real is connected to a bar, slider, or pointer instrument, the property update path that propagates the configured maximum, minimum, and current value fails to commit the visibility flag of the bar's drawing layer. The bar's geometry, color ramp, and tick-mark arrays are pushed to the runtime buffer, but the layer's Visible attribute remains in the design-time state of False, producing an empty screen region.
Two related defects are corrected simultaneously by Update 2:
- Multiplex tag binding: Bar, slider, and pointer instruments could not consume a multiplex tag index without corrupting the screen object's drawing context. Multiplex tags allow a single visual element to mirror different PLC values based on the current index, eliminating duplicate bar widgets per measured point. Prior to Update 2, the multiplex indirection caused the same invisibility condition.
- Animation propagation: When a configured tag was modified in any of the dynamic interfaces (appearance, position, color) of a selected screen object, the change failed to broadcast to sibling objects in the same selection set. The engineer could not batch-update bars sharing a common PLC tag structure.
Both issues are addressed by V14 SP1 Update 2 and inherited by all subsequent updates through V14 SP1 Update 7. The official Siemens readme states verbatim:
"Screens and screen objects
Multiplex tags can be used in bars, sliders and pointer instruments.
A change to the configured tags in an animation affects all of the selected objects."
Solution: Install TIA Portal V14 SP1 Update 2 or Later
Prerequisites
- Local administrator rights on the engineering workstation.
- All TIA Portal instances closed before patch deployment.
- Siemens Automation License Manager installed and functional.
- A valid TIA Portal license (floating or single-user) for at least one WinCC Professional editor seat.
- Minimum 4 GB free disk space on the system partition for the patch expansion.
- Project archive (.zap14) committed to source control or external backup prior to upgrade.
Step-by-Step Update Procedure
- Navigate to the official Siemens Industry Online Support portal and locate the entry for SIMATIC TIA Portal V14 SP1 Update 2 (article ID 109749283 or the equivalent delivery record for cumulative Update 3).
- Download the package
SIMATIC_TIA_Portal_V14_SP1_UPD2.exe(or the corresponding cumulative installer) to a local working directory. - Right-click the installer and execute Run as administrator. The setup detects the existing V14 SP1 base installation and prompts for upgrade mode.
- Accept the license agreement and confirm the target installation path matches the existing TIA Portal root (default
C:\Program Files\Siemens\Automation\Portal V14 SP1). - Select Complete component coverage to ensure WinCC Professional, WinCC Runtime Professional, PLCSim, and all HMI device packages receive the patch.
- Allow the installer to stop the TIA Portal background services (TIA Administrator, ALM, license server) and complete file replacement. A typical upgrade requires 10-20 minutes.
- Restart the engineering workstation when prompted to refresh the registry and service entries.
- Verify the upgrade by launching TIA Portal, opening Help → Installed Software, and confirming the WinCC Professional version reads
14.0.1.2or later.
Alternative: Cumulative Update 3 Deployment
Update 3 includes Update 1 and Update 2 plus additional corrections for the TIA Portal framework (graph editor, project library, multiuser server). Installing Update 3 is recommended when multiple patch levels are missing, as it consolidates the deployment into a single maintenance window. Cumulative installers follow the same procedure as Update 2; the executable name is SIMATIC_TIA_Portal_V14_SP1_UPD3.exe.
Verifying the Bar Graph Visibility Fix
After applying Update 2 (or later), perform the following regression test sequence to confirm the bar graph renders correctly in runtime:
- Open the affected TIA Portal project and navigate to the HMI device containing the bar object.
- Select the bar widget in the screen editor. Confirm the Properties → General → Process value field references the correct
RealHMI tag. - Compile the HMI station: right-click the HMI device → Compile → Software (rebuild all). A clean compile emits no warnings or errors referencing the bar object.
- Start the WinCC Runtime via Online → Start Runtime (simulator) or download the project to the panel.
- Force the PLC tag to mid-range value (e.g., 50% of configured max) from the PLC's watch table or PLCSim.
- Observe the bar fill: the colored fill region must extend from the configured minimum endpoint to the value marker. The scale, tick marks, and label must remain visible.
- Force values at 0%, 25%, 75%, and 100% to validate linear interpolation and end-cap rendering.
- Trigger a value change during runtime to confirm the bar updates in real-time without flicker, blanking, or screen refresh artifacts.
Configuring the Bar Object Correctly
Beyond the update installation, validate the bar configuration against the documented WinCC Professional schema:
| Property | Recommended Setting | Notes |
|---|---|---|
| Process value (Tag) | HMI tag of type Real or Int
|
Must be an HMI tag, not a raw PLC DB address. Direct DB addressing requires a tag wrapper. |
| Maximum value | Matches engineering range (e.g., 100.0) | For Real tags with engineering units, set decimal precision in the tag properties. |
| Minimum value | 0.0 (or process zero) | Negative minimum values invert the fill direction. |
| Bar direction | Bottom to top / Left to right | Configure per screen layout and human-factors convention. |
| Color ramp | Single color or gradient per zone | Multi-zone ramps require the V14 SP1 fixed version for stable runtime. |
| Scale | Major ticks at 25%, 50%, 75%, 100% | Scale tick labels inherit the tag's display format. |
| Limit lines | Configured as separate "Line" screen objects | Native limit-line support is introduced in V15. |
| Visibility animation | Optional; based on a discrete HMI tag | Do not bind visibility to the same process tag as the value, or the bar disappears on zero values. |
Working with Multiplex Tags on Bars
The Update 2 fix enables multiplex tag indexing for bars, sliders, and pointer instruments. A multiplex tag is a structured HMI tag containing an array or UDT whose index is driven by a separate index tag. The bar then displays the value at the current index, eliminating the need for N bar widgets per N measured points.
Multiplex Tag Configuration Procedure
- Define a UDT in the PLC (e.g.,
typeMeasurementPoint) with aReal value,Bool alarmHigh, and other fields. - Create an HMI tag of type
WStringor arrayArray[0..31] of Realmatching the UDT structure. - Add a separate
IntHMI tag namedIndexVarto drive the multiplex selector. - Open the bar object's Properties → General. In the Process value field, click the tag selector and choose Multiplex tag.
- Select the array tag and the index tag. Confirm the type matches the bar's value property (
Real). - Compile and download. Increment
IndexVarat runtime via a script or screen button to switch the displayed measurement point.
Animation Propagation Behavior
Prior to Update 2, modifying a tag reference in the animation interface (e.g., appearance color, position offset) of one screen object did not propagate to other selected objects sharing the same tag. Engineers working with grouped bars (e.g., a row of 8 bars representing motor currents) had to re-edit each object's animation individually.
Update 2 introduces selection-set animation broadcasting: with multiple screen objects selected, editing a dynamic tag in the animation panel applies the change to every selected object whose interface supports that animation type. This is a productivity fix rather than a runtime correctness fix, but it is the second half of the official Update 2 release note.
Recommended Workflow for Grouped Bars
- Insert the first bar and fully configure it (process value, color, limits, scale).
- Select the bar, copy with Ctrl+C, and paste it with Ctrl+V to clone the configuration.
- Multi-select all cloned bars using Shift+Click or rubber-band selection.
- Open the Animation panel. Modify the Appearance tag reference. The change applies to all selected bars in a single operation.
- Repeat for Position and Color animation interfaces as required.
Project Migration Considerations
Projects created in V14 SP1 GA open without modification after Update 2 installation. The update is binary-compatible at the project file level. However, the following clean-up tasks are recommended to avoid downstream issues:
- Re-compile all HMI stations after the update installation. Compiled runtime files generated by GA versions may reference obsolete symbol IDs.
- Re-download panel images to physical Comfort and Unified Comfort panels. The runtime mirror stored in the panel flash retains pre-update binaries until overwritten.
- Validate scripts that reference bar objects by name. The screen-object internal naming scheme was not changed by Update 2, but downstream V15 migrations may require renaming.
- Audit library references for any custom master copies of the bar object. Custom bar variants may need to be re-anchored to the updated master.
-
Back-archive the project as
ProjectName_v14sp1_u2.zap14to capture the post-update build for traceability.
Related Configuration: Process Tag vs. PLC Tag
The original symptom was triggered by binding a process tag of type Real. The distinction between HMI tags and direct PLC address references is critical in TIA Portal V14 SP1:
| Tag Source | Binding Method | Runtime Behavior |
|---|---|---|
| HMI tag (created in HMI tag table) | Drag HMI tag to process value field | Acquisition cycle, scaling, and limit handling applied |
| PLC tag (symbolic) | Drag PLC tag from project tree to process value field | Implicit HMI tag created; same behavior as HMI tag with direct PLC connection |
Absolute address (e.g., %DB5.DBD0) |
Direct address typing into process value field | Legacy mode; supported but not recommended for new projects |
| Multiplex tag (Update 2+) | Select Multiplex tag in tag browser | Indexed access; correct rendering requires Update 2 or later |
When the bar disappears after binding, verify the HMI tag exists in the HMI tag table, the connection path to the PLC is established (right-click HMI device → Connections), and the PLC tag is reachable. Use the HMI tag diagnostics view (Online → HMI tag diagnostics) to confirm the tag is updating.
Field Diagnostics Checklist
If the bar remains invisible after Update 2 installation and project recompile, execute the following diagnostic sequence:
- Tag update rate: In Online &ranti HMI tag diagnostics, force the value and confirm the HMI tag updates within the configured acquisition cycle. A frozen tag indicates PLC connection issues, not bar object issues.
- Range validity: Confirm the process value falls within the bar's configured [Min, Max] range. Values outside the range clamp but should still render; values returning NaN (e.g., from division by zero in the PLC) cause the bar to disappear.
-
Visibility animation: Open the bar's Properties → Animations panel. If a visibility animation is configured, inspect the trigger tag and Boolean expression. A
Falsetrigger tag hides the bar regardless of value binding. - Layer order: Check the screen layer ordering. A solid-fill rectangle or other object drawn above the bar layer occludes it. Move the bar to the topmost layer via Arrange → Bring to Front.
- Screen resolution scaling: On high-DPI engineering workstations, the bar may render at 0 height if the screen zoom factor is non-integer. Reset the editor zoom to 100%.
-
Corrupted compilation: Delete the compiled HMI station files (project subdirectory
\IM\HMI\<station>\Compile) and recompile from scratch.
Forward Path: WinCC Unified RT Bar Object
Engineers planning to migrate from WinCC Professional V14 SP1 to WinCC Unified (V17, V18, V19, V20) should review the unified bar object's property model. The unified bar inherits the corrected rendering pipeline from V14 SP1 Update 2 onward, eliminating the legacy visibility bug entirely. The configuration surface is exposed in the Inspector window under Layout, Appearance, and Animations categories, with the process value, minimum, maximum, and color ramp configurable from a single property sheet.
For projects targeting Unified Comfort Panels (MTP700 Unified, MTP1000 Unified, MTP1200 Unified, MTP1500 Unified, MTP1900 Unified, MTP2200 Unified), the bar object is native to the Unified runtime and does not require legacy WinCC Professional fix-ups. Migrate bar-heavy screens from V14 SP1 Comfort Panels to Unified Comfort Panels when panel hardware replacement is on the maintenance schedule.
References and Standards
Engineers verifying the fix should consult the official Siemens documentation:
- SIMATIC TIA Portal V14 SP1 Update 2 Readme (Siemens Support, ID 109749283)
- Bar (RT Unified) - WinCC Unified V20 Screen Objects Reference
Frequently Asked Questions
Does installing Update 2 break my existing V14 SP1 projects?
No. Update 2 is binary-compatible with V14 SP1 GA project files. Existing projects open, compile, and download without modification. The fix is internal to the screen-object rendering engine and does not alter the project schema, HMI tag table, or screen object metadata.
How do I verify Update 2 is installed on my engineering workstation?
Open TIA Portal, click Help → Installed Software, and confirm the WinCC Professional entry reads version 14.0.1.2 or later. The title bar in the main window frequently displays an outdated version string; the Installed Software dialog is authoritative.
Do I need to update the panel firmware separately after installing Update 2?
Yes, for physical panels. Comfort Panels and Unified Comfort Panels store the compiled runtime image locally. After recompiling the project in the updated engineering tool, perform a full project download (not delta) via ProSave, TIA Portal, or the panel's service interface to overwrite the pre-update image.
Can I install Update 2 over V14 SP1 GA without first installing Update 1?
Yes. Update 2 is a standalone incremental patch and includes all prior fixes for the V14 SP1 baseline. For multi-step upgrade paths, the cumulative Update 3 (which contains Updates 1 and 2) is preferred to minimize the number of maintenance windows.
Why does my bar still not render after Update 2 installation?
The Update 2 fix addresses the specific defect where bar, slider, and pointer instruments become invisible after process tag binding. If the bar remains invisible after update installation, check the visibility animation trigger tag, verify the process value is within the configured range, confirm the screen layer ordering, and recompile the HMI station from a clean state. Use the HMI tag diagnostics view to confirm the underlying tag is updating correctly.
Does the bar visibility defect affect WinCC Comfort/Advanced panels as well?
Yes. The defect is in the WinCC Professional runtime rendering pipeline, but the same bar object is shared with WinCC Comfort/Advanced in V14 SP1. Update 2 corrects the defect across all three runtime editions (Comfort, Advanced, Professional).