1. Problem Overview
Engineers commissioning Siemens WinCC V6.2 SP1 frequently encounter a runtime startup error: the project loads into Runtime, then immediately reports "Insufficient License", and the tag counter collapses to the red DEMO state. Typical reported configuration: a single workstation PC holding both an RT (Runtime) 1024-tag license and an RC (Runtime/Configuration) 8192-tag license, with a project that only references roughly 600-800 process tags. The user-visible symptom is misleading: the project has more than enough licensed capacity, yet Runtime refuses to honour it.
This article consolidates the diagnostic and remediation paths for this class of fault. It is written against WinCC V6.2 SP1 but applies equally to the broader WinCC V6/V7 line, since the licensing engine, the tag-counting rules, and the runtime startup sequence are unchanged across these releases. Procedures also remain valid after migration to WinCC V7.5 / V7.5 SP1 and to TIA Portal's WinCC Professional option, with the caveat that the Automation License Manager (ALM) version and the entry point of the log files differ slightly.
2. WinCC V6.2 SP1 Licensing Architecture
WinCC licensing is handled by the Automation License Manager (ALM) service and validated at three points: project load, runtime activation, and tag-database compilation. Understanding the categories is essential because the wording "Insufficient License" can be triggered by any of the three.
| License Family | Common Tag Buckets | Typical Use | Project Type Required |
|---|---|---|---|
| WinCC RT 128 | 128 PowerTags | Small single-user HMI | Single-User Project |
| WinCC RT 256 / 512 / 1024 / 2048 / 4096 / 8192 | 256 / 512 / 1024 / 2048 / 4096 / 8192 | Single-user HMI of any size | Single-User Project |
| WinCC RC 128 / 256 / 512 / 1024 / 2048 / 4096 / 8192 | Matching bucket | Operator station on a multi-user system | Multi-User Client or Server |
| WinCC Server | Server licence (no tag cap) | Central server with multiple clients | Multi-User Server |
| WinCC Client / Client Soft | Client-only licence | Operator panel viewing server data | Multi-User Client |
| WinCC Redundancy | Add-on | Fault-tolerant server pair | Server project with redundancy option |
| WinCC WebNavigator / WinCC / WebUX | Concurrent-user licence | Browser-based access | Server or Single-User with Web option |
Key rule: the project type (single-user or multi-user) and the license type (RT or RC/Server/Client) must match. The same PC can hold multiple licenses, but only one is selected by the WinCC runtime startup logic, and the choice is determined by the project's Computer Type property, not by which license is currently "active" in ALM.
When the chosen project type does not match the available license, WinCC silently downgrades the project to DEMO mode: Runtime starts, but the licensing banner in the lower right corner displays DEMO and runtime is restricted to the 1-hour evaluation window after each activation. Tag limit enforcement still applies, so even a small project will continue to be flagged if the licensing subsystem believes the configuration is invalid.
DEMO in red, and the counter "External Tags: xxxxx / License: xxxxxx" displays 0 for the License field. This is the primary visual cue that a license-mismatch - not a tag-count limit - is the root cause.3. Tag Counting Rules: Internal vs External
WinCC distinguishes between three tag categories, and only one of them drives the licensing check:
- Internal Tags: variables that live entirely inside the WinCC database. They do not require a PowerTag license and do not contribute to the count shown in the licensing dialog.
- External Tags (PowerTags): variables connected to a PLC via a channel driver (S7, MPI, PROFIBUS, TCP/IP, OPC, etc.). Each configured external tag consumes one PowerTag from the license pool.
- Archive Tags: external tags additionally configured to be logged. They count as PowerTags exactly once; the archive tag itself does not consume an additional license unit.
The licensing check is performed on the External Tag count only. WinCC Explorer reports this in two places:
-
Status bar (bottom right):
External Tags: 678 / License: 1024while the project is open in the Explorer. - Tag Management dialog: the Channel/Connection tree shows the number of configured external tags per driver.
If the status bar shows the correct project count but the License value reads 0 or DEMO, the issue is licensing - not tag count. If the status bar shows a count higher than expected, audit the Tag Management tree: unconnected tags and tags inherited from a copy-paste of a larger project can silently inflate the count.
4. Root Cause Analysis: Why "Insufficient License" Appears
The WinCC V6.2 SP1 runtime startup sequence performs a license validation in this order:
- Read the project's Computer Type property (single-user vs. multi-user server vs. multi-user client).
- Query ALM for a compatible license matching that project type.
- Compare the licensed tag bucket against the configured External Tag count.
- If no match is found, fall back to DEMO mode and emit a startup entry in the license log.
The "Insufficient License" message is therefore triggered by any of four root conditions:
| Root Cause | Symptom in License Bar | Where to Verify |
|---|---|---|
| Project type is "Multi-User Server" but only a single-user RT license is installed | DEMO | Project Properties → General tab |
| Project is correct type, but ALM has not registered the license (dongle missing, license file corrupted) | DEMO or 0 | ALM → License Key View |
| Two valid licenses of conflicting types on the same PC; WinCC selects the wrong one | Bucket shown belongs to a different license | License log in Diagnose folder |
| External Tag count genuinely exceeds the bucket of the license WinCC selected | Bucket shown, count exceeds it | Status bar / Tag Management |
In the typical reported case (1024 RT + 8192 RC on one PC, ~678 tags), the root cause is almost always #1 or #3: a multi-user project type is consuming the slot, leaving only the multi-user RC license, and the 8192 bucket looks correct, but the runtime configuration does not match what the project expects. Switching the project to Single-User Project type, or moving the RT license onto the workstation where runtime actually executes, resolves it.
5. Diagnostic Procedure
-
Open the Diagnose folder. Navigate to the WinCC install path (default:
C:\Program Files\Siemens\Automation\WinCC\Diagnose). Inspectlicense.logandlicense_info.log. Each contains a timestamped list of the licenses WinCC requested from ALM and the response received. A line such asLicense for XXXX not foundorFalling back to DEMOpoints to the exact gap. Older WinCC versions wrote these files with GermanFehler/Warnungprefixes if the host locale was German; this is normal and does not indicate a fault. - Read the project type. In WinCC Explorer, right-click the computer icon at the top of the project tree, choose Properties, and open the General tab. The Type field shows Single-User Project, Multi-User Server, or Multi-User Client. This single value is the most common cause of the issue.
-
Read the live licensing status. With the project still open in WinCC Explorer, look at the bottom right of the Explorer window. The line reads
External Tags: NNNN / License: NNNN. Record both values. - Cross-check ALM. Open the Automation License Manager (Start → Siemens Automation → Automation License Manager). The "Active" pane shows every license currently recognised on this PC. The "Invalid" pane shows any license file that ALM considers corrupt, expired, or moved. Note the license numbers and tag buckets.
-
Verify the dongle (if applicable). RT/RC licenses ship as either software license files (placed under
%ProgramData%\Siemens\Automation\License) or hardware dongles (the orange/red USB stick). Hardware dongles must be plugged in before WinCC Explorer or Runtime is started; hot-plugging will not register the license until the ALM service is restarted. - Compare against the project type. Apply the table from Section 4. If the project is Single-User but only an RC/Client license is present, that is the mismatch.
6. Resolution Path A: Single-User vs Multi-User Project
The single most common fix for the reported fault.
- In WinCC Explorer, right-click the computer icon and choose Properties.
- On the General tab, change Type of project to Single-User Project.
- Click OK. WinCC will warn that the change cannot be undone without recreating the project; confirm only if you are sure.
- Close WinCC Explorer, restart the Siemens ALM service, then re-open the project and start Runtime.
If the original project must remain multi-user (for example, you plan to attach Operator Stations later), skip this path and use Path B or Path C instead.
7. Resolution Path B: License Count vs License Type
If the project type is correct and a valid license is installed but the tag count still appears insufficient:
- Confirm the license bucket is in fact the one WinCC selected. The status bar (
External Tags: 678 / License: 1024) shows the bucket of the selected license. If the License field reads0, no compatible license was found. - If the status bar reads, for example,
License: 1024and you actually have an 8192 RC license installed, the RC license has been ignored. Cause: WinCC selected the 1024 RT license because the project is Single-User; the RC license is being held as a fallback or is being used by another project on the same PC. - Two valid responses: either accept the 1024 limit (and reduce the project's external tag count below 1024) or upgrade the RT license to a larger bucket. RC licenses do not supersede RT licenses on a Single-User project.
For projects genuinely above 8192 tags, contact your Siemens sales channel for a custom RT bundle. The standard PowerTag buckets stop at 8192 in WinCC V6/V7; larger configurations are sold as a Server/Client configuration with a separate Server license.
8. Resolution Path C: Multiple License Conflict
When more than one compatible license is installed on the same PC, WinCC follows a deterministic selection order but the order has changed between V6 and V7. Common failure mode: an old evaluation license remains in %ProgramData%\Siemens\Automation\License and gets selected before the production license.
- Open ALM. Move the unwanted license to the Invalid pane (drag and drop) or remove it entirely. Do not delete the production license.
- Restart the ALM service.
- Re-open WinCC Explorer and confirm the status bar shows the expected bucket.
If the license is locked to a different PC's dongle, it cannot be moved by drag and drop. Use ALM's License Key View → Manage to deactivate the license on the source PC and reactivate it on the target.
9. Verification and Commissioning Checks
After applying any of the above resolutions, perform the following sequence before declaring the fault closed:
-
License bar in Explorer: confirm
License: NNNNshows the expected bucket and not0orDEMO. -
License log review: open
license.login the Diagnose folder; the latest entry should show a successful match rather than a fallback. -
Runtime startup: activate Runtime. The status bar must show the licensed tag count, not
DEMO. Let the runtime sit for at least 10 minutes to confirm the evaluation timer has not started (if DEMO is engaged, Runtime silently terminates after 1 hour). - Service restart test: reboot the PC. A clean start with the license present is the only proof that the configuration is persistent.
- Process value test: change a process value in the PLC and verify the corresponding WinCC tag updates. A DEMO-mode project that opens a previous project file from cache can appear to run normally for a few minutes; live data is the proof.
10. Common Pitfalls and Field-Notes
- Copy-pasted project files often retain the source computer's Type property. Even a 678-tag project copied from a server PC will start as a Server project on the new PC and will require an RC/Server license.
- Channel driver duplication: adding a second S7 channel does not double-count tags, but adding a second connection under the same channel can do so if a tag is bound to both. Audit Tag Management if the status bar count is unexpectedly high.
- OPC DA driver quirk: tags imported from an OPC server count as PowerTags even if the underlying PLC variable is later deleted from the OPC server. Clean unused OPC items in Tag Management before checking the count.
-
Service account for ALM: the ALM service runs under
LocalSystemby default. If you have a restricted user environment, ensure the service account has read access to%ProgramData%\Siemens\Automation\License. -
Antivirus interaction: some security products quarantine the
CCLicense.exefile in the WinCC install directory. The licensing subsystem will then fail to start; whitelist the full WinCC install path before commissioning. - Cross-version upgrade: if you migrate a project from V6.2 to V7.x without a fresh license, the project may run for 30 days in V7 demo mode even with a valid V6 license present. Confirm the V7 license separately.
11. Reference Parameter Summary
| Parameter | Location | Expected Value (Single-User, 678 tags) |
|---|---|---|
| Computer Type | Project Properties → General | Single-User Project |
| External Tags (status bar) | WinCC Explorer, bottom right | 678 |
| License (status bar) | WinCC Explorer, bottom right | 1024 or larger, never 0/DEMO |
| RT license bucket | ALM → License Key View | RT 1024 or larger |
| Diagnose folder | ...\WinCC\Diagnose |
license.log, license_info.log present |
| ALM service | services.msc → Siemens ALM | Running, restarted after any change |
Why does my WinCC V6.2 SP1 project with 678 tags say "Insufficient License" when the RT license supports 1024 tags?
The 1024-tag RT license only applies to a Single-User Project. If the project was created or copied as a Multi-User Server project, WinCC skips the RT license and looks for a Server/RC license. Open Project Properties → General tab and confirm the type is Single-User Project; change it to Single-User and restart the ALM service.
How do I check which WinCC license is currently active on my PC?
Open the Automation License Manager (ALM) from the Siemens program group. The Active pane lists every license ALM currently recognises. In WinCC Explorer, the status bar at the bottom right of the window shows External Tags: NNNN / License: NNNN for the open project. The Diagnose folder at ...\Siemens\Automation\WinCC\Diagnose contains license.log and license_info.log with detailed startup entries.
The license bar in WinCC Runtime shows "DEMO" even though ALM shows my license is active. What is wrong?
Three common causes: (1) the project type does not match the license family - e.g. a Multi-User Server project on a PC that only has an RT license; (2) the ALM service was not restarted after the license was added; (3) a second license of a different family on the same PC is being selected, leaving the project type unmatched. Resolve by aligning the project type with the installed license and bouncing the ALM service.
Can I use an RC 8192 license on a Single-User project instead of the RT 1024 license?
No. RC licenses are bound to Multi-User Server/Client projects. A Single-User Project requires an RT license of an equal or greater bucket. If you genuinely need more than 1024 PowerTags on a single workstation, upgrade the RT license to the 2048, 4096, or 8192 bucket, or restructure the project as a Multi-User Server with a Client connection.
Will moving the project from a server PC to a workstation PC change the required license?
Yes. The project type is a property of the project, not the computer. If the project was originally created as a Multi-User Server and you only have an RT license on the target PC, change the project type to Single-User before starting Runtime. Alternatively, install a matching Server license on the new PC if the architecture requires server/client separation.