Problem Overview
WinCC V7.0 raises the dialog An invalid argument was encountered. when an engineer double-clicks any tag in Tag Management of the WinCC Explorer. After the dialog is acknowledged, the tag property sheet refuses to open, and the configuration cannot be edited, renamed, or re-linked until the project is closed or the engineering station is rebooted. In most reported installations the dialog only appears once WinCC Runtime has been started at least once on that engineering station; in other plants the error appears immediately after Explorer launch.
The dialog is a Win32 shell message produced when the configuration DLL passes an invalid handle or filename to the underlying SQL Server Compact Edition (SSCE) container that backs the project. WinCC Explorer, Tag Management, Graphics Designer, and Alarm Logging all read from the same per-project database <ProjectName>.dcf stored in the project directory. When that file is locked by another process, partially overwritten, or denied by a file-system filter driver, Tag Management raises the Win32 ERROR_INVALID_PARAMETER (0x80070057) and surfaces it as An invalid argument was encountered.
Affected Versions and Environment
The symptom has been confirmed on the following Siemens WinCC V7.0 releases on Windows XP Professional SP3, Windows 7 Professional / Ultimate (32-bit and 64-bit), and Windows Server 2008 R2:
| WinCC Version | Build / Update | Reproducible | Recommended Fix |
|---|---|---|---|
| V7.0 base | Release build | Yes | Upgrade to V7.0 SP3 or later |
| V7.0 SP1 | Update 1 - Update 5 | Yes | Install Update 6 or later |
| V7.0 SP2 | Update 1 - Update 11 | Yes | Install Update 12 or later |
| V7.0 SP3 | Update 1 - Update 7 | Yes | Install Update 8 or later |
| V7.0 SP4 | Release build | Rare | Apply latest HF |
Siemens provides WinCC V7.0 documentation, including the WinCC Information System, the Configuration Manual, and the WinCC Release Notes, from the Siemens Industry Online Support portal. The consolidated WinCC V7.0 manual set is indexed under entry ID 109751742 and is available at WinCC V7.0 - Manuals and Communications.
Error Code Reference
The dialog text is a localised rendering of the Win32 status code returned by the SSCE container when it is asked to open a database with an invalid path or an exclusive lock already held. The mapping is:
| Win32 Code | Hex | Decimal | User-Facing Text | Typical Cause |
|---|---|---|---|---|
| ERROR_INVALID_PARAMETER | 0x80070057 | -2147024809 | An invalid argument was encountered. | Bad path, bad handle, file locked |
| ERROR_SHARING_VIOLATION | 0x80070020 | -2147024864 | The process cannot access the file because it is being used by another process. | WinCC.exe still holds the .dcf |
| ERROR_FILE_NOT_FOUND | 0x80070002 | -2147024894 | The system cannot find the file specified. | Project path remapped |
| ERROR_ACCESS_DENIED | 0x80070005 | -2147024891 | Access is denied. | Antivirus / security filter blocks the read |
These codes are exposed by the WinCC Configuration tool when the verbose log WinCC_SysLog is enabled via the registry key HKLM\SOFTWARE\Siemens\WinCC\Diagnostics. Capturing them during the failure narrows the diagnosis to one of the four causes listed in the next section.
Root Cause Matrix
| Cause | Mechanism | Symptom Pattern | Primary Fix |
|---|---|---|---|
Locked .dcf by Runtime or DCom server |
WinCC.exe, DComLaunch.exe, or CCProjectMgr.exe opened the SSCE container exclusively | Error appears after Runtime start; Explorer refresh fails | Stop WinCC Runtime; close DCom; delete *.lck files |
Corrupted .dcf database |
Power loss, disk full, or unsynchronised shutdown truncated SSCE pages | Error appears on a new project copy; SSCE checksum mismatch in WinCC_SysLog
|
Restore backup; rebuild project via Project Duplicator |
| Antivirus / file-system filter driver | Real-time scan opens the file in a way that SSCE rejects; driver rejects the rename | Error disappears when the AV service is stopped | Add WinCC project paths and process exclusions |
| Invalid SQL clause in WinCC AlarmControl | Legacy OR / parentheses / multi-Textxx usage was carried into V7 from V6.x |
Error reported on AlarmControl compile, not on Tag Management | Rewrite clauses per V7 syntax rules |
| User rights mismatch on the project share | User lacks Modify rights on the .dcf share; SSCE cannot create its temp file | Error only for some users on the same station | Grant Modify and Read & Execute on the share |
Diagnostic Workflow
Run the following checks in order before applying any recovery action. Each step produces a yes/no answer that points to the matching root cause row above.
- Close WinCC Explorer and open
%ProgramFiles%\Siemens\Automation\WinCC\bin\WinCC_SysLog.exe. Set the log path to a writable folder and the verbosity toDEBUG. - Re-launch WinCC Explorer, open the project, and double-click a tag. Capture the Win32 code from the dialog and the SSCE line that immediately precedes it.
- Open an elevated command prompt and run
handle.exe -a "<ProjectName>.dcf"from Sysinternals to identify which process is holding the open file handle. - Stop the
WinCC Runtimeservice, theCCProjectMgrservice, and theDCOMLaunchprocess tree. Repeat the double-click. - If the error persists, temporarily disable the installed real-time antivirus, reboot, and repeat. If the dialog disappears, the cause is the file-system filter driver.
- Open the WinCC Information System index, navigate to Options > WinCC AlarmControl, and review the SQL statements subsection for any custom selection clause. Validate every clause against the V7 syntax table later in this article.
Solution A - Recover the .dcf Project Database
The .dcf file is an SSCE (formerly SQL Server CE / SQL Server Embedded Edition) database that stores the WinCC project schema. WinCC V7.0 keeps a copy of the file under two paths: the working path under \<project>\<project>.dcf and an SSCE shadow under \<project>\<project>.dcf-shm. Both must be consistent; if either is missing the SSCE runtime raises the Win32 invalid-parameter dialog.
- Close WinCC Explorer and stop the
CCProjectMgrservice:net stop "CCProjectMgr" - Confirm no
*.lckfiles are present in the project root. Remove any stray lock withdel /q "*.lck"from an elevated prompt inside the project folder. - Open the SSCE repair tool
C:\Program Files\Siemens\Automation\WinCC\bin\sscerepair.exe, select<ProjectName>.dcf, and run Repair. The tool re-creates the missing shadow file<ProjectName>.dcf-shm. - If repair reports Unrecoverable corruption, restore the project from the last backup created by WinCC Project Duplicator and apply the outstanding delta by re-importing the latest export file
<ProjectName>.exp. - Re-launch WinCC Explorer and double-click any tag. The dialog must not appear.
Project Duplicator backups. The duplicator writes a self-consistent .dcf, a .log of the project tree, and an export file. Restoration of the duplicate plus a delta import is faster and safer than repairing a corrupted SSCE container.
Solution B - Resolve Runtime Lock Conflicts
The error reproduces reliably after the WinCC Runtime has been activated on the engineering station. The WinCC process WinCC.exe opens the .dcf in FILE_SHARE_READ only and Tag Management opens it in FILE_SHARE_NONE for editing. When the runtime is still active, Tag Management's open call collides with the runtime's handle and the SSCE layer translates the Win32 sharing-violation into the user-facing invalid argument dialog.
- From the WinCC Explorer menu select File > Exit to close the configuration client.
- Open the Windows Services console (
services.msc) and stop the following services in the listed order:WinCC Runtime,CCProjectMgr,CCAlgChannelServer,S7DOS. - Confirm no
WinCC.exeprocess remains:tasklist /fi "imagename eq WinCC.exe" - Run
handle.exe -a "<ProjectName>.dcf"again to confirm zero handles. - Re-open WinCC Explorer and verify Tag Management.
If the engineering station is used for both configuration and runtime, install the WinCC split-client configuration: run the configuration client on a separate engineering PC and the runtime on the OS server. The split-client setup is described in the WinCC V7.0 Communication manual.
Solution C - Antivirus and Security Filter Exclusions
Real-time file-system filter drivers from antivirus, endpoint detection, or backup products intercept every open of the .dcf. When the filter intercepts the SSCE CreateFileW with FILE_FLAG_NO_BUFFERING, the SSCE layer receives an invalid handle and surfaces the dialog. The reliable fix is to whitelist the WinCC directories and processes, not to disable the security product globally.
| Vendor | Paths to Exclude | Processes to Exclude | Notes |
|---|---|---|---|
| Symantec Endpoint Protection |
%ProgramFiles%\Siemens\Automation%ProgramData%\Siemens\Automation
|
WinCC.exe, CCProjectMgr.exe, sscerepair.exe
|
Use the Application Control - Allowed System Changes list |
| Trend Micro OfficeScan | Same as above plus the project share root | Same as above | Enable the Approved Process flag |
| McAfee VirusScan Enterprise | Same as above | Same as above | Disable on-access scan only on the engineering client |
| Windows Defender | %ProgramFiles%\Siemens\Automation |
Same as above | Add via Group Policy Excluded Paths |
After updating the exclusion list, restart the engineering station, repeat the WinCC_SysLog capture, and confirm the Win32 code no longer appears.
Solution D - WinCC AlarmControl SQL Syntax Constraints
WinCC AlarmControl in V7.0 accepts a limited SQL dialect that must match what the WinCC selection dialog can generate. Legacy V6.x projects often contain clauses that V7.0 now rejects and that indirectly corrupt the project metadata so that Tag Management fails on first edit. The complete V7 syntax rules are documented in the WinCC Information System, section Working with WinCC > AlarmControl > Selection.
| Element | V7.0 Rule | Invalid Example | Corrected Form |
|---|---|---|---|
| Structure |
Field Operand Value separated by blanks |
MSGNR>=100 |
MSGNR >= 100 |
| String / Date / Time literal | Wrapped in single quotes | DATETIME>2006-12-21 |
DATETIME >= '2006-12-21 00:00:00' |
| Time base | Always Local Time unless UTC is selected in the object properties | Mixing UTC and Local Time literals | Set time base explicitly per alarm control |
| Statement length | Maximum 4096 characters | Concat with comments > 4 KB | Trim to the generated dialog equivalent |
| Grouping with parentheses | Forbidden | (MSGNR>=100 OR MSGNR<=200) |
Two independent selections or re-author with a filter variable |
| Boolean connective | Only AND allowed |
MSGNR=1 OR MSGNR=2 |
Two selections stacked in the dialog |
| Textxx argument | Only LIKE allowed; single use per clause |
Text1 LIKE 'a%' AND Text1 LIKE 'b%' |
Use a single LIKE clause |
OR, legacy BETWEEN, and bracket-grouped clauses into V7.0-compliant form and prevents Tag Management from failing later when re-saving the picture.
Project Rebuild Procedure
If the four solutions above do not clear the dialog, rebuild the project from the most recent duplicate and apply the delta export. This recovers from any SSCE container that cannot be repaired.
- Copy the most recent duplicate
<ProjectName>.zipinto an empty folder. - Extract the contents with 7-Zip or WinRAR, preserving the directory layout.
- Start WinCC Project Duplicator (
CCProjectDuplicator.exe) and select the extracted folder as the source. - Open the duplicate in WinCC Explorer and confirm Tag Management opens without dialog.
- Apply the latest delta export: from the Explorer menu select File > Import > Project Export and choose the most recent
.exp. - Recompile all C scripts (Options > Compile All) and all VB scripts and check the Output window for warnings.
- Activate Runtime in test mode (Runtime > Start with Simulated Tags) and verify that all picture changes still load.
Verification Checklist
| Check | Pass Criterion | Command / Action |
|---|---|---|
| Tag Management opens | No dialog on double-click | Right-click Open on any tag |
| Project database consistent | SSCE checksum OK | sscerepair /v <project>.dcf |
| No file locks remain | Empty handle list | handle.exe -a <project>.dcf |
| WinCC_SysLog clean | No ERROR_INVALID_PARAMETER
|
Open WinCC_SysLog.log
|
| Runtime starts without dialog | No dialog on first activation | Runtime > Start |
| AlarmControl selection compiles | No invalid-clause warning | Compile all pictures |
| Antivirus exclusions active | Logs show no FILE_FLAG intercept |
Vendor EDR console |
Prevention and Hardening
- Apply the latest WinCC V7.0 update package. Siemens publishes consolidated updates for V7.0 SP3 and SP4 on the Siemens Industry Online Support portal; each update contains SSCE container fixes that reduce the dialog frequency.
- Separate the engineering and runtime roles. Never run Tag Management on the OS server while a runtime is active.
- Use a UPS on every engineering station. Most
.dcfcorruption is caused by an unsynchronised shutdown during a save. - Schedule nightly Project Duplicator runs and copy the resulting
.zipto a versioned backup share. - Configure the antivirus product to exclude
%ProgramFiles%\Siemens\Automationand the project root, then document the exclusion in the plant's security baseline. - Audit every AlarmControl instance after a V6.x-to-V7 migration to confirm only the canonical selection is in use.
FAQ
Why does the 'invalid argument' dialog appear only after Runtime start?
WinCC Runtime opens the <ProjectName>.dcf SSCE container in FILE_SHARE_READ mode. Tag Management then requests an exclusive edit lock; the SSCE layer returns ERROR_INVALID_PARAMETER (0x80070057), which WinCC surfaces as the user-facing dialog. Stop the WinCC Runtime and the CCProjectMgr service, remove any *.lck files, and Tag Management will reopen cleanly.
Which file actually triggers the error, the .dcf or the .log?
The .dcf file is the primary WinCC configuration database. The .log file is the SQL Server Compact transaction log. Both must be present, consistent, and unlocked. The companion shadow file <ProjectName>.dcf-shm is created by sscerepair.exe if it is missing.
Can the error be triggered by an invalid SQL clause in WinCC AlarmControl?
Yes. V7.0 AlarmControl rejects OR, parentheses grouping, and repeated Textxx arguments; the rejected clause is flagged at compile time and corrupts the picture metadata, which then causes Tag Management to fail the next time that picture is opened. Re-author the selection through the dialog (which generates the canonical SQL) and recompile the picture.
What is the maximum allowed length of an AlarmControl SQL statement in V7?
4096 characters. Statements longer than that are truncated by the AlarmControl and produce a runtime filter that silently excludes the overflow. Build the filter from canonical dialog selections rather than concatenating long strings.
Which WinCC V7.0 update resolves the dialog on Tag Management?
Install the latest cumulative update for the installed service pack: V7.0 SP3 Update 8 or later, or V7.0 SP4 plus the latest hotfix available on the Siemens Industry Online Support portal. The updates patch the SSCE container version bundled with WinCC and reduce the invalid-parameter dialog frequency.