RSLogix 5000 String Building with Ordered CONCAT Rungs

Brian Holt6 min read
Allen-BradleyBest PracticesRSLogix 5000
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

RSLogix 5000 string assembly works best as a visible sequence of small, ordered operations. Multiple readable rungs are safer than one large rung when predefined text and converted dynamic data must be joined with CONCAT.

Remove the quick fixes first

Do not compress every operation onto one rung just to make the routine shorter. A large rung hides execution order, makes online monitoring harder, and forces the next technician to trace several branches at once. It also does not make an incorrect data dependency correct.

Do not place several CONCAT instructions on parallel rungs that write independently to the same destination. If the routine executes those rungs during one scan, each write replaces the destination produced by the previous write. The last executed write becomes the value seen after the routine completes.

Do not treat a string conversion and a concatenation as though they occur simultaneously. When one instruction produces dynamic text and another consumes it, their order must be explicit. A consumer that executes first reads the value left from an earlier scan.

Check before moving on: Identify every instruction that writes the final string, every instruction that creates a converted value, and every intermediate string. Each destination should have one intentional writer at a given stage.

Lay out the required string in order

Write the finished message as a sequence of fields before editing ladder logic. Separate fixed text from dynamic text and show punctuation, delimiters, and spaces as fields rather than hiding them inside unrelated tags.

Stage Input A Input B Destination purpose
1 First predefined text Second predefined text or delimiter First intermediate string
2 First intermediate string Converted dynamic data Second intermediate string
3 Second intermediate string Remaining predefined text Final output string

This table is a dependency chain. Stage 2 cannot produce the current message until Stage 1 has completed, and Stage 3 cannot run correctly until Stage 2 has completed. Add or remove stages to match the actual format; do not invent empty stages merely to follow the example.

Name intermediate tags by purpose or stage so online monitoring shows how the message grows. Avoid reusing one scratch tag for unrelated messages unless the logic prevents those message builders from executing together.

Check before moving on: Read down the table and reconstruct the exact intended message without looking at the ladder routine. If the spaces and delimiters are unclear in the table, they will remain unclear in the controller.

Put conversion ahead of its first consumer

Place the instruction that converts dynamic data to a string before the first CONCAT that reads that converted tag. This matters because ladder logic is evaluated in execution order; graphical proximity alone does not create a dependency.

  1. Trigger the conversion under the same message-build condition used by the concatenation sequence.
  2. Write the converted result to a dedicated string tag.
  3. Place the first consuming CONCAT after the conversion in the executed path.
  4. Keep later concatenations below the earlier stages so the dependency is visible from top to bottom.

If conversion runs under a different condition, define what should happen when that condition is false. The tag otherwise retains its previous value, which can place stale dynamic data in an otherwise new message. Clear or deliberately preserve it according to the process requirement; make that choice visible in the logic.

Check before moving on: Change the source value while online and confirm that the converted string updates before the final message is assembled. Test the false condition too and verify whether retention or clearing matches the required behavior.

Chain each CONCAT through a separate stage

Build the message from top to bottom. Feed each stage from the preceding intermediate result rather than asking parallel rungs to compete for the same destination.

Converted dynamic data
        ↓
CONCAT stage 1 → Intermediate_1
        ↓
CONCAT stage 2 → Intermediate_2
        ↓
CONCAT stage 3 → Final_String

The stage names above are descriptive examples, not required tag identifiers. Use the project naming convention already applied to production tags.

Small rungs normally make this sequence easier to troubleshoot because each rung presents one transformation. Keep a rung within a practical online viewing area when possible. If a single rung remains readable and its execution dependencies are unambiguous, using one rung is acceptable; rung count is not the design objective.

Where several messages share fixed fragments, keep ownership clear. A predefined tag may feed many instructions, but an intermediate or final destination should not receive unexplained writes from separate branches, routines, or operating modes.

Check before moving on: Monitor the intermediate tags during one build request. Each tag should show the expected partial message, and the final string should match the last stage rather than whichever rung happened to execute last.

Control when the message is rebuilt

Decide whether the routine should assemble the message continuously or only when a build condition occurs. Continuous execution keeps the output aligned with its inputs, but it also rewrites the string every scan. Event-driven execution reduces needless work but requires a clear rule for retriggering after any input changes.

Apply one build condition across the complete dependency chain. Do not allow a later concatenation stage to run while its conversion or earlier stage is blocked unless retaining the old partial value is an explicit requirement. Mixed conditions create hybrid messages containing fields from different updates.

Also inspect every reference to the final destination. A correct builder can appear faulty when another routine, branch, or operating mode writes the same tag later in the scan. Cross-reference the tag and account for every write before changing the string logic.

Check before moving on: Exercise the build condition on, off, and through repeated transitions. Confirm that all stages update together and that no other writer changes the result after the builder completes.

Verify the complete message path

  1. Enter recognizable values for each predefined fragment and the dynamic source.
  2. Run one complete build and inspect the converted tag, every intermediate tag, and the final destination in order.
  3. Change only the dynamic source and repeat the build. Confirm that no value from the previous build remains.
  4. Change only one predefined fragment and repeat the test. Confirm that the expected stage and every downstream stage change.
  5. Test boundary conditions present in the application, including empty fragments and the longest legitimate inputs. Compare the resulting string with the destination capacity configured in the project.
  6. Cross-reference the final destination once more and verify that the displayed or transmitted consumer reads the completed tag.

Document the field order beside the routine or in the project description. The night-shift test is simple: a technician should be able to watch the partial strings grow without decoding a dense network of parallel branches.

Final check: Trigger the same operating sequence that uses the message, then verify both the controller value and the receiving function. A correct online tag is not sufficient if the downstream consumer reads another tag or captures the string before construction finishes.

FAQ

Can I use one rung for several CONCAT instructions?

Yes, if the dependency order remains obvious and the rung is easy to monitor. Split it into ordered rungs when branches or conversions make the sequence difficult to trace.

Can I write the same destination string from parallel rungs?

Avoid it. Multiple writes make the final value depend on execution order, so chain intermediate strings and give the final destination one intentional writer.

Does converted dynamic data update before CONCAT runs?

Only when the conversion executes first in the active path. Place conversion ahead of the consuming CONCAT and test the false condition for stale retained data.

Does splitting string assembly across rungs slow the PLC?

The required operations still execute; splitting them primarily exposes their order and intermediate results. Judge performance from actual task monitoring and controller diagnostics rather than rung count alone.

Stop here if intermediate strings are correct but the final tag changes elsewhere, the routine execution order cannot be established, or controller diagnostics show a fault during string handling. Preserve the failing values and cross-reference results, then escalate through the official manufacturer support channel with the project configuration and exact reproduction steps.

Back to blog