Problem Overview
On SIMATIC S7-1500 CPUs (S7-1511, S7-1513, S7-1515, S7-1516, S7-1517, S7-1518, and the S7-1500 Software Controller on IPC), the router address entered in the PROFINET interface properties appears to be accepted by TIA Portal in STOP mode and by the front-panel display, but it is reverted to 0.0.0.0 after a power-on reset (POR) or POWER OFF / POWER ON cycle. The same applies when the value is set through the CPU's online "Assign IP address" wizard or with PRONETA's single-device assignment.
Three symptoms cluster:
- The CPU retains the gateway only until the next restart; load memory is not updated.
- WinCC Comfort/Advanced, WinCC Unified, and TIA HMI panels connected over a routed path start to display
####instead of live process values once the gateway has been lost. - Direct engineering access from a PG/PC on the same physical subnet still works, because the local-subnet route does not require the gateway.
0.0.0.0. HMI tags freeze at ####. CPU reference architecture: SIMATIC S7-1500 system manual, Siemens Industry Online Support.Root Cause Analysis
The behavior is not a bug. It reflects the difference between the CPU's work memory (volatile RAM) and load memory (non-volatile SIMATIC Memory Card or internal flash). All three of the following write paths touch RAM only:
- TIA Portal > Online > Online & Diagnostics > Functions > Assign IP address / Assign router
- CPU front panel: Settings > Addresses > X1 / X2 > Router
- SIMATIC Automation Tool or PRONETA "Assign IP" functions targeting a single device
None of these paths triggers a write to the load memory image of the project. The CPU boots from the load memory image; if no router address has been compiled into the hardware configuration and downloaded to the device, the interface starts with 0.0.0.0 for the gateway and remains there until the next RAM write from one of the paths above. The same logic applies to the IP address and subnet mask of the interface.
The secondary question — "is the router the same as the gateway?" — is answered in the affirmative for IP routing. The PROFINET interface on an S7-1500 has a single routing entry called Router in the TIA Portal UI. This entry populates the operating system's default gateway and is functionally equivalent to the Default Gateway field in Windows network settings.
S7-1500 Routing Architecture
S7-1500 CPUs support two distinct routing mechanisms that are often confused in field service reports:
| Mechanism | Purpose | Where it is configured | What carries it |
|---|---|---|---|
| IP routing | Routes IP packets between IP subnets | CPU properties > PROFINET interface > Ethernet addresses > Use router | Default gateway in the IP stack of the CPU's own interface |
| S7 routing | Routes S7 protocol telegrams across S7 subnets through a gateway CPU | CPU properties > Routing > S7 routing (gateway), plus PG/PC routing table | S7 protocol layer; uses MAC / S7 connection routing, not IP |
| PN/PN coupler (proxy) | Bridges PROFINET subnets without IP routing | PN/PN coupler device config | PROFINET record data, transparent at IP layer |
The "Router address" field in the Ethernet addresses dialog controls IP routing only. S7 routing is enabled separately under Properties > General > Routing in the device configuration. See the Siemens function manual Overview of the routing mechanisms of S7-1500 CPUs for the architecture diagrams and selection criteria.
Reference topology
Prerequisites for a Permanent Router Configuration
- TIA Portal V16 or later (V17 / V18 / V19 / V20 behave identically for this configuration step).
- An offline project containing the S7-1500 station with the PROFINET interface of the CPU fully configured (IP address, subnet mask).
- Programming device with a routable connection to the CPU; this can be the same subnet as subnet A in the topology above.
- CPU in STOP if the IP / router is being changed for the first time after a fresh project download (Siemens does not require STOP for an IP change, but field practice recommends it to force a clean re-resolve of connections).
- The correct gateway IP for the subnet the CPU's interface physically resides on. If the CPU is on
192.168.0.0/24, the gateway must be reachable on that subnet (commonly the LAN-side address of the router/firewall, e.g.192.168.0.254). - Write/read access to the project (no exclusive project lock, no full know-how protection on the device configuration).
- A formatted SIMATIC Memory Card (SMC) of an approved type, 6ES7954-8Lx02-0AA0 or higher, if the CPU is configured to load from card.
Step-by-Step Configuration via TIA Portal
The router is part of the device configuration, not the program blocks. It must be entered offline and downloaded to the device.
- In the TIA Portal project tree, expand the S7-1500 station and double-click Device configuration.
- Select the CPU in the device view, then click the PROFINET interface [X1] (or [X2] if the CPU is dual-interface, e.g. S7-1518 / S7-1518T) in the graphic area.
- In the inspector window, switch to Properties > General > Ethernet addresses.
- In the IP protocol section, confirm that IP address and Subnet mask are correct for the local subnet.
- Tick Use router. The Router address input field activates.
- Enter the IP address of the default gateway on the local subnet (e.g.
192.168.0.254). Do not enter the WAN-side address of the router. - Right-click the CPU in the project tree and choose Compile > Hardware (rebuild all). Confirm that the compile finishes without errors.
- Right-click the device and choose Download to device > Hardware configuration. Use the "Search for online nodes" wizard if the CPU is not already selected; tick Overwrite IP address in the online device only if the IP itself changed.
- Wait for the download to complete and the CPU to restart (PROFINET interface renumbering can briefly drop the connection; this is normal).
- Reconnect with Online > Online & Diagnostics and navigate to Diagnostics > Ethernet addresses. The router field must now show the configured value.
- Power-cycle the CPU: POWER OFF, wait at least 5 seconds, POWER ON. After the CPU reaches RUN, re-check the router field via Online & Diagnostics. The value must persist.
CPU Display Configuration (Front Panel)
Modern S7-1500 displays allow IP, subnet, and router entries through Settings > Addresses > X1. This path writes to RAM. The behavior is documented and intended for commissioning where a PG is not yet available. The value is overwritten by the load memory image on the next restart.
Procedure on the display:
- Navigate Settings > Addresses > X1 > Router.
- Enter the IP address; confirm with OK.
- Cycle the CPU.
Result: the value reverts to 0.0.0.0 unless the value has also been compiled into the offline hardware configuration. The display is therefore a verification tool, not a configuration tool, for permanent installations.
Display-level lock: under Protection > Display > Know-how protection / Access level, the menu paths to change IP parameters can be password-protected. If the field engineer cannot reach the router dialog on the display, the protection level must be relaxed first, ideally via the TIA Portal project.
DHCP-Based Router Assignment
If the S7-1500 CPU is configured to obtain its IP address from a DHCP server, the same server can deliver the default gateway. The relevant DHCP option is option 3 (Router) per RFC 2132. Siemens DHCP support on the S7-1500 is documented in Principle of address assignment via DHCP (S7-1500).
Conditions for DHCP router delivery to work:
- CPU > Properties > Ethernet addresses > Obtain IP address from a DHCP server is enabled.
- DHCP server is configured with option 3 set to the local-subnet gateway IP.
- DHCP lease time has not expired; on lease expiry the CPU will renew, and if option 3 is missing from the renewal the gateway may drop back to
0.0.0.0until the next full handshake. - The CPU and the DHCP server are on the same broadcast domain (no router between them).
- DHCP client identifier: the S7-1500 sends its PROFINET device name as the client identifier; some DHCP servers require a name reservation to assign option 3.
For deterministic behavior in industrial networks, prefer a static gateway in the compiled hardware configuration over DHCP. DHCP is useful for temporary commissioning or for fleets that move between subnets.
S7 Routing vs. IP Routing
Many field engineers enable "S7 routing" expecting that to make the CPU reachable across subnets. S7 routing is a protocol-level mechanism for S7 communication and does not populate the IP default gateway. If the use case is "let a remote PG reach this CPU over a routed path," the IP gateway is what is needed. If the use case is "let an HMI on subnet B communicate with the PLC on subnet A using S7 protocol," S7 routing through a gateway CPU or SCALANCE can be used in addition to or instead of IP routing.
| Use case | Use IP routing (gateway) | Use S7 routing |
|---|---|---|
| Remote PG / TIA Portal across subnets | Yes | Useful if only S7 protocol must traverse, otherwise plain IP is simpler |
| WinCC Unified / Comfort Panel cross-subnet | Yes (HMI also needs gateway) | Optional |
| Modbus TCP / OPC UA / PROFINET across routers | Yes | No |
| Replacing legacy S7-300/400 PG routing | No (legacy did not need it) | Yes |
| Mail / SNMP / syslog to a central server | Yes | No |
HMI "####" Error Correlation
When an HMI displays #### in a tag field, the HMI is signaling that the tag value cannot be read at the configured update rate. The four most likely root causes when a router change has just been made:
-
HMI gateway not configured. The HMI also needs the IP address of its local-subnet router. If the HMI is on
192.168.1.0/24with gateway192.168.1.253, and the gateway is missing, the HMI cannot reach192.168.0.20. - PLC connection points to wrong IP. The HMI connection in the TIA project may still reference the old IP if the device was renumbered.
-
PLC gateway lost on restart. The symptom in this article: PLC gateway back to
0.0.0.0means the PLC cannot reply on a routed path. The HMI then keeps timing out. - PLC and HMI on the same physical subnet. If so, neither gateway is required and the issue is purely the connection string.
Use TIA Portal > Online > Accessible nodes to verify the HMI's reachable IP from the PG. From the HMI, use Control Panel > Network & Internet > Ping (or the diagnostic page on Unified Comfort Panels) to confirm the PLC is reachable. WinCC Unified stores the gateway in the runtime configuration under Network settings > Ethernet.
Project Protection and Access Control
Two protection-related settings interfere with online IP changes and must be understood before assuming a write was accepted:
| Setting | Path | Effect |
|---|---|---|
| Access level > HMI / OPC UA / etc. | CPU properties > Protection & Security | Restricts which online functions are accepted without password |
| "Permit access with PUT/GET communication" | CPU properties > Protection & Security > Connection mechanisms | Blocks or allows PUT/GET; does not affect IP configuration writes |
| Know-how protection on the device configuration | Right-click PLC > Properties > General > Protection | Does not block hardware config download from the same project |
| Project-level user rights | TIA Portal > Project tree > Security > Users and roles | Blocks edits on a multi-user project |
For the symptom described, none of these is normally the cause of the power-cycle loss. They become relevant if the user expects to write IP parameters from a different project (not the source project) and sees the write rejected. The recommendation for permanent commissioning is to embed the IP / router in the project source itself and protect the project against unauthorized edits at the source-control level (e.g. TIA Portal multiuser or a Git workflow).
Verification Procedures
After the download and power-cycle test, run the following checks:
-
Online diagnostics. TIA Portal > Online > Online & Diagnostics > Diagnostics > Ethernet addresses > IP / Subnet / Router. All three must show the configured values, not
0.0.0.0. -
Local ping from the PG. Open a Windows command prompt on the PG and run
ping 192.168.0.20. The response must come from the CPU's MAC in the OUI prefix00:0E:8C(older S7-300/400) or28:63:36(newer S7-1500 modules). - Routed ping from subnet B. From a PG on subnet B, ping the PLC. If the routed path is required, this validates that the gateway is correct on both ends.
- PRONETA scan. Run Siemens PRONETA in network analysis mode to confirm the CPU appears with the expected IP and that no duplicate IP is on the network.
- Power cycle x3. POWER OFF / POWER ON three times consecutively. Each time the router must come back with the configured value. This catches memory-card-related issues where a single boot appears correct but subsequent boots revert.
-
HMI live value test. On the HMI, switch to a screen with a tag derived from the PLC and confirm that the
####is replaced by the live value. - Firmware-downgrade test. If a firmware update is planned, perform the upgrade, then re-download the project. Some firmware versions reset non-volatile IP parameters if the project on the memory card does not match.
If the value still reverts, the most likely remaining cause is a project that has not been re-compiled and downloaded after the IP edit (e.g. another engineer's project on the engineering server has overwritten the device). Use TIA Portal's project comparison (menu > Tools > Compare) to identify configuration drift between offline and online.
Troubleshooting Matrix
| Symptom | Probable cause | Verification | Remedy |
|---|---|---|---|
| Router reverts to 0.0.0.0 after power cycle | Online write only, not committed to load memory | Offline > Hardware configuration > Compare with online | Compile HW, download HW configuration |
| Router accepted in STOP, lost on POWER ON | Online & Diagnostics path writes RAM only | Check load memory image in project | Configure offline, download HW |
| HMI shows #### after router configured | HMI gateway missing or wrong | HMI Control Panel > Network | Set HMI gateway, recompile HMI |
| HMI shows #### but PG online works on same subnet | PLC gateway correct, HMI cannot route | Ping PLC from HMI | Set HMI gateway in the same subnet as the HMI |
| CPU display lets you set router, value reverts | Display write is RAM-only | Restart CPU and read display | Compile router into offline HW config |
| "Use router" checkbox greyed out in TIA Portal | Interface assigned to a PROFINET IO controller role only | Properties > PROFINET interface > Operating mode | Set "Not IO device / Not IO controller" or assign explicit PN interface |
| Duplicate IP on network | Another device using same IP | PRONETA scan | Re-number one of the devices |
| Cannot download HW config | PG in different subnet, no gateway on PG | PG ipconfig | Add PG default gateway or connect via same subnet |
| Router present, but PG cannot cross subnet | PC firewall blocks inbound ICMP / TCP | Disable Windows Firewall temporarily | Add firewall rule for the subnet range |
| Router reverts after firmware update | FW update may reset non-volatile IP params if project not present | Project on memory card? | Re-download project after firmware update |
| DHCP router works initially, drops later | DHCP server not sending option 3 on renewal | DHCP server logs | Static gateway in offline HW config preferred |
| Online > Assign IP address fails with error | Different project trying to overwrite protected IP | Check protection level | Use the source project to change IP, or adjust protection |
| Router shows, but Modbus TCP connection fails | Modbus client uses its own gateway, not the PLC's | Check client IP stack | Configure client gateway to PLC subnet |
| Router correct but OPC UA discovery returns empty | OPC UA discovery uses IP multicast; router blocks it | Test with opc-ua-test-client
|
Configure direct endpoint, not discovery |
Firmware-Specific Considerations
For the S7-1500 Software Controller (CPU 1505SP / CPU 1507S / CPU 1508S) running as of firmware V20.8, Siemens revised the IP routing behavior to better support IPC deployments with multiple Ethernet interfaces. Key points per the Siemens application document IP routing with the S7-1500 Software Controller as of firmware V20.8:
- Routing must be explicitly enabled per interface: tick Use router and enter the local-subnet router address. The example in the document uses
192.168.73.2. - Multiple PROFINET / Ethernet interfaces can each have their own router; they are not shared.
- Firmware V20.8 onward stores the gateway in the project on the memory card of the IPC's CFast / SSD, but only if the project contains the value.
- Earlier firmware (V20.6 and below) on the Software Controller had known issues where the router was not honored for certain S7 routing paths; the workaround was to enable IP forwarding at the IPC level, which is not recommended in production.
For S7-1500 hardware CPUs (S7-151x), the firmware-version dependence is minimal; the configuration steps are identical from firmware V1.5 onward. Always check the release notes for the firmware on the CPU; major releases (V2.0, V2.5, V2.9, V3.0) occasionally reset to defaults if a downgrade is performed without a project reload.
Diagnostic Commands and Code Snippets
For quick verification on a Windows PG in the same subnet:
REM Verify the PLC IP and MAC
arp -a | findstr 192.168.0.20
ping -n 4 192.168.0.20
REM Trace the route from subnet B to the PLC
tracert 192.168.0.20
REM Resolve DNS-style name if name resolution is enabled
nslookup s7-1500-plant1
REM Show the PG's own routing table
route print
For PRONETA network scan, the CLI flag to focus on a single subnet:
Proneta.exe /scan /subnet 192.168.0.0/24 /report network_report.html
For an SCL block in the CPU that reads back the current gateway at runtime (read-only, for diagnostics):
// SCL — read current IPv4 gateway of PROFINET interface X1
#retCode := RDREC(SYS1:RDREC_DB,
ID := 0,
INDEX := 1, // IF1 record index 1 = IP parameters
MLEN := 24,
BUFFER := #buf);
IF #retCode = 0 THEN
#gateway := DWORD_TO_IP(#buf.DWORD4); // offset 8 = default gateway
END_IF;
For quick reference, the byte layout of the Siemens "IP parameters" record (index 1) used above is:
| Offset (bytes) | Field | Length (bytes) |
|---|---|---|
| 0 | IP address | 4 |
| 4 | Subnet mask | 4 |
| 8 | Default gateway | 4 |
| 12 | DHCP server | 4 |
| 16 | DNS server 1 | 4 |
| 20 | DNS server 2 | 4 |
The field at offset 8 in the Siemens record is labeled "Default Gateway" in the documentation; this is the value that the TIA Portal UI presents as the "Router address." Offsets are platform-endian; use the appropriate byte-swap helpers when reading into PLC tags.
S7-1500 vs S7-1200 vs S7-300 Routing Notes
| Platform | Default gateway configurable? | Path in TIA Portal | Power-cycle behavior |
|---|---|---|---|
| S7-1500 (V1.5+) | Yes | CPU > PROFINET interface > Ethernet addresses > Use router | Persists when compiled into HW config; lost if set online |
| S7-1200 (V4.0+) | Yes | CPU > Ethernet addresses > Use router | Persists when compiled into HW config; lost if set online |
| S7-300 (legacy) | Limited (S7 routing only) | CPU > Properties > General > Gateway | Stored in system data block |
| ET 200SP CPU | Yes | Same as S7-1500 | Same as S7-1500 |
| S7-1500 Software Controller | Yes (V20.8+ recommended) | Same as S7-1500 | Stored on IPC storage; requires project with value |
The mechanism is consistent across the S7-1500 / ET 200SP CPU / S7-1200 families: the router is part of the device configuration and must be downloaded to the device to persist. Field engineers moving from S7-300 should be aware that S7-300 gateways were set in system data blocks via NetPro, not in the device configuration.
FAQ
Why does my S7-1500 router address reset to 0.0.0.0 after every restart?
The value was written through Online & Diagnostics, the CPU display, or PRONETA, all of which target volatile work memory. Compile the router into the offline hardware configuration (CPU > Properties > Ethernet addresses > Use router) and download the hardware configuration to the device so it is stored in non-volatile load memory.
Is the "Router address" the same as the "Default gateway"?
Yes, for IP routing. The S7-1500 PROFINET interface has a single routing field labeled "Router" in TIA Portal; this populates the operating system's default gateway and is functionally identical to the "Default Gateway" field on a Windows network adapter.
The HMI shows #### after I set the PLC router. What is wrong?
Either the PLC's gateway was lost again (back to 0.0.0.0 after restart), or the HMI's own gateway is missing. Set the HMI gateway to the local-subnet router in the HMI's network configuration, recompile, and download. Verify with a ping from the HMI to the PLC's IP before assuming the PLC is at fault.
Can I configure the router from the S7-1500 display without a PG?
Yes, but the change is temporary. The display writes to RAM and is overwritten by the load memory image on the next restart. Use the display for initial commissioning only, and load the project with the same value for permanent operation.
Do I need both "Use router" and a static IP, or can I use DHCP?
Both are valid. With DHCP, enable "Obtain IP address from a DHCP server" and ensure the DHCP server sends option 3 (Router) per RFC 2132. For deterministic industrial behavior, prefer a static IP with a static router compiled into the hardware configuration.