S7-300 and S7-400 PLC Lifecycle Siemens Support Phases and Spares

David Krause11 min read
PLC HardwareSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview of Siemens SIMATIC Product Lifecycle Management

Siemens applies a four-stage Product Lifecycle Management (PLM) model to every automation component sold under the SIMATIC family, including the S7-300 and S7-400 PLC families. The PLM phases are documented in the official Siemens Industry Online Support entry SIMATIC Product Lifecycle Phases (entry ID 91688124) and are referenced whenever a part is purchased, quoted, or archived in the Siemens Mall (Industry Mall).

The PLM milestones are designated PM300, PM400, PM410, and PM490. They apply identically to CPUs, signal modules (SM), function modules (FM), communication processors (CP), power supplies (PS), interface modules (IM), and SIMATIC HMI accessories. When a project engineer asks "for how many years will Siemens provide support or spares for the S7-300 and S7-400," the correct technical answer is: up to 22 years from initial product delivery release — 12 years of active delivery plus 10 years of spare-part commitment. Field service life of properly maintained hardware frequently exceeds this window.

PM300: Active Product (Product Delivery Release)

PM300 marks the official start of normal commercial availability. From the PM300 milestone onward, the product is orderable through the Siemens Mall for up to 12 years (active selling phase). During PM300 the catalog is fully stocked, firmware updates are issued as needed, technical data sheets are actively maintained, and migration kits to successor families (e.g., ET 200SP or S7-1500) are typically offered.

Parameter Value
Phase code PM300
Status label in Siemens Mall Active Product
Typical duration Up to 12 years from PM300
Firmware updates Issued as needed
New deliveries Yes — full catalog availability
Spare-part commitment Not yet started; will begin at PM400
During PM300, plan a migration roadmap. The 12-year clock starts at PM300 and the spare-part guarantee begins only after PM400 is published, so the longest combined availability window for the same article number is the PM300-to-PM490 span.

PM400: Announced Phaseout

PM400 signals the end of the active selling phase and the beginning of a 10-year spare-part commitment period. From PM400 onward the product is no longer produced in volume, but new units in unopened original packaging are still available while warehouse stock lasts. Engineering changes are frozen except where safety-relevant corrections are required.

Parameter Value
Phase code PM400
Status label in Siemens Mall Phase-out announced / announced discontinuation
Typical duration Bridge between PM300 and PM410; typically weeks to a few months
New deliveries Limited — remaining stock only
Spare-part commitment 10 years (begins at PM400)
Documentation updates Corrective only

The PM400 announcement is the critical trigger for spare-part stocking decisions. Sites that depend on a specific S7-300 CPU or S7-400 CPU should place a final-volume order at this milestone, including any peripheral modules that share the same lifecycle bucket.

PM410: Product Cancellation (End of Production)

PM410 starts the dedicated spare-part phase. New production is stopped. The product can still be ordered, but only as a spare part with possible minimum-quantity rules, longer lead times, and—in some cases—replacement through refurbished (exchange) units. With few exceptions, marketing brochures, configurator entries, and the standard catalog are withdrawn.

Parameter Value
Phase code PM410
Status label in Siemens Mall Product Cancellation / End of Production
Typical duration Fills the remainder of the 10-year spare-part commitment
New deliveries No new production; spare-part basis only
Repair service Available while components are obtainable from Siemens sub-suppliers
Spare-part commitment Active — runs until PM490

PM490: Product Discontinuation

PM490 is the formal endpoint. The product is no longer available from Siemens, support is discontinued, and spare-part obligations expire. Documentation remains accessible as an archived entry, but no firmware patches, no corrections, and no exchange units will be supplied.

Parameter Value
Phase code PM490
Status label in Siemens Mall Product Discontinuation
Spare-part commitment Ended
Support Discontinued
Documentation Archived; remains visible for reference
Replacement path Migration to successor family (e.g., S7-1500 / ET 200SP)
PM490 is a hard cut-off for spare parts but is not a hard cut-off for installed hardware. Many S5-115U systems installed in the 1980s continue to run in 2024 because their I/O and mechanical assemblies remain serviceable; however, Siemens will no longer provide any official replacement parts or technical support once those part numbers reach PM490.

Aggregated Lifecycle Timeline

Phase Code Activity Cumulative Years from PM300
Active selling PM300 Full catalog availability 0 – 12
Phase-out announced PM400 10-year spare-part commitment begins ~12
End of production PM410 Spare-part only delivery 12 – 22
Discontinuation PM490 No further support or spares ~22

The maximum official support window for a single SIMATIC article number is therefore approximately 22 years from PM300, regardless of family (S7-300, S7-400, ET 200, HMI, SINAMICS, etc.).

Checking Lifecycle Status of a Specific Part Number

The lifecycle status of every MLFB (Siemens order number, e.g., 6ES7…) is published in two places:

  1. Siemens Industry Online Support — support.industry.siemens.com → product search → entry for the article number.
  2. Siemens Industry Mall — the price-and-availability lookup displays the PLM code (PM300 / PM400 / PM410 / PM490) directly on the product page.

Example part number:

Article Number:     6ES7315-2EH14-0AB0
Product Description: SIMATIC S7-300 CPU 315-2 PN/DP
Family:              CPU 315-2 PN/DP
Work memory:         384 KB
Interface 1:         MPI/DP 12 Mbit/s
Interface 2:         Ethernet PROFINET, 2-port switch
Media:               Micro Memory Card required
Product Lifecycle:   PM300 — Active Product

For a large site inventory, generate an accurate parts list (CPU + SM + FM + CP + PS + IM + HMI + cables + memory cards) and look up each MLFB individually. Mixed systems are common: an S7-300 CPU may still be PM300 while an older SM321 signal module on the same rack is already PM410. Procurement must respect the shortest remaining lifespan on the BOM.

S7-300 Lifecycle Considerations

The S7-300 family entered its PM300 active phase in 1994 (first generation CPU 312 IFM / CPU 313 / CPU 314) and is being phased out model-by-model as customers migrate to S7-1500 with ET 200SP. Successive CPU generations (e.g., CPU 315-2 PN/DP, CPU 317-2 PN/DP, CPU 319-3 PN/DP) have been moved through PM400 announcements in waves since roughly 2018.

Specific S7-300 lifecycle items to monitor:

  • CPU 31x and 31xC series — early variants already reached PM410; later PN/DP variants are still PM300 or PM400.
  • Micro Memory Cards (MMC) — most S7-300 CPUs from the 314 IFM era onward require an MMC; MMC part numbers have a separate lifecycle from the host CPU.
  • Front connectors (6ES7392-…) — long PM300 lifespans but worth checking individually.
  • Signal modules SM321 / SM322 / SM331 / SM332 — variants are split; e.g., 6ES7321-1BL00-AA0 may differ in lifecycle from 6ES7321-7BH01-0AB0.
  • F-CPUs and F-modules — see dedicated section below for additional PFD/PFHD documentation.

S7-400 Lifecycle Considerations

The S7-400 family entered service in 1995 and has a longer generational tail than the S7-300. Siemens published a formal "SIMATIC S7-400 discontinuation of sale" announcement in waves starting in 2020, with most CPUs entering PM400 in 2020–2023. The standard 10-year spare-part commitment therefore runs into the 2030–2035 window for typical S7-400 installations. AS 410 single stations and AS 410H / AS 400H redundant stations share a common lifecycle but each MLFB is checked individually.

Specific S7-400 lifecycle items to monitor:

  • CPU 412, 414, 416, 417 series — base variants and PN/DP variants have separate lifecycles.
  • CP 443-1 / CP 443-5 Extended — these communication processors are decoupled from the CPU lifecycle and may remain PM300 longer.
  • PS 405 / PS 407 power supplies — typically share the longest PM300 windows; check 10 A / 20 A variants separately.
  • F-modules (F-CPU, F-SM, F-DO) — see dedicated section below.
  • Memory cards (RAM, Flash, MC) — storage media have shorter practical lifespans than the host PLC and should be replaced preventively.

S7-300 / S7-400 Migration Path to S7-1500

Siemens provides explicit migration tooling and successor families for both S7-300 and S7-400:

Legacy PLC Recommended Successor Migration Tool
S7-300 / ET 200M S7-1500 + ET 200SP SIMATIC Automation Tool, TIA Portal Migration Tool
S7-400 single station S7-1500 (high-end) TIA Portal with S7-1500 CPU 1518 / 1518F
S7-400H redundant S7-1500H redundant TIA Portal; S7-1500RH for R1 redundancy class
S7-300 F-CPU S7-1500F CPU + F-modules ET 200SP TIA Portal Safety; F-CPU migration wizard
S7-400 F-CPU S7-1500F / S7-1500HF TIA Portal Safety

The migration is non-trivial: STEP 7 V5.x projects must be converted to TIA Portal, I/O wiring must be remapped, and PROFIBUS DP slaves (on the S7-300/400) are commonly replaced with PROFINET IO devices (on the S7-1500). Plan migration windows in advance of PM410 to avoid rush engineering.

Special Note on F-Modules: PFD and PFHD Parameters

Fail-safe (F-) CPUs and F-modules carry additional lifecycle-relevant parameters: PFD (Probability of Failure on Demand) and PFHD (Probability of dangerous Failure per Hour). These values are used to calculate the safety integrity level (SIL) of a safety loop and are documented separately from the standard PLM phase. Refer to the official FAQ Which values can you use with F-CPUs and products of the ET 200 family for PFD and PFHD? for the latest numerical table.

Important: PFD/PFHD values are valid for the certified mission time (typically 20 years) and may be revised if the module firmware is updated. Safety lifecycle parameters are unrelated to the PM300/PM400 commercial lifecycle — a module may be PM410 commercially and still have a valid PFD/PFHD certificate, or vice versa.

Field Operating Life vs. Siemens Support Life

The Siemens PLM timeline governs Siemens' commercial support. The actual field operating life of an S7-300 or S7-400 depends on environmental conditions:

Stress factor Accelerates aging Mitigation
Ambient temperature > 40 °C continuous Electrolytic capacitor drying; solder joint fatigue Cabinet cooling; verify MTBF data
Humidity > 85 % or condensing PCB creep; connector oxidation Heaters; conformal-coated modules (-CC)
Dust / corrosive atmosphere (e.g., H2S, chlorine) Contact wear; dendrite growth Sealed cabinet; conformal coating
Vibration > 1 g RMS at panel Connector back-off; cracked solder Vibration mounts; locking clips
Power cycle count Inrush on electrolytics UPS on PS 407 / PS 307
Battery absence on SRAM CPUs Program loss when buffer fails Annual battery replacement

Field reports confirm that S5-115U PLCs installed in the 1980s are still operational in 2024 in well-controlled factory environments. S7-300 and S7-400 hardware has equivalent or better MTBF ratings and is expected to operate for 15–25+ years on the factory floor if maintained correctly. However, operating beyond PM490 means no Siemens spare-part guarantee; the operator assumes all obsolescence risk.

Spare-Part Planning Strategy

  1. Inventory every MLFB in the control cabinets, including CPUs, SMs, FMs, CPs, PSs, IMs, HMI panels, and cables.
  2. Pull lifecycle status for each MLFB from the Siemens Industry Online Support portal or the Industry Mall.
  3. Classify each item by minimum remaining years to PM490.
  4. Stock critical spares at PM400 — typically 1× CPU of each type, 10–15 % of the SM population, 1× of every CP and FM, plus all firmware-loaded memory cards.
  5. Schedule migration before PM410 to avoid rush engineering; build the new S7-1500 system on TIA Portal V17 or later and validate in parallel with the running S7-300/S7-400.
  6. Archive programs and project files on durable media; the STEP 7 V5.x project for the legacy system is the only path to firmware-equivalent operation if a CPU swap is needed.
  7. Track F-module mission time separately; replace F-CPUs and F-SMs before their 20-year PFD/PFHD mission time expires, independent of PLM.

Environmental and Storage Notes

  • Store spare CPUs and modules in their original anti-static packaging at 0–60 °C and 5–95 % non-condensing humidity.
  • Spare S7-300/S7-400 modules stored for more than 5 years should be functionally tested before being placed into a live system, especially electrolytic capacitors and backup batteries.
  • Conformal-coated variants (MLFB suffix -CC, e.g., 6ES7315-2EH14-0AB0 → no -CC for this MLFB; check per article) are preferred for spare-part stocks intended for harsh environments.

Frequently Asked Questions

How many years of support does Siemens guarantee for an S7-300 or S7-400 PLC?

Siemens guarantees up to 22 years of total support for any SIMATIC article number: 12 years of active selling (PM300) plus 10 years of spare-part delivery (PM400 → PM490). The exact window depends on the individual MLFB; check the Siemens Industry Online Support entry or the Industry Mall for the specific part.

How do I find the current lifecycle phase of an S7-300 module?

Enter the MLFB (e.g., 6ES7315-2EH14-0AB0) into the search field at Siemens Industry Online Support or in the Siemens Industry Mall. The product page lists the current phase as PM300, PM400, PM410, or PM490.

What is the difference between PM400 and PM410?

PM400 is the announcement of phase-out and triggers the 10-year spare-part commitment; new units from existing stock are still orderable. PM410 is the actual end of production; from this point on the part is supplied only on a spare-part basis, possibly with exchange units.

Can an S7-300 or S7-400 keep running after PM490?

Yes — many installed systems continue to operate for years after PM490 because the hardware itself remains functional. However, Siemens will no longer supply spare parts, firmware updates, or official support. The operator bears all obsolescence risk and must plan a migration before critical components fail.

What is the modern replacement for an S7-300 or S7-400?

For S7-300: migrate to S7-1500 CPUs with ET 200SP distributed I/O on PROFINET. For S7-400 (single station): use high-end S7-1500 CPUs such as CPU 1518-4 PN/DP. For S7-400H redundant: use S7-1500H or S7-1500RH. Migration is performed in TIA Portal using the STEP 7 V5.x project converter.