S7-300 High-Speed Weighing: SIWAREX and SM 335 Module Selection

David Krause16 min read
PLC HardwareSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Application Profile: 10-Channel Multi-Cell Weighing at 5–6 Hz

The reference application specifies a small-frame PLC (S7-300 / SLC 500 class) that must read ten strain-gage load cells simultaneously at 5–6 conversions per second per channel, deliver true weight values rather than threshold comparisons, and provide 10 V DC bridge excitation per cell. The aggregate throughput floor is therefore 10 channels × 6 Hz = 60 conversions / second. Because the design eliminates the external signal conditioner to minimize group delay, the analog front-end has to accept raw bridge output (typically 1–3 mV/V at full scale) and resolve to weighing accuracy without a discrete instrumentation amplifier in the path.

This profile is incompatible with general-purpose analog input cards because their resolution and channel scan architecture are tuned for process signals (4–20 mA, ±10 V), not microvolt bridge outputs. Three product families genuinely fit:

  • Siemens SIWAREX weighing modules — purpose-built bridge front-ends that mount in the S7-300 rack.
  • Siemens SM 335 (6ES7 335-7HG01-0AB0) — fast analog I/O module for closed-loop control.
  • Generic analog input cards (e.g., 1746-NI4 on SLC 500, TSXISPY101 on Schneider TSX Premium) used with either external instrumentation amplifiers or with the load cell's internal amplifier.
Important: If sub-millisecond per-channel conversion and direct bridge excitation are both required, only the SIWAREX family (or an equivalent vendor weighing module such as the Schneider TSXISPY101) is correct. General-purpose fast AI modules like the SM 335 do not provide regulated bridge excitation and require a separate excitation supply.

Load Cell Signal Fundamentals

A 350 Ω, 2 mV/V load cell excited with 10 V DC produces a full-scale differential output of 20 mV. Resolving 0.05 % of full scale requires a least-significant bit (LSB) of 10 µV at the ADC input. The relationships below govern module selection:

Full-scale bridge output:

VFS = S × VEXC

where S = sensitivity (V/V), VEXC = excitation voltage.

Required ADC noise-free resolution:

Resolution (bit) ≥ log2(VFS / VLSB)

For 20 mV / 10 µV: log2(2000) ≈ 10.97 → 11 bits minimum for 0.05 %; 16 bits provides comfortable headroom for noise and tare.

The signal chain also must reject common-mode noise from motor VFDs, thermcouple-like ground loops, and 50/60 Hz mains pickup. Weighing electronics therefore combine a true instrumentation amplifier, a programmable gain stage, and either a sigma-delta or dual-slope ADC with internal digital filtering. Reference designs from converter vendors describe these topologies in detail in Texas Instruments SNAA099 — Ultra-High Speed ADCs Revolutionize Digital Receiver Design and Analog Devices AN-835 — Understanding High Speed ADC Testing and Evaluation.

Siemens S7-300 SIWAREX Weighing Module Family

SIWAREX modules are the dedicated weighing front-end for S7-300. They mount in the standard 40 mm slot of the S7-300 I/O rack and communicate to the CPU over the backplane as distributed I/O; programming is performed through a Siemens function block library (SIWATOOL) and standard STEP 7 ladder or SCL. The S7-300 platform is described in the Siemens SIMATIC S7-300 product documentation.

Module Order Number (example) Channels Update Rate Resolution Excitation
SIWAREX U 7MH4601-1AA01 1 load cell (or 4 with junction box) 50 / 60 Hz selectable 16 bit (≈ ±20 000 counts) 10.0 V DC regulated, ≤ 150 mA
SIWAREX MS 7MH4603-1AA01 1 (multi-channel variants available) 50 / 60 Hz 16 bit 10.0 V DC regulated
SIWAREX FTC 7MH4900-1AA01 2 (belt scale, loss-in-weight) 50 / 60 Hz 16 bit 10.0 V DC regulated
SIWAREX CS 7MH4910-0AA01 1 (for S7-1200 / ET 200SP) 50 / 60 / 100 Hz 16 bit 5 V or 10 V selectable
SIWAREX WP321 7MH4908-1AA01 1 (ET 200SP) up to 1 kHz 24 bit 5 V / 10 V selectable

For ten channels of 5–6 Hz weighing on an S7-300, the typical configuration is one SIWAREX module per load cell pair (using the SIWAREX junction box to parallel up to four cells per module) or ten SIWAREX MS / U modules when channels must remain independent. Each module occupies a single slot and is addressed by the CPU as a standard analog input word. Update rate and excitation voltage are configured through SIWATOOL V7 (or the current Siemens weighing configuration utility), not through hardware jumpers.

Why 50 Hz is sufficient: 50 Hz corresponds to a 20 ms cycle. With a 5–6 Hz requirement the controller can average multiple reads (4–10 per decision) and still meet the update period, dramatically improving signal-to-noise ratio at the cost of one PLC scan of latency. Most weigh-in-motion and batching applications specify 10–20 readings averaged before the next control decision, which is well within the 60 Hz aggregate budget.

SM 335 High-Speed Analog I/O Module (6ES7 335-7HG01-0AB0)

The SM 335 (order number 6ES7 335-7HG01-0AB0) is a fast analog I/O module designed for closed-loop control, not dedicated weighing. Its relevant characteristics are summarized in the table below based on the Siemens SIMATIC S7-300 module data manual.

Parameter Specification
Analog inputs 4 (configurable ±10 V, 0–10 V, ±5 V, 0–5 V, ±20 mA, 4–20 mA, RTD)
Analog outputs 4 (±10 V or ±20 mA)
A/D conversion time per channel ≤ 0.05 ms (typ.) — order of magnitude faster than 50 Hz
Digital resolution 14 bit
Encoder inputs 3 counter / encoder inputs (24 V, 10 kHz) on the same module
Bridge excitation Not provided. External excitation required.
Channel-to-channel isolation Yes (functional isolation, not 1 500 V reinforced)
Use case High-speed analog feedback, cam emulation, torque / pressure control, not raw bridge readout

The SM 335 is the right answer when:

  • the load cell already has an integrated amplifier producing 0–10 V or 4–20 mA,
  • the application needs microsecond-class latency (e.g., weight-based force control inside a single servo cycle), or
  • the same module is also used for fast actuator outputs.

It is the wrong answer when the load cell exposes a raw mV/V bridge, because the input voltage ranges (≥ ±5 V) are 250 times larger than a 20 mV bridge signal — the 14-bit ADC then offers no useful resolution below 5 mV, which corresponds to 25 % of a typical load cell range.

Allen-Bradley SLC 500 Alternative: 1746-NI Family

The Allen-Bradley SLC 500 platform offers analog input modules that physically fit the I/O rack but do not provide bridge excitation. They are usable only with pre-amplified load cells.

Module Channels Input Range Resolution Update Time Notes
1746-NI4 4 ±10 V, 0–10 V, ±5 V, 0–5 V, 0–20 mA, 4–20 mA 14 bit ~5 ms (all ch.) Requires external 10 V excitation and instrumentation amp
1746-NI8 8 ±10 V, 0–10 V, 0–20 mA, 4–20 mA 14 bit ~10 ms (all ch.) Same — 8 channels reduce per-channel scan latency
1746-NI16I 16 Current only 16 bit ~30 ms (all ch.) 4–20 mA only — load cell must have integral transmitter
1746sc-NI8U 8 Universal, ±10 V, ±5 V, RTD, TC, mA 16 bit ~8 ms (all ch.) Same pre-amplification requirement

For ten raw bridge channels, a typical SLC 500 implementation would pair each 1746-NI4 input with a separate 4-channel load cell signal conditioner (e.g., RDP S7DC, Hardy HI 2151-30A, or similar). The total module count grows: 10 cells → 10 amplifier channels → 3 × 1746-NI4 slots minimum, plus 10 excitation supplies (or one shared precision 10 V reference with sufficient current budget).

Decision point: If the customer is willing to use a vendor weighing instrument (e.g., Hardy HI 1771-WS) on a front-end industrial network, an SLC 500 with the standard analog input may still be acceptable. If the design must be "off-the-shelf PLC with no external weigh instrument," SIWAREX remains the cleaner solution.

Schneider TSX Premium TSXISPY101 ISP Plus

The Schneider TSX Premium platform hosts the TSXISPY101 "ISP Plus Integrated Weighing System" module, a dedicated weighing front-end for Modicon Premium / TSX Premium PLCs. The module:

  • Supports 1 to 8 load cells per module through a junction box,
  • Samples at 50 Hz (one conversion every 20 ms),
  • Provides bridge excitation internally,
  • Exposes measured weight, net weight, and zero/span calibration over the Premium backplane.

With one TSXISPY101 per eight cells, a ten-channel system needs two modules, leaving six of the rack slots free for additional Premium I/O. The TSX Premium processor accepts up to 32 ISP Plus modules in a single rack, so channel density is rarely the limit. Schneider's weighing block library handles filtering, tare, and flow-rate integration in PL7 or Unity Pro.

For greenfield installations where the integrator is not committed to Siemens, the TSXISPY101 is the closest direct competitor to SIWAREX U on the same architectural level (PLC-resident weighing front-end).

Aggregate Throughput Calculation

Validate the 5–6 Hz / 10-channel requirement with the following calculation:

Required throughput = Ncells × fupdate Required throughput = 10 × 6 = 60 conversions / second
Platform Per-Channel Update 10-Channel Aggregate Headroom vs. 60 conv/s
SIWAREX U (50 Hz) 20 ms 500 conv/s ~8.3×
SIWAREX WP321 (1 kHz) 1 ms 10 000 conv/s ~166×
TSXISPY101 (50 Hz) 20 ms 250 conv/s (2 modules) ~4.2×
SM 335 (0.05 ms) 0.05 ms 200 000 conv/s ~3 300×
1746-NI4 (5 ms all ch.) ~1.25 ms ~800 conv/s ~13× (with ext amp)

All candidates satisfy the raw throughput. The discriminator becomes channel-count efficiency (how many cells per slot), excitation source (integral or external), and integration effort (vendor weighing library vs. custom math in STEP 7).

Wiring, Shielding, and Isolation

Low-level bridge signals are sensitive to ground loops, VFD common-mode noise, and capacitive coupling from parallel AC runs. The SIWAREX wiring manual specifies the following practices, which apply equally to any weighing front-end.

  1. Use shielded twisted-pair (STP) cable with overall foil shield plus drain wire. Typical cable: Belden 8761 or Alpha 6330 for 4-wire bridge; 6-wire (sense line) cable if the load cell supports remote sensing to compensate lead resistance.
  2. Ground the shield at the module end only. Multi-point grounding creates ground loops that couple 50/60 Hz directly into the mV signal.
  3. Keep bridge wiring in a separate conduit at least 200 mm (8 in) from VFD output cables and unfiltered motor feeders. Cross at 90° if unavoidable.
  4. Twist the four bridge conductors tightly (≥ 8 twists per metre) to cancel magnetic pickup.
  5. Verify excitation sense lines at the load cell. 4-wire cells are tolerant of lead resistance but lose calibration with long cable runs; 6-wire cells compensate up to several hundred ohms of lead.
  6. Use a precision 10.000 V reference at the module. Calibration drift in the excitation source appears directly as scale error.
  7. Bond the load cell hardware to a single ground point if cells are mounted on a conductive frame; otherwise leave the cell body floating.

For SIWAREX, the module's "Load Cell Connection" diagram in the SIWAREX U manual (available on the Siemens Industry Online Support portal) shows the precise pin assignment for the 6ES7 standard front connector, including sense-line jumpers when used in 4-wire mode.

Configuration and STEP 7 / TIA Portal Integration

SIWAREX modules are configured through SIWATOOL V7 (or the current version) and integrated into STEP 7 / TIA Portal as standard analog input words. The following sketch illustrates a minimal ladder logic block that reads gross weight, applies a linearization, and publishes it to the process image for the S7-300 CPU.

// STEP 7 STL excerpt - read SIWAREX gross weight from PIW 288
      L     PIW 288         // raw 16-bit SIWAREX gross weight
      ITD                    // convert to double integer
      DTR                    // convert to REAL (engineering units)
      L     2.764810e+02    // calibration factor (counts per kg)
      /R                     // divide -> kg
      T     DB10.DBD0       // store in "ProcessWeight" DB

In TIA Portal on a newer S7-300 (or S7-1500 with SIWAREX WP321 on PROFINET), the Siemens "SIWAREX" library provides ready-made function blocks (FB250 "SIWA") that wrap the calibration, filtering, and zero-tracking logic. Engineers should not reimplement tare, span, and drift compensation from scratch — the library handles corner cases such as the digital filter settling time after a zero command.

For the SM 335 (6ES7 335-7HG01-0AB0), configuration is performed through HW Config (STEP 7) by inserting the module in the rack and assigning it to an analog input address range; no vendor library is required because the inputs are raw voltage / current values.

Calibration Procedure

Every SIWAREX and TSXISPY101 deployment must complete the following three-step calibration. Skipping any step invalidates the weighing accuracy certificate.

  1. Zero calibration — with the load cell unloaded, execute the "Calibrate Zero" command through the vendor configuration tool. The module stores the offset in non-volatile memory.
  2. Span calibration — apply a known reference weight (typically 80 % of the load cell nominal capacity, NIST-traceable), enter the reference mass, and execute "Calibrate Span." The module computes the gain factor.
  3. Verification — apply 0 %, 25 %, 50 %, 75 %, 100 % of nominal mass and confirm each reading is within the specified accuracy class. Repeatability across three cycles should be within the load cell's combined error specification (typically ≤ 0.02 % C…O for precision cells).

For the SM 335 / 1746-NI4 path with an external amplifier, calibration is performed at the amplifier front end, not the PLC. The PLC sees a 0–10 V or 4–20 mA signal proportional to weight; the calibration factors live in the PLC scaling code rather than in a vendor-validated block.

Selection Decision Matrix

Constraint SIWAREX (S7-300) SM 335 (S7-300) SLC 500 + ext. amp TSXISPY101
Direct bridge readout (no ext amp) ✓ integral ✓ integral
10 V bridge excitation integral external external integral
Channels per module 1 (or 4 via JB) 4 fast AI 4–8 (with ext amp) 1–8 (via JB)
Update rate per cell 50 Hz up to 20 kHz 100–200 Hz 50 Hz
Built-in weigh library SIWATOOL + FB250 none third-party only vendor FB
Module count for 10 cells 10 (U/MS) or 3 (WP321 via JB) 3 3 NI4 + 10 amps 2
Best fit for the reference application Primary recommendation Only if cells have integrated amp Legacy platform only Equivalent alternative

Common Pitfalls and Field-Engineering Notes

  1. Confusing sampling rate with effective throughput. A 50 Hz SIWAREX module samples one cell 50 times per second. Ten cells in a single CPU do not yield 500 Hz per cell — they share the 50 Hz sample slot. The aggregate of 60 conversions / second in the application profile refers to one conversion per channel, which the 50 Hz architecture satisfies easily.
  2. Forgetting the junction box current budget. SIWAREX U supplies up to 150 mA at 10 V. Four 350 Ω cells in parallel draw 4 × 28.6 mA = 114 mA — within spec. Six cells in parallel exceed the budget; reduce to four cells per SIWAREX U or move to SIWAREX WP321.
  3. Using the SM 335 for raw bridge inputs. The 14-bit resolution across a ±10 V input gives 1.22 mV per LSB; a 20 mV full-scale bridge signal uses only 16 LSBs total. The result is unusable weighing accuracy.
  4. Long cable runs without sense lines. A 100 m run of 24 AWG copper is approximately 8 Ω per conductor. In a 4-wire cell this introduces 16 Ω × 28.6 mA = 0.46 V drop on the excitation line, which directly becomes a 4.6 % scale error. Use 6-wire cells or shorten the cable.
  5. Mixing isolation grounds. SIWAREX and SM 335 share a common backplane ground. Do not float the PLC chassis relative to the load cell structure ground — the resulting CM voltage will saturate the input amplifier.
  6. Neglecting mechanical filter dynamics. A 5–6 Hz update is faster than many mechanical structures can respond. The reading will appear noisy because the structure itself is oscillating. Implement a digital low-pass filter with cutoff below the first structural mode.

Recommended Bill of Materials (Reference Application)

For ten channels of 5–6 Hz load cell weighing on an S7-300, the minimum BOM:

  • 1 × S7-300 CPU (e.g., 6ES7 315-2EH14-0AB0) with STEP 7 V5.5 or TIA Portal V16+
  • 10 × SIWAREX U (7MH4601-1AA01) — one per cell for full channel independence, OR
  • 3 × SIWAREX WP321 (7MH4908-1AA01) on ET 200SP distributed I/O with PROFINET, using junction boxes to parallel up to 4 cells per module
  • 3 × SIWAREX JB junction boxes (or compatible) for 6-wire bridge distribution
  • 10 × 4-conductor shielded cable (Belden 8761 or equivalent), one per cell, terminated to the front connector
  • 1 × SIWATOOL V7 configuration cable (7MH4601-1AA01 / USB or RS-232 depending on the variant)

Verification Checklist

After commissioning, complete the following checks before releasing the system to production:

  1. Confirm SIWAREX "Operating Mode" LED is steady green; a flashing LED indicates parameterization or calibration error.
  2. Apply a calibrated 80 % reference weight to each cell and verify reading is within ±0.05 % of nominal.
  3. Capture 1 000 raw samples at idle; standard deviation should be < 0.01 % of full scale with the digital filter engaged.
  4. Disconnect one excitation lead and verify the module flags a "Sense Lead Open" diagnostic bit in the process image — confirms fault detection is functional.
  5. Repeat accuracy check after 24 hours of thermal soak to verify drift; expected < 0.02 % over 10 °C ambient swing.

FAQ

What SIWAREX module replaces the older 7MH4601 variants for new S7-300 designs?

For new S7-300 designs use the SIWAREX U (7MH4601-1AA01) for single-channel applications. For multi-channel applications or where PROFINET is preferred, migrate to SIWAREX WP321 (7MH4908-1AA01) on an ET 200SP distributed I/O station — it provides 24-bit resolution and up to 1 kHz update while remaining STEP 7 / TIA Portal compatible.

Can the SM 335 (6ES7 335-7HG01-0AB0) read a raw 2 mV/V load cell directly?

No. The SM 335 has 14-bit resolution over ±10 V input ranges, giving 1.22 mV per LSB. A 20 mV bridge signal occupies only ~16 LSBs and yields unusable weighing accuracy. Use the SM 335 only with load cells that include an integrated amplifier producing 0–10 V or 4–20 mA output.

How many load cells can I connect to one SIWAREX U?

The SIWAREX U drives up to four 350 Ω cells in parallel through a SIWAREX junction box without exceeding the module's 150 mA excitation budget. For more cells per module, use the SIWAREX WP321, which supports up to eight 350 Ω cells per channel with 24-bit resolution and selectable 5 V / 10 V excitation.

What is the actual update rate of a SIWAREX U at 10 channels across 10 modules?

Each SIWAREX U samples independently at 50 Hz (20 ms period). With 10 modules in a single S7-300 rack, the PLC scan reads all 10 PIW words in one scan cycle — typically 5–15 ms — so the system delivers 50 readings per second per cell with one scan of latency. The aggregate throughput of 500 conversions per second across the rack comfortably exceeds the 60 conv/s application floor.

Why use 6-wire load cell wiring instead of 4-wire for a 5–6 Hz application?

4-wire cells tolerate lead resistance at the cost of scale accuracy over long runs. At 100 m of 24 AWG cable the 4-wire excitation drop is approximately 4.6 %, which becomes a direct scale error. 6-wire cells use separate sense lines to measure the actual voltage at the cell and regulate the excitation to compensate, restoring absolute accuracy independent of cable length. For any run over 20 m, specify 6-wire cells.

What is the recommended digital filter cutoff for 5–6 Hz weighing on noisy factory floors?

Set the SIWAREX digital filter to 10–20 Hz (the "medium" or "fast" preset depending on vendor revision). Below 10 Hz the filter attenuates the desired signal; above 20 Hz it no longer rejects mains-borne noise and VFD harmonics. If structural vibration is the dominant noise source, profile the structure with an accelerometer first and set the filter 3× below the lowest structural mode.

Back to blog