Overview
Engineers migrating projects from legacy STEP 7 V5.x or commissioning a S7-300 station inside TIA Portal V13 SP1 (and later) frequently discover that fields, tags, and system constants that exist on a S7-1500 CPU are simply not generated for S7-300 hardware. The most common symptom is the absence of a hardware identifier (HW identifier, HWID, German: Hardware-Kennung) for an I/O module, an interface, a submodule, or an IO-link master. On S7-1200 and S7-1500 the HWID appears automatically in the project tree under PLC tags > System constants and is consumed by extended instructions such as RDREC, WRREC, DPWR_DAT, DPRD_DAT, and by the IO device / I-device configuration. On S7-300 and S7-400 the same object is not generated because the underlying addressing model is based on the logical I/O address of the slot, not on a system-issued HWID.
This reference explains why S7-300 has no HW identifiers, shows the exact navigation path to recover the logical address that replaces them, maps the relationship between slot, first input/output, and the value used in user code, and provides a worked example for an IO-link master mounted on an ET 200SP IM155-6 PN interface module where the displayed example value (80) and the slot-derived value (128) can both appear depending on firmware and TIA Portal revision.
What is a Hardware Identifier?
A hardware identifier is a system-assigned integer constant (16-bit or 32-bit depending on the data type) that uniquely references a hardware object inside the S7-1200/1500 project. Siemens documents the concept in the TIA Portal help and in the function manual "Programming and Operating Manuals for S7-1200/1500":
- Example for the use of hardware identifiers (S7-300, S7-400, S7-1500) — Siemens Support entry 109742272.
- What you need to know about HW identifiers (S7-1200, S7-1500, S7-1500T) — TIA Portal V20 documentation.
The HWID is the only valid handle for instructions that need to address a module, submodule, port, or transfer area. Each HWID has a hardware data type that constrains which instructions can use it:
| Data type | Hardware object | Typical instructions |
|---|---|---|
HW_DEVICE |
IO controller / IO device / I-device | Device configuration, PROFINET commissioning |
HW_INTERFACE |
PROFINET interface, PROFIBUS interface | Port commands, interface diagnostics |
HW_IOSYSTEM |
PROFINET IO system, PROFIBUS DP master system | Topology, system diagnostics |
HW_SUBMODULE |
Submodule (head module, IO-link channel, port) |
RDREC, WRREC, GETIO
|
HW_IO |
Central or distributed I/O module slot | Direct I/O access (rarely required, I/O address preferred) |
The system assigns the HWID at compile time, and the value is stable for the lifetime of the compiled project. Renaming or re-inserting a module may change the HWID even if the slot and the I/O address remain identical.
Why S7-300 and S7-400 Do Not Expose HW Identifiers
The S7-300 and S7-400 families predate the HWID concept. Their programming model is built around two coordinate systems that the user supplies explicitly:
- Logical I/O address (also called process image address or module start address) — a byte-aligned value configured in the device view that is bound to the module's slot.
-
Diagnostic address — a separate slot-bound address used by
RDREC/WRRECand by the diagnostic interrupt OB (OB82).
Because the user controls both numbers, the engineering tool never needs to invent a third internal handle. The HWID exists in TIA Portal's S7-300/400 view only as a derived value used by some Wizards (for example the "Find module by HWID" search) and is not published to the symbol table, the PLC tag table, or the system constants. The result is the situation described in the source: opening the same TIA Portal V13 SP1 Update 5 project next to a S7-1500 station shows HWIDs for the 1500 hardware and nothing for the 300 hardware.
RDREC/WRREC against an IO-link master must use the module's diagnostic address, not a HWID. The diagnostic address appears in the Device View of the ET 200SP station and is independent of the IO data area.Locating the Module's Logical Address in TIA Portal
For a S7-300 CPU, the relevant addressing information is in the Device View of the station. The exact navigation path is:
- Open the project and double-click the Devices & networks entry.
- Select the S7-300 station (the rack symbol that contains the CPU).
- Open the Device view tab (lower-left of the station editor).
- Click the module whose address is required — for example the IO-link master on slot 1 of an ET 200SP head module.
- In the Properties inspector (right-hand panel) open the General tab, then the I/O addresses sub-tab.
The I/O addresses tab shows four editable fields:
| Field | Meaning | Editable? |
|---|---|---|
| Start address (input) | First input byte of the module's process image | Yes, unless locked by the system |
| Start address (output) | First output byte of the module's process image | Yes |
| Process image | Partition assignment (OB1, OB40, ...) | Yes |
| Diagnostic address | Slot-bound address for record/parameter access | Yes |
For central modules (slots 0–3 of the S7-300 rack, or the first row of the ET 200SP station) the module's logical address — the value the user program reads with PEW/PAW or with L PIW/T PQW — equals the start address shown in the I/O addresses tab. For distributed modules behind PROFINET/PROFIBUS, the start address is still the relevant address; the diagnostic address is separate and is the value used in RDREC/WRREC with MLEN or the implicit call from OB82.
Diagnostic Address vs Logical Address: Practical Example
Consider a S7-300 CPU 315-2 PN/DP (6ES7 315-2EH14-0AB0, firmware V3.3) connected over PROFINET to an ET 200SP station with an IM155-6 PN HF (6ES7 155-6AU00-0BN0) and a 4-port IO-link master (6ES7 137-6BD00-0BA0) inserted in slot 1. A typical TIA Portal configuration displays:
| Slot | Module | Order number | Input start | Output start | Diagnostic address |
|---|---|---|---|---|---|
| 0 | IM155-6 PN HF | 6ES7 155-6AU00-0BN0 | — | — | 2045 |
| 1 | IO-link master 4xM12 | 6ES7 137-6BD00-0BA0 | 0 | 0 | 2046 |
| 2 | Digital input 8x24V | 6ES7 131-6BF00-0BA0 | 1 | — | 2047 |
| 3 | Digital output 8x24V | 6ES7 132-6BF00-0BA0 | — | 1 | 2048 |
The diagnostic address follows the convention used for PROFINET devices: head module = 2045, slot 1 = 2046, slot 2 = 2047, and so on. Do not hard-code 2046 in the program; instead read the address from the slot symbol that TIA Portal generates. A SCL block that reads the IO-link master's identification data (index 0x0010) on a S7-300 looks like this:
// Read IO-link master identification (record 16) via PROFINET
// Diagnostics address of the IO-link master module
#ioLinkMasterDiagAddr := 2046; // source: Device view -> Properties -> I/O addresses
#status := RDREC(
REQ := TRUE,
ID := DW#16#0, // always 0 for record access
INDEX := 16, // IM 0x10 = identification
MLEN := 64, // record length
VALID => #valid,
BUSY => #busy,
ERROR => #error,
STATUS => #retStatus,
RECORD := #idData);
ID input of RDREC is a word with the format DW#16#Dxxx for PROFINET slot addressing, but STEP 7 accepts 0 and routes the call via the diagnostic address in the SZL/locale. For S7-300 the more reliable form is to pass the value directly through the diagnostic address of the slot. Refer to the S7-300/400 function manual "FB / FC Blocks" for the exact signature of RDREC on a 300 CPU.Why an Example Project May Show 80 or 128 for the Same Module
Engineers who port Siemens example projects frequently see the "module's logical address" printed as 80 in the project documentation while the slot-derived value computed by hand comes out to 128. The mismatch is usually one of three causes:
- Different TIA Portal revision. TIA Portal V13 SP1 Update 5 assigned a different start address than V14, V15, V16, or V17 for the same hardware configuration because the address space was reorganized when the system constants / HWID model was extended.
- Different ET 200SP head module firmware. The IM155-6 PN HF firmware V3.3 and V4.x differ in slot addressing. The V4.x firmware introduced 0–65 slot range with a different diagnostic base; a V3.3 head module running in a V4.x project uses the older 2000-series diagnostic addresses.
- Manual address override. The project author may have explicitly typed the start address 80 into the module's I/O address tab to free up the low address range for the process image partition. Once typed, the value is independent of the slot index.
The two values 80 and 128 can both be valid: 80 is the IO-link master's input start address after the user typed it in; 128 is what the slot auto-assignment would have produced for a module in slot 4 of the ET 200SP. Verify the actual value by reading the start address from the Device View of the user's specific project, not from a printed example.
HWID in S7-1500 vs Logical Address in S7-300: Conversion Table
For migrating user code from S7-1500 to S7-300, the following substitution table applies when the S7-1500 block uses the hardware identifier as the input of an instruction:
| S7-1500 instruction | S7-1500 input | S7-300 / S7-400 equivalent |
|---|---|---|
RDREC |
HWID (HW_SUBMODULE, HW_IO, HW_DEVICE) |
Diagnostic address (WORD) of the module slot |
WRREC |
HWID |
Diagnostic address of the module slot |
GETIO / SETIO
|
HWID |
Direct L PIW / T PQW on the start address |
DPWR_DAT / DPRD_DAT
|
HWID (DP slave) |
Logical address of the slave + offset |
| PROFINET port commands |
HWID (HW_INTERFACE) |
Use the Port dialog of the head module; the address is in slot/diagnostic form |
The substitution is not automatic. The code must be rewritten by hand because the S7-1500 instructions accept a typed system constant while the S7-300 blocks accept a plain WORD/INT input. TIA Portal's cross-compiler cannot convert the two.
Special Case: IO-link Master on ET 200SP behind a S7-300 CPU
The IO-link master 6ES7 137-6BD00-0BA0 (or its successor 6ES7 137-6BD20-0BA0 with port class A) is treated as a PROFINET submodule. From the S7-300 perspective, three addresses are relevant:
- Process image start (input) — the start byte for cyclic process data. The IO-link master occupies 2 bytes of input and 2 bytes of output by default; channel-level diagnostic data is mapped to the diagnostic address, not the process image.
- Process image start (output) — the start byte for the master's cyclic command data (e.g. port enable, fallback direction).
-
Diagnostic address — the address used for acyclic
RDREC/WRRECcalls and for the diagnostic interrupt OB (OB82). The diagnostic frame is mapped to bits of input byte 0–3 of the master, with a status byte and a channel number byte.
For port-level access (read IO-link device parameter, write IO-link device parameter) the user's block uses RDREC/WRREC against the master's diagnostic address with index 0x8000 + port_index for the IO-link device (port 1 = index 0x8000, port 2 = 0x8001, port 3 = 0x8002, port 4 = 0x8003). A SCL sketch for port-1 parameter read:
// Read IO-link device parameter (port 1, index 0)
// Use the IO-link master's diagnostic address
#idx := INT_TO_WORD(16#8000 + 0); // port 1, subindex 0
#status := RDREC(
REQ := #go,
ID := INT_TO_WORD(0),
INDEX := #idx,
MLEN := 32,
VALID => #done,
BUSY => #busy,
ERROR => #err,
STATUS => #rc,
RECORD := #buf);
Finding the Module's Logical Address on a S7-300 with TIA Portal V13 SP1
TIA Portal V13 SP1 Update 5 was released in 2015. On this revision, the navigation path to the I/O address is identical to newer revisions:
- Devices & networks → select S7-300 station → Device view.
- Click the module on the rack.
- Properties → General → I/O addresses tab.
If the I/O address tab is greyed out, the module is a "head module" (the IM155-6 PN itself, slot 0). Head modules have no process image; they have a diagnostic address only. To find the diagnostic address of a head module on a S7-300 project, open the Properties → General → PROFINET interface tab; the "Diagnostics address of the module" field shows the value.
Common Pitfalls
| Pitfall | Symptom | Fix |
|---|---|---|
| Using the S7-1500 HWID in a S7-300 block | Compiler error "unknown tag" or "type mismatch" | Replace the HWID with the WORD/INT start or diagnostic address read from the Device View |
| Confusing the start address with the diagnostic address |
RDREC returns STATUS W#16#80A1 (module not found) |
Use the diagnostic address for record calls, the start address for L PEW / T PAW
|
| Trusting a printed example value | IO-link master returns no cyclic data | Re-read the start address from the Device View of the actual project, do not paste 80 / 128 from a manual |
| Slot numbering of IM155-6 | Slot 0 vs slot 1 mismatch in the example project | Verify head module (slot 0) and the first I/O module (slot 1) match the physical layout |
| Different TIA Portal revisions | Compiled values differ between V13 SP1 and V17 | Open the project on the target version, recompile, and re-read the start address |
Verifying the Address at Commissioning
To confirm the value is correct without writing a full program, use the S7-300 online watch table and the CPU's Monitor / Modify function:
- Go online with the S7-300 CPU.
- Create a watch table with three rows: PEW start, PAW start, and PIB diagnostic_address.
- Power-cycle the IO-link device; the master's diagnostic byte should show the channel event.
- Read PIB diagnostic_address with status byte = 0xF0 (channel diagnosis present) and a channel number matching the IO-link port.
If the status byte is non-zero but the channel number is unexpected, the start address is wrong by exactly one slot. Move to the next slot in the Device View and re-read.
Frequently Asked Questions
Does the S7-300 have hardware identifiers in TIA Portal V13 SP1?
No. S7-300 and S7-400 do not generate user-visible hardware identifiers. The S7-1200 and S7-1500 do, and the system constants are visible in PLC tags > System constants. For a S7-300 use the logical start address (process image) and the diagnostic address (for RDREC/WRREC) of each module.
How do I find the IO-link master's logical address on an IM155-6 PN in TIA Portal?
Open Devices & networks, select the S7-300 station, click the ET 200SP head module's slot that holds the IO-link master (typically slot 1), then in Properties go to General > I/O addresses. The fields Start address (input), Start address (output), and Diagnostic address are shown. Use the start address for process data, the diagnostic address for RDREC/WRREC and OB82.
Why does my Siemens example show logical address 80 while my own project shows 128?
Can I use a S7-1500 RDREC call with a HWID in a S7-300 program?
No. S7-300 does not generate HWID tags. Replace the HWID input with a WORD constant that contains the module's diagnostic address. The remainder of the call (REQ, INDEX, MLEN, RECORD, STATUS, BUSY, ERROR, VALID) is identical between the two families; only the ID input handling differs.
What is the diagnostic address of the IM155-6 PN HF head module?
The head module's diagnostic address is typically 2045 in a default TIA Portal configuration (slot 0 of the ET 200SP station). The first I/O module (slot 1) takes 2046, slot 2 takes 2047, and so on. These are visible in the Device View under General > I/O addresses; the values are editable but should not be changed without consulting the project documentation.