S7-300 PLC STOP on PROFINET Startup: Resolving OB86 Rack Failure

David Krause21 min read
S7-300SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Overview

An S7-300 PLC acting as a PROFINET IO controller enters the STOP state at startup when a configured PROFINET IO device is not yet reachable. The diagnostic buffer logs a rack failure caused by the missing IO device and stops the CPU with the entry "OB not loaded or not possible, or no FRB". The symptom is most visible on machines where one or more IO devices (robots, drives, vision systems, third-party controllers) take significantly longer to boot than the S7-300 CPU.

This article documents the specific failure mode observed on an ET 200S station built around an IM151-8 PN/DP CPU (Siemens article number 6ES7151-8AB00-0AB0 for firmware V2.x, 6ES7151-8AB01-0AB0 for firmware V3.x). The IO controller is connected to a KUKA robot controller (KR C4) that requires roughly two minutes to complete its own boot. The IM151-8 CPU finishes power-on in about 20–40 seconds, polls the IO device, receives no response, and goes into STOP because the project does not contain an OB86 (Rack Failure OB).

Symptom signature: diagnostic buffer shows PROFINET IO: station failure followed by STOP caused by rack failure (OB not loaded or not possible, or no FRB). The third entry, PROFINET IO: station return, event 16#38CB, arrives too late because the CPU has already transitioned to STOP.

The fix is to create OB86 in the STEP 7 project. The block can be empty; the CPU only needs the block to exist so the operating system has somewhere to deliver the rack-failure event. After downloading the new OB86, the CPU remains in RUN while the IO device is offline, and resumes cyclic IO exchange as soon as the IO device returns.

2. Affected Hardware and Firmware

Identify the exact components before applying any fix. The failure mode is the same for all S7-300/ET 200S CPUs that act as a PROFINET IO controller (CPU 315-2 PN/DP, CPU 317-2 PN/DP, CPU 319-3 PN/DP, and the IM151-8 PN/DP CPU), but the configuration steps differ slightly between STEP 7 V5.x and TIA Portal.

Component Article number Firmware Role
ET 200S, IM151-8 PN/DP CPU (V2.x) 6ES7151-8AB00-0AB0 V2.0.x – V2.2.x PROFINET IO controller, S7-300 instruction set
ET 200S, IM151-8 PN/DP CPU (V3.x) 6ES7151-8AB01-0AB0 V3.0.x – V3.3.x PROFINET IO controller, supports "IO device is not required for CPU startup"
ET 200S, IM151-8F PN/DP CPU (fail-safe) 6ES7151-8FB00-0AB0 / 6ES7151-8FB01-0AB0 V2.x / V3.x Same behaviour, fail-safe variant
PROFINET IO device (KUKA KR C4 / KR C5) Vendor-specific GSD/GSDML Robot controller firmware PROFINET IO device, ~2 min startup
STEP 7 V5.5 + SPx (engineering) 6ES7810-4CC10-0YA5 V5.5 SP2 or later Engineering tool, classic
TIA Portal (engineering) 6ES7822-1AA04-0YA5 (V15.1) or later V13 SP1 or later Engineering tool, unified
PC adapter USB A2 6GK1571-1AA00 N/A Online interface for STEP 7 V5.x
Onboard Ethernet (PROFINET) Integrated N/A Online interface for TIA Portal and HMI

Verify the firmware version of the IM151-8 in PLC > Module Information > Online > Firmware or read it from the physical module's label. Firmware V3.x is recommended because it adds the "IO device is not required for CPU startup" configuration option in HW Config, which is a much cleaner solution than relying solely on OB86.

3. Diagnostic Buffer Interpretation

The diagnostic buffer is the most reliable source of root-cause information. Open SIMATIC Manager > PLC > Module Information > Diagnostic Buffer (STEP 7 V5.x) or Online & Diagnostics > Diagnostics buffer (TIA Portal). The events that prove the missing-OB86 root cause appear in the following sequence:

# Event text Hex detail Meaning
1 PROFINET IO: station failure FLT_ID = B#16#0A, EV_CLASS = B#16#39 Configured IO device did not respond within the startup timeout
2 STOP caused by rack failure (OB not loaded or not possible, or no FRB) — CPU went to STOP because OB86 was missing in the project
3 PROFINET IO: station return, event 16#38CB FLT_ID = B#16#0B, EV_CLASS = B#16#38 IO device finally came online — too late, the CPU is already in STOP

The detail line for the station-failure event includes the following parameters, taken directly from a real IM151-8 buffer in this configuration:

  • Address of affected station (input): 2042 — logical base address of the IO device input area
  • IO system ID: 100 — PROFINET IO system index 100 (the first PN IO system in the CPU)
  • Station number: 1 — PROFINET device number assigned in HW Config
  • Logical base address of the IO controller: 2043 — controller's interface slot
  • Requester OB: RACK failure OB (OB86)
  • Priority class: 26 — OB86 runs at priority 26 in the S7-300/ET 200S
  • Event class: External error, outgoing event

Translate hex event ID 16#38CB to the OB86 form: FLT_ID = B#16#0B with EV_CLASS = B#16#38 (outgoing = station return). For comparison, the failure event decodes as FLT_ID = B#16#0A with EV_CLASS = B#16#39 (incoming = station failure). The full set of OB86 PROFINET FLT_ID values used by the IM151-8 / S7-300 PN CPUs is:

FLT_ID EV_CLASS Event meaning
B#16#03 B#16#39 PROFINET IO system failure
B#16#04 B#16#38 PROFINET IO system return
B#16#05 B#16#39 PROFINET IO station failure (slot)
B#16#06 B#16#38 PROFINET IO station return (slot)
B#16#0A B#16#39 PROFINET IO device failure
B#16#0B B#16#38 PROFINET IO device return
B#16#0C B#16#39 PROFINET IO submodule failure
B#16#0D B#16#38 PROFINET IO submodule return
B#16#0E B#16#39 PROFINET IO slot failure
B#16#0F B#16#38 PROFINET IO slot return

4. Root Cause Analysis

The S7-300 and ET 200S CPUs follow a fixed startup sequence defined in the operating system:

  1. Power-on or mode selector transition from STOP to RUN.
  2. Hardware configuration is evaluated; configured PROFINET IO devices are polled within the IO startup timeout.
  3. OB100 (warm restart) is executed once, top to bottom.
  4. Cyclic operation begins: OB1 runs, the IO controller cyclically updates IO devices, and PROFINET alarms are dispatched to OB82/OB86.

If a PROFINET IO device is not accessible during step 2, the operating system raises a rack failure event. The expected user response is to load OB86 in the project. The CPU then calls OB86 with the relevant OB86_MDL_ADDR, OB86_FLT_ID, and OB86_PNT_INFO values. If OB86 is not loaded, the CPU cannot pass the failure event to a user program and, by design, transitions to STOP with the diagnostic buffer entry "OB not loaded or not possible, or no FRB".

This is the documented default behaviour in the S7-300 CPU 31x system manual and the IM151-8 PN/DP CPU operating instructions. A useful reference for the failure pattern is the Siemens TIA Portal manual collection, which describes how an IO device failure is handled in the S7-1500R/H redundant system: Failure of an IO device in the PROFINET ring. The S7-300/ET 200S follow the same conceptual model, although the configuration options are more limited.

Common misconception: configuring a longer PROFINET startup timeout does NOT prevent the STOP when OB86 is missing. The CPU still enters STOP as soon as the rack-failure event fires. The startup timeout only delays the event itself; it does not change the CPU's reaction to a missing OB86. A longer timeout makes the symptom less frequent in marginal conditions, it does not eliminate it.

5. Primary Solution: Create OB86 in STEP 7 V5.5

The most direct fix is to insert an OB86 organisation block into the S7 program. An empty OB86 is sufficient — the CPU only needs the block to exist so the operating system has somewhere to deliver the rack-failure event.

5.1 Procedure in STEP 7 V5.5 (SIMATIC Manager)

  1. Open SIMATIC Manager and load the S7-300 / ET 200S station from the project archive.
  2. In the project tree, expand S7-300 CPU > S7 Program > Blocks (for STEP 7 V5.x) or CPU > Program in TIA Portal.
  3. Right-click Blocks > Insert New Object > Organisation Block.
  4. In the Properties — Organisation Block dialog, set the following values:
    • Name: OB86
    • Symbolic name: Rack_Failure (optional but recommended for readability)
    • Author: project default
    • Comment: Handles PROFINET IO device failure and return; prevents CPU STOP on rack failure
  5. Click OK. STEP 7 generates a default OB86 with the standard local variable declarations (OB86_EV_CLASS, OB86_FLT_ID, OB86_IO_FLAG, OB86_MDL_ADDR, OB86_RACKS_FLTD, OB86_PNT_INFO, OB86_Z2).
  6. Do not add any user code. The default contents (a single BE instruction) are sufficient for the CPU to remain in RUN.
  7. Save and compile the program (Station > Save and Compile or Ctrl+F7).
  8. Download the blocks to the CPU (PLC > Download or Ctrl+L). The online dialog will warn that the CPU will be stopped for the download. The IM151-8 then performs an automatic warm restart after the download.

5.2 Procedure in TIA Portal

  1. Open the project in TIA Portal (V13 SP1 or later, V15.1+ recommended for IM151-8 V3.x firmware).
  2. Expand the S7-300 / ET 200S station in the project tree.
  3. Right-click Program blocks > Add new block.
  4. Choose Organisation block as the type, set the name to OB86, and confirm the number 86.
  5. Click OK. TIA Portal inserts a default OB86 with the same local variable declarations as STEP 7 V5.x.
  6. Compile the program and download the blocks to the CPU.
Field result: after downloading the new OB86 and cycling power, the IM151-8 PN/DP CPU no longer transitions to STOP when the robot controller is offline at startup. The diagnostic buffer still logs PROFINET IO: station failure followed by PROFINET IO: station return once the robot comes online, but the CPU stays in RUN throughout. The BF LED is on while the IO device is missing and turns off automatically when the device returns.

6. Secondary Solution: Configure PROFINET IO Startup Behaviour

For a more deterministic configuration, adjust the PROFINET IO device startup parameters in HW Config. This complements OB86 and reduces the number of rack-failure events that the application has to handle.

  1. Open the S7-300 / ET 200S station in HW Config (STEP 7 V5.x) or in the device view (TIA Portal).
  2. Select the PROFINET IO interface of the IM151-8 CPU.
  3. Open Properties > PROFINET IO > Startup (TIA Portal: Properties > General > PROFINET interface > Advanced options > Startup).
  4. Set "Compare preset / actual configuration" to "Startup CPU only if expected configuration matches" only when every IO device must be present at startup. For mixed-criticality installations, leave this option disabled.
  5. Open the properties of the IO device (KUKA controller). Set the Watchdog time and the Replacement time to values that tolerate the robot's two-minute startup. A typical value for a 2-minute boot is 200,000 ms (200 s) for both fields.
  6. In the PROFINET interface properties of the CPU, on the Time tab, set the IO device startup timeout to a value larger than the worst-case IO device boot time.

Firmware V3.x of the IM151-8 PN/DP CPU adds the option "IO device is not required for CPU startup" in the PROFINET IO device properties (HW Config / device view). When this checkbox is enabled, the IO controller does not stall startup if the device is missing, and the CPU enters RUN immediately. Enable this option when the IO device is a non-critical peripheral (robot, vision, or auxiliary drive) and when the application can tolerate the IO device being absent during the first scan cycles.

7. Supplementary OBs for Startup Behaviour

OB86 is the minimum required block. Three other OBs frequently improve startup behaviour in this exact scenario and should be added to every S7-300 / ET 200S PROFINET deployment as a baseline.

OB Name Priority Trigger Why it helps
OB82 Diagnostic interrupt 6 IO device diagnostic interrupt (channel fault) Prevents STOP if a PROFINET device reports a diagnostic alarm (e.g. wire break on a robot I/O module)
OB86 Rack failure 26 IO device failure / return Prevents STOP when an IO device disappears or returns (root-cause fix in this article)
OB100 Warm restart 27 Power-on / STOP→RUN transition Runs once at startup; ideal for one-time initialisation of HMI tags, set-points, and handshake bits
OB122 Peripheral access error Priority of the causing OB Direct I/O access to a missing or failed module Prevents STOP if a STEP 7 program reads a PROFINET input that is currently not available

For a robust deployment, insert all four OBs as empty blocks. The CPU then ignores these errors and continues in RUN. Add real user code to OB82/OB86/OB122 only when you need to log the events or set fallback values for the application.

7.1 Example: initialise a startup handshake in OB100

Insert the following STL snippet into OB100 to set a startup-completed flag that the HMI can poll. Replace the operand names with the symbols used in your project.


      A     "HMI_Heartbeat"          // HMI heartbeat tag (M100.0)
      AN    "CPU_Restart_Lock"       // Latch cleared on operator reset (M100.4)
      S     "CPU_Startup_Done"       // Set startup flag (M100.1)
      S     "Robot_Online_Required"  // Set robot-expected flag (M100.2)
      R     "Robot_Online_OK"        // Clear robot-online flag (M100.3)
      R     "PN_IO_Station_Fault"    // Clear sticky PROFINET fault (M100.5)
      BEA                            // End of OB100 (warm restart)

7.2 Example: log OB86 PROFINET IO failure in SCL

Insert the following SCL block in OB86 to copy the failure code into a flag word that the HMI can display. The block leaves the CPU in RUN by simply ending with RETURN — no special action is required.


// SCL source for OB86
IF #OB86_IO_FLAG = B#16#54 THEN
   // PROFINET IO failure (FLT_ID 0x0A or 0x0C)
   "PN_IO_Fault_Code" := WORD#16#0A00 + #OB86_FLT_ID;
   "PN_IO_Fault_Addr" := #OB86_MDL_ADDR;
   "PN_IO_Station_Nr" := #OB86_Z2;
   "PN_IO_Station_Fault" := TRUE;
ELSE
   // PROFINET IO return (FLT_ID 0x0B or 0x0D)
   "PN_IO_Station_Fault" := FALSE;
   "PN_IO_Return_Code" := WORD#16#0B00 + #OB86_FLT_ID;
END_IF;
RETURN;

8. Warm Restart Without STEP 7

The original problem statement requires a way to bring the CPU out of STOP without STEP 7 once the HMI is in charge of the line. Several mechanisms are available; choose the one that matches the operational constraints of the machine.

8.1 Mode selector switch

The IM151-8 PN/DP CPU has a three-position mode selector on the front:

  • RUN — CPU executes the user program in cyclic mode.
  • STOP — CPU is stopped, outputs are disabled, diagnostic buffer is preserved.
  • MRES — memory reset (not needed for a warm restart).

Toggle the switch from STOP → RUN to perform a warm restart. The outputs are re-initialised according to the values in OB100, OB100 runs once, and the CPU returns to RUN. This is the most reliable field-tested method but requires physical access to the PLC.

8.2 Power cycle

Power the CPU off, wait at least 3 seconds, then power it back on. The CPU performs a warm restart as long as the operating mode is set to RUN on the selector and the retentive memory is configured correctly. A cold restart (OB102) only occurs if the power-on is treated as a cold restart by the CPU configuration; on the IM151-8 with a valid OB100 in the project, the power-on is treated as a warm restart by default.

8.3 Restart from a custom HMI via S7 communication

When the HMI is the only available tool, send an S7 "START" command to the CPU. Three options are available, depending on the HMI driver:

  1. Built-in driver function: most modern SCADA packages (WinCC / TIA WinCC, Zenon, iFIX, InTouch, Citect) include a PLC start/stop command. Enable the option in the driver configuration and bind it to a button on the HMI screen.
  2. PG/PC S7 protocol: use the SIMATIC Automation Tool (Siemens) or a custom .NET application that connects via TCP/IP to the CPU's PROFINET interface and sends a START command. The CPU accepts a START command from a partner with PG (programming) rights; configure the connection in NetPro / "Devices & Networks" with the right PG authorisation.
  3. Soft-PLC handshake: a user program in OB1 monitors a control bit (e.g. M 200.0 = Request_Restart) that the HMI sets. When the bit is detected, the program calls SFC46 "STP" to put the CPU in STOP. After a configurable delay, the HMI sends the START command, and OB100 re-initialises the application.

For a fully autonomous HMI-driven restart, configure the S7 connection with PG rights on the HMI side. The CPU accepts a START command from a partner whose "Connection resource" is configured as "PG/OP connection" and whose "Connection authorisation" includes the "Start" right. In NetPro / TIA Portal Devices & Networks, open the S7 connection properties and set Connection authorisation to PG/OP.

8.4 Soft warm restart via SFC20 / SFC46

For an HMI-driven restart that does not require the S7 START command, implement a "soft warm restart" sequence:

  1. The HMI sets the control bit Request_Restart (e.g. M 200.0).
  2. OB1 detects the bit and calls SFC46 "STP" to put the CPU in STOP.
  3. The HMI detects the STOP (via the diagnostic buffer or a status tag read cyclically) and, after a configurable delay, toggles a digital output connected to a relay that momentarily powers the CPU off and on.
  4. On power-on, the CPU performs a warm restart and runs OB100, which clears the Request_Restart bit and signals completion to the HMI.
Safety warning: always validate the consequences of an automatic restart on the connected machinery. Insert hardwired safety relays in the E-Stop chain so that a software restart cannot bypass them. The PROFINET safety protocol PROFIsafe is the preferred method for safety I/O and must not be replaced by a software workaround. Confirm the restart sequence with the machine risk assessment before commissioning.

9. Advanced Diagnostics with SFC/SFB

When the basic OB86 approach is in place, add diagnostics in the user program to log IO device state transitions. The following blocks are useful:

Block Name Typical call point Use
SFC13 DPNRM_DG OB82 / OB86 / OB1 Read PROFIBUS DP / PROFINET IO diagnostic data from a slave
SFC51 RDSYSST OB1 / OB100 Read system status lists (SSL); list 0x00B4 returns the PROFINET IO status
SFB52 RDREC OB82 / OB86 Read data record from a PROFINET device (index 0x8000 for IO device state)
SFB53 WRREC OB1 Write data record to a PROFINET device (e.g. acyclic parameter setpoints)
SFB54 RALRM OB82 / OB86 Read all alarm information; extract the alarm payload inside the OB

Example — read PROFINET IO system status in OB1 cyclically and store the device state in a flag byte:


// Call SFC51 to read SSL 0x00B4 (PROFINET IO status)
CALL  "RDSYSST"          // SFC51
     REQ     := TRUE
     SZL_ID  := W#16#00B4
     INDEX   := W#16#0001
     RET_VAL := "SFC51_RetVal"           // INT return code
     BUSY    := "SFC51_Busy"             // BOOL busy flag
     SZL_HEADER := "SFC51_Header"        // 32-byte SSL header
     DR      := "PN_IO_Status_Buffer"    // 28-byte data record per IO system

SSL 0x00B4 returns a 28-byte record for each PROFINET IO system. Byte 0 contains the IO system state, byte 1 the number of IO devices, and the remaining bytes list the IO device number, the number of slots, and the number of submodules per device. Other useful SSL IDs for IO diagnostics on the IM151-8 / S7-300 PN CPU are:

SSL ID Name Use
W#16#00B3 Diagnostic data of a PROFINET IO device Read channel-level diagnostic alarms for one device
W#16#00B4 PROFINET IO status Cyclic view of all IO devices in one system
W#16#00D0 PROFINET IO AR (Application Relationship) state Detailed state of each PROFINET connection
W#16#00D1 PROFINET IO CR (Communication Relationship) state Detailed state of each CR (controller / device / supervisor)
W#16#0019 Diagnostic status of a module Per-module diagnostic state for direct I/O faults

10. Verification Procedure

Run the following procedure after the OB86 has been downloaded to confirm the fix. Repeat the test at least three times to confirm repeatability, and document the diagnostic buffer and LED states for the operator manual.

  1. Power-cycle the IM151-8 CPU while the KUKA robot controller remains off.
  2. Wait for the CPU to finish startup (about 20–40 s for IM151-8 V3.x).
  3. Open Module Information > Diagnostic Buffer:
    • Confirm event #1 is PROFINET IO: station failure with FLT_ID B#16#0A.
    • Confirm there is no STOP caused by rack failure entry.
    • Confirm OB86 was called (event class External error, incoming with OB86 reference).
  4. Confirm the CPU mode is RUN: the mode selector and the online view both show RUN, the RUN LED on the front is steady green, and the STOP LED is off.
  5. Power on the KUKA robot controller and wait for it to finish startup.
  6. After the controller is online, observe a new diagnostic buffer entry: PROFINET IO: station return, event 16#38CB with FLT_ID B#16#0B.
  7. Verify cyclic IO exchange by toggling a digital output on the KUKA controller and observing the corresponding input in the S7 program (use a VAT table in STEP 7 or a tag in the HMI).
  8. Repeat the test three times to confirm repeatability. Document the diagnostic buffer screenshot, the LED states, and the timestamps in the commissioning report.
LED State Meaning in this scenario
RUN (green) Steady CPU is in RUN, user program is executing (expected after fix)
RUN (green) Flashing 0.5 Hz CPU is in STARTUP; OB100 is being processed (transient)
STOP (yellow) Steady CPU is in STOP (problem still present — missing OB86 or another error)
STOP (yellow) Flashing 0.5 Hz CPU is in STOP with diagnostic information pending
SF (red) Steady Group error; check diagnostic buffer
BF (red, on PROFINET port) Steady PROFINET bus fault; one or more IO devices unreachable (expected while KUKA is off)
BF (red, on PROFINET port) Flashing Configuration mismatch or wrong GSD
MAINT (yellow) Steady Maintenance demanded; check maintenance events in the buffer

A correct implementation keeps the RUN LED steady throughout, even with the BF LED on during the KUKA controller's boot phase. The BF LED will turn off as soon as the IO device returns and starts cyclic data exchange.

11. Field-Proven Best Practices

  • Always include OB82, OB86, OB100, OB122 as a baseline in any S7-300/ET 200S deployment that uses PROFINET IO with non-deterministic slaves. Empty blocks are acceptable. This single rule prevents the majority of unexpected STOP events on production machines.
  • Configure PROFINET IO timeouts in HW Config to be larger than the worst-case slave boot time. For a 2-minute KUKA boot, set the IO device Replacement time to 200,000 ms (200 s) and the Watchdog to the same value.
  • Use OB100 to initialise HMI tags, set first-cycle flags, and clear latched alarms. This makes the cold/warm restart behaviour deterministic and the HMI display predictable.
  • Avoid direct I/O access to PROFINET inputs that may be unavailable. Use the process image (PII/PIQ) and let OB122 handle access errors. Prefer the "All" process image update setting in HW Config.
  • Use a dedicated "Restart Lock" bit in OB86. If the application requires operator acknowledgement after a fault, set a sticky error bit in OB86 that the HMI must clear before allowing a restart. This prevents the machine from cycling in and out of faults without operator intervention.
  • Document the LED behaviour for the operators so they can distinguish a normal "BF during slave boot" from a true bus fault. A small label on the cabinet door is often the most cost-effective documentation.
  • Keep STEP 7 and the project archive on the HMI PC or a versioned file server. Even if STEP 7 is no longer in use for online commissioning, a copy is needed if a memory reset is ever required. The project archive is the single source of truth for the system configuration.
  • Validate the restart path under controlled conditions before relying on it. The HMI-driven restart requires a working S7 connection; if the CPU is in STOP and the HMI is the only partner, the HMI must have the correct PG/PC interface configuration and connection rights.
  • Use a watchdog bit in the HMI that toggles cyclically and is monitored by the S7 program. If the HMI goes off-line, the S7 program can detect the loss of the watchdog and enter a safe state.
  • Test the OB86 fix with multiple slaves. The fix is independent of the number of IO devices; each device triggers OB86 individually with its own station number. Verify that all slaves are handled correctly when they come online at different times.

FAQ

Why does the S7-300 CPU go into STOP when a PROFINET IO device is missing at startup?

The CPU raises a rack failure event when a configured PROFINET IO device is not reachable at the end of the startup phase. Without OB86 loaded, the operating system cannot hand the event to a user program and transitions to STOP with the diagnostic buffer entry "OB not loaded or not possible, or no FRB". Inserting OB86 (even empty) prevents the STOP.

Do I need to write any code in OB86 to keep the CPU in RUN?

No. An empty OB86 (default STEP 7 content, ending with BE) is sufficient. The CPU only needs the block to exist so the rack-failure event has a delivery target. Add user code only if you need to log the event, set fallback values, or implement a restart lock that the operator must clear before continuing.

Which organisation blocks should I include for a robust PROFINET deployment?

At minimum, include OB82 (diagnostic interrupt), OB86 (rack failure), OB100 (warm restart), and OB122 (peripheral access error). All four can be empty. Optionally include OB121 (programming error) and OB80 (timeout) for full coverage of all operating-error conditions.

How can I bring the CPU out of STOP without STEP 7?

Use the mode selector on the front of the CPU (STOP → RUN for a warm restart) or a power cycle. From a custom HMI, you can send an S7 START command over the PROFINET interface; most SCADA packages include a built-in PLC start command. Configure the S7 connection with PG/OP authorisation so the HMI can issue the start command. Always validate the restart path during commissioning.

What is the meaning of event ID 16#38CB in the diagnostic buffer?

16#38CB is the hexadecimal event ID for a PROFINET IO station return: the IO device has re-entered cyclic data exchange. In OB86 the same event appears as FLT_ID = B#16#0B (PROFINET IO device return) with EV_CLASS = B#16#38 (outgoing event). The corresponding failure event is 16#38CA / FLT_ID B#16#0A / EV_CLASS B#16#39.

Is OB86 also required when the IO device drops out at runtime (not only at startup)?

Yes. OB86 is called for both startup and runtime events. If OB86 is missing, the CPU goes to STOP on any rack failure, including a PROFINET IO device that drops out during normal operation. Inserting OB86 covers both cases.

What is the priority class of OB86 on the S7-300 / IM151-8?

OB86 runs at priority class 26 on the S7-300 and ET 200S. This is higher than OB1 (priority 1) and lower than OB100 / OB101 / OB102 (priority 27). The priority is fixed and cannot be changed by the user.

Back to blog