S7-300 Pulse Generation for Motion Sync: FM 352-5 Module Guide

David Krause15 min read
Motion ControlSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview: Pulse Generation as a Master Clock Source

Driving a bank of servo inverters or variable frequency drives (VFDs) from a single master clock generated by an S7-300 CPU 315F-2 DP is a recurring requirement in converting lines, packaging machinery, and web-handling applications. The specification in the source brief calls for a clock signal that is fed into a downstream controller (often a SIMOTION, SINAMICS, or third-party motion controller) so that all axes can be tied to a common reference. The fundamental engineering question is not whether the PLC can toggle a digital output, but whether the resulting signal has the deterministic edge-to-edge timing required to keep a moving web or chain in registration.

Before selecting any module, calculate the required pulse rate. The two operating modes in the brief translate as follows:

Resolution Max linear speed Required pulse frequency fpulse
1 pulse / 1 mm 400 mm/s 1 × 400 = 400 Hz
1 pulse / 0.1 mm 400 mm/s 10 × 400 = 4,000 Hz
1 pulse / 1 mm 100 mm/s (ramp start) 100 Hz
1 pulse / 1 mm 300 mm/s (ramp end) 300 Hz

Use the general form f_pulse (Hz) = resolution (pulses/mm) × linear_speed (mm/s). For any axis synchronisation problem the same formula applies with the encoder-pitch substituted for the linear travel.

Why Standard Digital Output Modules Cannot Hold the Rate

When a standard SM 322 DO module is commanded from OB1, the latency stack between the CPU's logical decision to set the bit and the physical transition of the field terminal includes:

  1. OB1 scan completion and PIQ transfer time
  2. Backplane bus update on the ET200S station (IM 151-1 HIGH FEATURE 6ES7151-1BA02-0AB0)
  3. PROFIBUS DP cycle time if the ET200S is on DP
  4. Module-internal output-driver propagation delay (typ. 50–100 µs for SM 322)
  5. Optocoupler and output-stage rise/fall time

The dominant contribution is the application scan. A typical CPU 315F-2 DP with mixed bit/word logic and a few FB calls runs OB1 in 8–15 ms. To generate a 400 Hz square wave from a single bit toggled each cycle, the scan must be at most 1.25 ms. To generate 4,000 Hz the scan must be ≤ 125 µs. Neither value is achievable in OB1 on a 315F-2 DP for any real production program.

Even if the scan were fast enough, jitter is the deal-breaker. Field experience has shown that a routine clock generated in OB1 with the cycle held at ~10 ms can stretch to 65 ms when communications overhead, alarm tasks, or math blocks temporarily extend the cycle. A 65 ms low period followed by a 10 ms high period produces a frequency that swings from 13 Hz to 50 Hz, and worse, the edge-to-edge distance at 400 mm/s drifts between 5.2 mm and 26 mm. That is exactly the failure mode that has been documented in the field: mis-synchronised axes, web stretch, and mechanical damage in the worst case.

Design rule: Never derive a master clock from a bit toggled in OB1. The PLC cycle, even on a high-end CPU, is non-deterministic in the microsecond range, and that is the band that matters for axis synchronisation.

Frequency Budget by Hardware Class

Source Max useful f (Hz) Jitter (typ.) Use case
SM 322 DO toggled in OB1, CPU 315F-2 DP ~50 ± 30 ms Indicator lights, slow actuators
SM 322 DO toggled in OB35 (2 ms) ~250 ± 0.5 ms Status pulses only — not synchronisation
ET200S 1Count 24V (6ES7138-4DA04-0AB0) 10,000 (1×), 1,000 (4×) ± 1 µs 1 pulse/mm @ 400 mm/s — fits with margin
FM 350-1 counter (6ES7350-1AH03-0AE0) 500,000 ± 0.5 µs High-end clock generation
FM 352-5 high-speed boolean processor (6ES7352-5AH0x-0AE0) 200,000 output transitions/s ± 1 µs Cam switching, pulse output, fast logic
PROFINET IRT, isochrone I/O Deterministic, cycle-tied < 1 µs Preferred for new systems

For the 100–400 Hz requirement (1 pulse/mm mode) the FM 350-1, the FM 352-5, and the ET200S 1Count 24V all have more than 10× margin. For the 4,000 Hz requirement (1 pulse/0.1 mm) all three still hold, but the standard-DO and OB35 solutions are excluded.

FM 352-5 High-Speed Boolean Processor

The recommendation in the engineering community for high-speed pulse generation on S7-300 is the FM 352-5. The device is a self-contained, electrically isolated 12-output high-speed logic module that runs independently of the OB1 cycle. The CPU downloads a configuration (a chain of AND/OR/TIMER/COUNTER/OUTPUT operations, plus cam-style switching) and the FM executes it on its own internal scan, typically 1 µs per instruction.

Parameter Value
Order number (typical) 6ES7352-5AH01-0AE0
Digital inputs 8 (24 V DC, 0.5 ms filter)
Digital outputs 4 (24 V DC, 0.5 A) + 8 relay or 8 transistor variants
Max output frequency per channel 200 kHz
Internal cycle time 1 µs per instruction
Programming LAD/FBD inside HW Config, FM 352-5 configuration tool
Configuration interface Backplane (S7-300)
Status/diagnostic LED per channel, channel status bits in I/O area

The FM 352-5 fits a standard S7-300 rail slot and is configured as a single analog or function module slot in HW Config. The user programs a sequence of boolean operations that toggle the output on a time or count basis; the CPU only writes a frequency setpoint and reads a status word. Because the FM keeps toggling the output on its own, the result is unaffected by OB1 jitter.

Configuration in HW Config (Step 7 V5.5 / TIA Portal V16+)

  1. Insert the FM 352-5 into the S7-300 station. Allocate a free slot; the FM cannot share a slot group with SM modules.
  2. Open the module properties and assign inputs DI0–DI7 to the events you want to act on (for a simple clock, none — use the on-board counter).
  3. Open the FM 352-5 configuration editor and place an OUTPUT element on the ladder rung. Wire a TIMER (set to 0.5 / f_desired) to the output.
  4. For dynamic speed changes, expose the timer preset as a DBW interface. The CPU writes the new value (in µs) on each ramp step, the FM updates on the next internal cycle.
  5. Download the HW Config and the FM configuration to the CPU. The FM self-initialises on CPU restart.

ET200S Counter Module Approach

For installations where the CPU 315F-2 DP drives an ET200S station with IM 151-1 HIGH FEATURE, the 1Count 24V (6ES7138-4DA04-0AB0) is a more compact solution. The 1Count module can be configured as a pulse generator with a frequency range of 0.1 Hz to 10 kHz, and it can be gated and re-parameterised on the fly through process data.

Parameter 1Count 24V (6ES7138-4DA04-0AB0)
Modes Counting, measuring, pulse generator
Max output frequency (pulse generator) 10 kHz
Frequency resolution 32 bits signed (0.1 Hz per LSB in pulse-gen mode)
Output 1 × DO 24 V, 0.5 A, short-circuit-proof
Update latency for setpoint change 1 DP cycle + 1 ms internal
Slot compatibility ET200S, any electronic module slot

Setpoint write in S7 is a simple PQW transfer:

// Frequency setpoint in 0.1 Hz LSB. 4000 Hz = 40000 dec.
L 40000
T PQW 304    // slot 4 base address; adjust to ET200S slot 1

For a smooth 100 → 300 Hz ramp, drive the PQW from an OB35 block (e.g. 100 ms) that adds a fixed increment per call. The module will accept each new setpoint at the next internal update without dropping a pulse.

Isochrone note: When the ET200S is on PROFIBUS DP with the IM 151-1 HIGH FEATURE, the 1Count module supports isochronous mode only if the DP master is set to constant bus cycle time (constant bus cycle time TDP = 1.5 ms minimum). Without isochrone mode, expect ± 1.5 ms of jitter on the output edge — still acceptable for 100–4000 Hz master-clock use.

FM 350-1 Counter Module (High-End)

For installations that exceed 10 kHz or that need quadrature simulation, the FM 350-1 counter (6ES7350-1AH03-0AE0) is the next step. It is a single-channel counter with an internal DSP for fast comparison and pulse-train generation.

Parameter FM 350-1 (6ES7350-1AH03-0AE0)
Counting frequency 500 kHz max
Operating modes Continuous, single, periodic count; frequency measurement; pulse generation
Outputs 2 × DO 24 V, isolated
Gate time / pulse width Programmable from 1 µs to 65 ms in 1 µs steps
Configuration HW Config FM 350-1 properties; SFC 84 / SFC 87 for dynamic parameter changes

Use the FM 350-1 when a system later requires encoder simulation or when the master clock has to be derived from a closed-loop ratio against a process variable (e.g. dancer position, line speed feedback).

OB35 Cyclic Interrupt — Limited Use

OB35 is a time-of-day interrupt that runs at a fixed interval set in HW Config (1 ms to 60,000 ms). It is deterministic relative to itself but not to the I/O update, because OB35 simply pre-empts OB1 at its scheduled time. For a clock generator, OB35 can be used as a high-level timer: the OB increments a counter, the program toggles a bit when the counter equals the half-period, and a SM 322 DO echoes the bit. With OB35 at 2 ms, the maximum square-wave frequency is 250 Hz with 2 ms jitter — and the jitter is exactly the OB period, which is unacceptable for axis sync above ~10 Hz.

Therefore OB35 is not a valid clock source. It is suitable for re-parameterising the FM 352-5 or 1Count module at a smooth rate, e.g. to ramp from 100 Hz to 300 Hz over 5 seconds (500 increments at 10 ms).

// OB35 — 10 ms cycle, ramp 100 Hz to 300 Hz over 5 s
// Setpoint written to 1Count at PQW 304 (0.1 Hz units)
      L     DB10.DBW 0       // current setpoint (0.1 Hz)
      L     2                // step = 0.2 Hz / 10 ms = 20 Hz/s
      +I
      T     DB10.DBW 0
      L     3000             // limit 300.0 Hz = 3000 dec
      <I
      JC    RAMP
      L     3000
      T     DB10.DBW 0
RAMP: L     DB10.DBW 0
      T     PQW 304

PROFINET IRT and Isochrone Mode

The most modern and deterministic approach on a SIMATIC system is PROFINET IRT (Isochronous Real-Time). With an isochrone-capable IM (e.g. IM 151-3 PN on ET200S) and an isochrone counter module, the entire path from the CPU's clock to the output terminal is synchronised to a fixed network cycle. Edge jitter drops to sub-microsecond.

Property PROFIBUS DP isochrone PROFINET IRT
Minimum cycle 1.5 ms 250 µs
Jitter (worst case) ± 10 µs ± 1 µs
CPU requirement PROFIBUS master with constant bus cycle PROFINET IRT controller (e.g. CPU 315F-2 PN/DP)
ET200S IM IM 151-1 HIGH FEATURE (6ES7151-1BA02-0AB0) IM 151-3 PN (6ES7151-3BA23-0AB0)
Counter module 1Count 24V in isochrone mode 1Count 24V / 1Count 5V

To enable isochrone mode, set "Constant bus cycle time" in HW Config under the DP master system properties and tick "Isochrone mode" on the slot that holds the counter module. The Ti and To times must be entered; typical values for the 1Count 24V are Ti = 250 µs, To = 100 µs.

Drive-to-Drive Synchronisation — The Architecturally Cleaner Choice

Generating a clock from any PLC and then shipping it down a wire to a separate motion controller introduces two new failure modes: cable break, and ground-loop noise on the clock edge. For new designs, evaluate the drive-native alternatives first.

  • SINAMICS S120 with CU320-2: SIMOLINK fibre-optic ring for deterministic, cycle-tied distribution of setpoints between drives. Up to 200 nodes, sub-microsecond synchronisation.
  • SINAMICS S120 with CU310-2: Master/slave position control over PROFIdrive telegram 110 — drive to drive, no PLC in the loop.
  • Allen-Bradley Kinetix 6500: CIP Motion on EtherNet/IP with Time Sync (IEEE 1588) — drive-to-drive only, PLC acts as configurator.
  • Yaskawa Sigma-7 / MP3300iec: MECHATROLINK-III motion bus.

For the application described, the SIMOLINK ring between SINAMICS S120 drives is often the most robust solution, because the master clock is generated by the first drive's encoder, not by the PLC. The PLC only needs to command the desired ratio through PROFIdrive.

Wiring and EMC Considerations

  1. Run the clock pair (24 V output and 0 V return) in a shielded twisted pair. Ground the shield at the source end only.
  2. Keep the clock cable in its own tray, at least 200 mm from VFD power cables. Cross at 90° if a crossing is unavoidable.
  3. Provide a 24 V DC suppressor (1N4007 reverse-biased, or a TVS) at the receiving controller's terminal block, especially when the cable run exceeds 10 m.
  4. Set the receiver's input filter to the minimum value that rejects the expected noise. A 0.5 ms input filter cuts the noise band but does not affect a 100 Hz to 4 kHz clock.
  5. Use a pull-up resistor on the receiver side (typically 2.2 kΩ to 24 V) only if the receiver is a sinking input; sourcing outputs of the SM/FM do not need it.

Verification and Commissioning Checks

Check Method Acceptance
Output frequency at static setpoint Oscilloscope or frequency counter on the output terminal ± 0.1 % of setpoint
Edge jitter Scope trigger on rising edge, 1 s persistence ≤ 50 µs for FM, ≤ 1 µs for IRT
Duty cycle Scope measurement 50 % ± 2 %
Ramp response (100 → 300 Hz over 5 s) Capture frequency on a chart recorder or trace Linear, no overshoot, no missing pulses
CPU OB1 scan during the test Read OB1 last scan time from diagnostic buffer Must be < 1.5 × OB35 period (else I/O update is being delayed)
Drive reception View drive's received pulse count vs. PLC's transmitted count Equal after 60 s of motion at 400 mm/s

Troubleshooting Matrix

Symptom Likely cause Action
Output frequency is half the setpoint Output toggles only on rising edge of internal timer; counter half-period miscalculated Verify TIMER preset = 0.5 / f, not 1 / f
Output frequency drifts during CPU restart FM 352-5 lost configuration because HW Config was re-downloaded Re-download FM configuration, not just HW Config
Pulses drop out when OB1 scan exceeds 30 ms 1Count setpoint register is being overwritten mid-period Write the setpoint from OB35 only; never from OB1
Receiving controller shows 65 ms jitter spikes Clock is being generated in OB1, not from a dedicated FM or counter Re-architect: use FM 352-5, FM 350-1, or 1Count 24V
Diagnostic buffer: "IO access error on output address" Slot mismatch between HW Config and physical rack Compare the slot list; do not auto-rearrange after download
Pulses stop during PROFIBUS diagnostic Constant bus cycle time not enabled Tick "Constant bus cycle time" in DP master system properties
Output frequency is correct but drives disagree on speed Each drive's gearing to the master clock is set differently Verify the gear ratio parameter on every drive; do not copy-paste from one to the next without scaling
Master clock signal inverted at receiver Sinking vs. sourcing mismatch Add the inverter logic at the FM output rung, or add a NOT element in the receiver configuration

Recommended Configuration Summary

Scenario Recommended source
1 pulse/mm, 100–400 Hz, simple I/O on existing ET200S DP ET200S 1Count 24V (6ES7138-4DA04-0AB0) in pulse-generator mode, setpoint from OB35
1 pulse/0.1 mm, up to 4 kHz, ET200S PN ET200S 1Count 24V with IM 151-3 PN, isochrone, IRT
Multiple clock outputs, complex boolean relationships FM 352-5 high-speed boolean processor
Encoder-style simulation, > 10 kHz FM 350-1 counter
New system, no legacy constraint Drive-to-drive synchronisation via SIMOLINK or PROFIdrive master/slave, no PLC in the loop

References to Official Documentation

Frequently Asked Questions

Can I generate a 400 Hz clock from a standard SM 322 DO toggled in OB1 on a CPU 315F-2 DP?

No, not reliably. The OB1 cycle is 8–15 ms typical and can stretch to 65 ms under load, so a bit toggled in OB1 produces a clock that drifts between 13 Hz and 50 Hz with 10–50 ms of edge jitter — far outside the tolerance for axis synchronisation. Use the FM 352-5, FM 350-1, or an ET200S 1Count 24V instead.

What is the difference between the FM 352-5 and the FM 350-1 for pulse generation?

The FM 352-5 is a high-speed boolean processor that runs a user-defined ladder of AND/OR/TIMER/OUTPUT operations on its own internal scan, ideal for cam switching and fast logic with up to 200 kHz output transitions. The FM 350-1 is a single-channel counter module with a 500 kHz DSP, better suited for frequency measurement, encoder simulation, and continuous pulse generation where you want hardware-driven setpoint accuracy.

How do I ramp the output frequency from 100 Hz to 300 Hz without dropping pulses?

Write the new setpoint from a cyclic OB (typically OB35 at 10–100 ms) into the PQW of the counter module, or into the FM's DBW interface. The hardware accepts the new value on the next internal cycle; the output is never interrupted because the counter or FM keeps toggling the bit autonomously between updates.

What is the maximum frequency I can get from the ET200S 1Count 24V (6ES7138-4DA04-0AB0) in pulse-generator mode?

The 1Count 24V supports up to 10 kHz output in pulse-generator mode, with setpoint resolution of 0.1 Hz. For the 4,000 Hz upper end of the requirement in this application, the module has more than 2× margin and is the most cost-effective choice.

Is OB35 alone fast enough to use as a clock source?

OB35 is deterministic relative to its scheduled time but still has ± 1 OB-period of jitter and an upper output frequency of 1 / (2 × OB_period). With a 2 ms OB35 the maximum is 250 Hz with 2 ms edge jitter, which is unacceptable for axis synchronisation. Use OB35 only to write setpoints to a dedicated pulse generator module; never to toggle the output bit directly.

What is the cleanest architecture for a multi-axis system that needs a common clock?

Use a drive-to-drive communication channel such as SIMOLINK (SINAMICS S120), PROFIdrive master/slave telegrams 110, or CIP Motion with IEEE 1588 time sync. The PLC's role is reduced to a configurator and supervisor; the clock is generated by the first drive's encoder and distributed on a deterministic, noise-immune medium. This eliminates the cable-break and ground-loop risk of a wired clock signal from the PLC.

Back to blog