Overview: Modbus Between Two S7-300 CPUs
Modbus is a de facto industrial protocol for inter-PLC data exchange, but Siemens S7-300 CPUs do not support Modbus RTU or Modbus TCP natively. Any S7-300 to S7-300 Modbus link requires dedicated hardware (a Communication Processor) and a licensed function block library, or a migration to a CPU family that has built-in Modbus support (S7-1200, S7-1500, ET 200SP).
Before specifying hardware, lock down the four design parameters that drive every later decision:
- Physical media – RS-485 half-duplex (RTU) vs. industrial Ethernet (TCP).
- Master / slave role assignment – which CPU initiates transactions, which responds.
- Data throughput – number of words, cycle time, determinism.
- Project budget – CP cost + Modbus driver library license vs. zero-cost alternatives such as S7 GET/PUT.
For two S7-300 stations in the same plant that simply need to exchange process data over Profinet or MPI, the S7 GET/PUT instructions are almost always the lower-cost, lower-risk path. Modbus becomes the right answer only when one of the CPUs must inter-operate with a third-party device (drive, SCADA RTU, energy meter, vendor package) that already speaks Modbus.
Modbus RTU Path: Hardware and Wiring
Modbus RTU on S7-300 always requires a serial Communication Processor (CP) on each rack. The integrated serial interfaces of the S7-300 CPUs (MPI / PtP combo port) cannot be used for Modbus because they do not support the RS-485 framing, slave addressing, and timing required by the Modbus RTU state machine when paired with the licensed driver.
CP Selection Matrix for Modbus RTU
| Module | Order Number (MLFB) | Interfaces | Max Baud Rate | Modbus RTU Library | Notes |
|---|---|---|---|---|---|
| CP 340 | 6ES7 340-1AH02-0AE0 | 1 × RS-485 (isolated) | 19.2 kbit/s (older revs), 115.2 kbit/s on 1BH02 | Modbus Master (RTU) for CP 340/341 – limited FC support | Lower cost, but Modbus driver support is limited and not recommended for new projects. |
| CP 341 | 6ES7 341-1AH02-0AE0 (RS-485) / 6ES7 341-1BH02-0AE0 (RS-232) | 1 × RS-485 or RS-232 | Up to 115.2 kbit/s | Modbus Master (RTU) for CP 341 or Modbus Slave (RTU) for CP 341 | Reference platform for Modbus RTU on S7-300; supports FC 01, 02, 03, 04, 05, 06, 07, 08, 11, 12, 15, 16. |
| CP 341 with RS-422/485 | 6ES7 341-1CH02-0AE0 | 1 × RS-422/485 | 115.2 kbit/s | Same as above | Use for multi-drop RS-485 buses with more than two devices. |
Install one CP 341 (RS-485 variant) in each S7-300 rack. Wire the two RS-485 ports point-to-point using a shielded twisted pair. RS-485 Modbus requires termination at both ends: 120 Ω across the data pair, with bias resistors enabled on at least one node if the master does not actively drive the line in idle state.
CP 341 DIP Switch and Front-Panel Settings
- Set the CP 341 to the Modbus Master or Modbus Slave firmware load using the parameter assignment tool in STEP 7 / TIA Portal. The Modbus protocol is uploaded to flash on the CP as a separate firmware package; the default load on delivery is a generic ASCII/3964(R) driver.
- Assign the RS-485 bus address (1–247). Each Modbus RTU device on a bus segment must have a unique address; for an S7-300 to S7-300 link, slave = 1 and master = 2 is a common convention.
- Match the baud rate and parity on both CPs (e.g. 19200, 8, E, 1) and verify the inter-character timeout (3.5 character times) that the CP uses to delimit RTU frames.
Modbus TCP Path: Hardware and Topology
Modbus TCP runs over industrial Ethernet. On the S7-300 you have two options:
- Integrated PROFINET port of an S7-31x-2 PN/DP CPU (e.g. CPU 315-2 PN/DP, CPU 317-2 PN/DP, CPU 319-3 PN/DP). The PROFINET interface is a standard 100 Mbit/s Ethernet port and can be used for Modbus TCP without any additional hardware, but it still requires the Modbus TCP library on the CPU.
- CP 343-1 (6ES7 343-1EX30-0XE0 or current 6GK7 343-1HX00-0XE0 Lean/Standard). Use a separate CP 343-1 when the integrated PROFINET port is fully consumed by I/O devices, HMI panels, or other PROFINET traffic and you need to isolate Modbus traffic on its own physical interface.
Modbus TCP Wiring
Modbus TCP is standard 10/100 Mbit/s Ethernet. Use Cat 5e or higher shielded cable. For a direct CPU-to-CPU link use a crossed cable (older gear) or rely on Auto-MDI/MDIX on the integrated PROFINET port. For multi-drop (master + several slaves, or multiple Modbus nodes behind managed switches), use a star topology with managed switches that support IGMP snooping and QoS.
TCP Port and Connection Parameters
| Parameter | Recommended Value | Note |
|---|---|---|
| Modbus TCP port | 502 (default) | Reserved by IANA; do not change unless behind a NAT. |
| Connection type | TCP (RFC-compliant), keep-alive enabled | Modbus TCP messages fit in a single TCP segment; UDP is not part of the Modbus TCP spec. |
| Max clients (server side) | Per library; check current release | The Modbus TCP CP library opens one passive connection per slave-side partner. |
| Transaction ID | Auto-managed by library | Each ADU carries a 2-byte MBAP transaction ID; the library handles request/response matching. |
| Poll cycle | Application-defined, typical 50–500 ms | Slower polling reduces CPU load and network traffic. |
Software Libraries: What Must Be Licensed
Unlike the S7-1200, S7-1500, ET 200S, and ET 200SP families, the S7-300 has no native Modbus function blocks in the operating system. Every Modbus implementation on S7-300 uses a separately licensed library that must be installed in STEP 7 and called from the user program. The currently supported packages for the legacy S7-300 line are:
Required Libraries for Modbus RTU on CP 341
-
Modbus Master (RTU) for CP 341 / CP 340 – order number
6AV6 671-1AE01-0AX0 (or current Modbus_Master_PtP). Provides FB 7 (P_SND_RK), FB 8 (P_RCV_RK), and the Modbus-specific FB 80 / FB 81 wrappers depending on version. -
Modbus Slave (RTU) for CP 341 / CP 340 – order number
6AV6 671-1AE02-0AX0 (or current Modbus_Slave_PtP). Provides FB 82 / FB 83 with FC 03, 06, 16 holding-register access.
Required Libraries for Modbus TCP on S7-300
-
Modbus TCP CP –
6AV6 671-1XC10-0AX0 for use with CP 343-1. Implements FB 65 (TCP_CONNECT), FB 66 (TCP_SEND), FB 67 (TCP_RECV) wrappers and the Modbus-specific FB 100 series blocks. -
Modbus TCP PN CPU –
6AV6 671-1XC00-0AX0 (or current Modbus_TCP_PN_CPU) for direct use on the integrated PROFINET port of an S7-31x-2 PN/DP. - Modbus TCP RedConnect / Redundant – for use with CP 343-1 Advanced and H-CP setups. Not required for a two-CPU non-redundant link.
Function Code Coverage (CP 341 RTU Library)
| FC | Function | Master | Slave | Typical Use |
|---|---|---|---|---|
| 01 | Read Coils | ✓ | ✓ | Digital outputs from a slave PLC. |
| 02 | Read Discrete Inputs | ✓ | ✓ | Digital inputs to a slave PLC. |
| 03 | Read Holding Registers | ✓ | ✓ | Most common: read 16-bit process words. |
| 04 | Read Input Registers | ✓ | ✓ | Analog inputs on the slave side. |
| 05 | Write Single Coil | ✓ | ✓ | Set a single digital bit. |
| 06 | Write Single Register | ✓ | ✓ | Setpoint writes. |
| 07 | Read Exception Status | ✓ | ✓ | Status word. |
| 08 | Diagnostics | ✓ | ✓ | Loop-back test. |
| 11 | Get Comm Event Counter | ✓ | ✓ | Bus health. |
| 12 | Get Comm Event Log | ✓ | ✓ | Error log readback. |
| 15 | Write Multiple Coils | ✓ | ✓ | Bit-packed output bursts. |
| 16 | Write Multiple Registers | ✓ | ✓ | Block parameter download. |
Configuration Walkthrough: Modbus RTU Between Two S7-300 Stations
Reference: Siemens Application Note 109474714 – Master-Slave Communication with Modbus RTU Protocol for S7-300.
Step 1 – Hardware Install
Insert a CP 341 (RS-485 variant, 6ES7 341-1AH02-0AE0) in slot 4–11 of each S7-300 rack, matching the slot rules for the CPU used. Power down, install, power up, and verify the CP is recognized in the online diagnostic view of STEP 7 HW Config.
Step 2 – Firmware Load
Open the CP 341 properties dialog in HW Config and select Modbus Master or Modbus Slave as the protocol. The tool pushes the Modbus firmware into the CP's flash. One side is master, the other is slave.
Step 3 – Library Install in STEP 7
Install the licensed library (e.g. Modbus_Master_PtP and Modbus_Slave_PtP) in the project. In the master station, open the library and drag the Modbus master FB (FB 80 / FB 81 depending on library version) into the OB 1 cyclic program. In the slave station, drag the Modbus slave FB into OB 1.
Step 4 – Instance DB Wiring
Each Modbus FB requires an instance data block. Configure the instance DB with:
-
LADDR– the I/O start address of the CP from HW Config (e.g. 256). -
SLAVE_ADDR– Modbus RTU address (1–247). -
START_REG– first holding register exposed to the bus. -
QTY– number of words or coils to transfer per transaction. -
DATA_PTR– pointer to a data block in the CPU (e.g.P#DB100.DBX0.0 WORD 50) that backs the Modbus register map.
Step 5 – Cycle and Trigger
Call the master FB once per application cycle (OB 1) or in a time-controlled OB (e.g. OB 35 at 100 ms). The FB handles request, response, error decoding, and retries internally; you monitor the STATUS and DONE/ERROR outputs to detect bus faults.
Modbus TCP Configuration Walkthrough
Reference: Siemens TIA Documentation – Overview of Modbus RTU Communication (S7-300, S7-400) and the corresponding Modbus TCP manual pages on the Siemens support site.
Step 1 – IP Plan and Connection Table
Assign static IP addresses to both CPUs (or the CPs). For a 192.168.10.0/24 subnet, set CPU-A = 192.168.10.10, CPU-B = 192.168.10.11, subnet mask 255.255.255.0, no gateway. Enable the PROFINET port in HW Config and assign it to the same subnet as the S7 routing path.
Step 2 – Open the Connection in NetPro / TIA
Insert a new S7 connection between the two PROFINET interfaces. Mark the local endpoint as Modbus_TCP_PN_CPU partner (or use the connection ID set up by the library configuration tool). For the CP 343-1 variant, the connection is established from the master to the slave's IP at port 502.
Step 3 – Master Call
On the master side, call the Modbus TCP function block (e.g. MODBUS_TCP_MASTER or FB 100 in the older library). The block encapsulates the MBAP header, the PDU, and the TCP send/receive calls. Use FC 03 (read holding registers) and FC 16 (write multiple registers) for the bulk data exchange.
Step 4 – Slave Call
On the slave side, call the matching Modbus TCP slave block. The block accepts incoming TCP connections on port 502, parses the PDU, and either reads from or writes to the configured data block.
Step 5 – Watchdog and Keep-Alive
Enable the application's own application-level watchdog (a heartbeat counter updated on every successful transaction). A stuck TCP connection with no watchdog is the single most common cause of "the link looks healthy but data is stale" in field reports.
The Native Alternative: S7 GET / PUT (No CP, No License)
If the only requirement is two S7-300 stations exchanging process data with each other – not with a third-party Modbus device – use the S7 communication services GET and PUT. These are part of the CPU firmware, require no CP, and need no license beyond the standard S7 CPU.
Why GET / PUT is Usually the Right Answer
| Aspect | GET / PUT (S7 Comm) | Modbus (RTU or TCP) |
|---|---|---|
| Hardware | Integrated PROFINET or MPI port | CP 341 or CP 343-1 on each station |
| License | None | Modbus library license per station |
| Configuration effort | One connection, two FB calls | Library install, connection, FB calls, register map |
| Data model | Direct access to any DB / bit / word | Holding-register / coil map emulation |
| Interoperability with 3rd-party | No (Siemens only) | Yes (drives, RTUs, SCADA) |
| Throughput on PROFINET | Higher (binary, no PDU encoding) | Lower (PDU encoding + TCP/IP) |
| Maximum partner count | Up to 16 connections (CPU-dependent) | Limited by library connection table |
GET / PUT Call Example (Master Side)
Place a single-instance call to GET in OB 1 with the partner connection configured in NetPro or the TIA devices & networks editor:
// ST – S7-300 master calling GET to read 20 bytes from partner DB 100
CALL "GET"
REQ := M10.0 // Trigger: edge
ID := 1 // Connection ID from NetPro
NDR := M10.1 // New data received (1 cycle pulse)
ERROR := M10.2 // Error flag
STATUS := MW12 // Detailed status word
ADDR_1 := P#DB100.DBX0.0 BYTE 20 // Partner area
ADDR_2 := P#DB200.DBX0.0 BYTE 20 // Local area
RD_1 := P#M 100.0 BYTE 20 // Receive buffer (local)
END_CALL;
For the reverse direction, call PUT with SD_1 as the local source and ADDR_1 as the partner destination. Cycle the REQ input at the desired poll rate; do not call it on every OB 1 pass unless you need sub-100 ms latency.
Troubleshooting Matrix
| Symptom | Likely Cause | First Check | Corrective Action |
|---|---|---|---|
| CP 341 SF LED on, BF LED flashing | Modbus slave not responding, parity / baud mismatch, A/B swapped | Verify baud / parity on both CPs with a Modbus scanner on the wire. | Swap A/B; restore matching parameters; add 120 Ω termination. |
| Modbus TCP STATUS = 0x80F1 | TCP connection could not be established | Ping partner IP; check firewall between subnets. | Open port 502 in firewall; verify IP / subnet mask / gateway. |
| Modbus TCP STATUS = 0x80F4 | Send/receive resource error | Check number of parallel open connections vs. library limit. | Reduce concurrent connections; upgrade CPU firmware if cap is a CPU limit. |
| Modbus response carries exception code 02 (ILLEGAL DATA ADDRESS) | Master requested a register outside the configured map | Compare START_REG + QTY with the configured DATA_PTR length. | Increase the DB size backing the register map, or reduce QTY. |
| Modbus response carries exception code 03 (ILLEGAL DATA VALUE) | Value out of range (e.g. FC 05 with non-0xFF00) or wrong function code for the block | Inspect master request bytes. | Fix the master; use FC 16 for block writes instead of FC 06 in a loop. |
| Communication works then drops every few hours | TCP keep-alive disabled, intermediate switch timeout | Check switch logs for MAC aging. | Enable TCP keep-alive in the connection; pin MAC in the switch. |
| Library FBs compile but download fails with "license missing" | License key not installed on MMC / card | Open Licenses view in TIA / STEP 7 for the target device. | Transfer license from the License Key (ALM) to the target. |
| GET / PUT STATUS = 0x0001 (resource problem) | No free connection resource on the partner CPU | Count active S7 connections in the partner's connection table. | Free or re-route one connection; add CP 343-1 if CPU limit reached. |
When to Choose Each Path
- Two Siemens S7-300s exchanging data, no third-party device – use GET / PUT over PROFINET or MPI. Lowest cost, lowest risk, fastest commissioning.
- One S7-300 talking to a Modbus RTU device (drive, RTU, energy meter) – install a CP 341 on the S7-300 side, add the Modbus Master (RTU) library, configure the bus.
- One S7-300 talking to a Modbus TCP SCADA or device – add the Modbus TCP PN CPU library (uses the integrated PROFINET port) or install a CP 343-1 and the Modbus TCP CP library if the PROFINET port is full.
- Both S7-300s must also be Modbus slaves to a third-party master – install one CP 341 per station and the Modbus Slave (RTU) library on each.
- New project with no installed base – choose S7-1200 / S7-1500 instead. Modbus TCP and Modbus RTU (via CB 1241 / CM 1241) are native firmware features with free FBs and no library license.
Verification Checklist
- Confirm the Modbus library license is installed on both target devices.
- With a Modbus scanner (e.g. Modbus Poll, CAS Modbus Scanner) connected to the bus, read the test register and verify the raw Modbus frame matches the configured start address and quantity.
- Use STEP 7 Monitor / Modify on the backing DB and observe values update per cycle.
- Force a fault (unplug the cable, power down the partner) and verify that the error status, retry counter, and exception codes propagate to the user program as expected.
- Log a 24-hour run with the CP diagnostic buffer and confirm zero CRC or timeout errors beyond the first minute after power-up.
- Document the bus address, baud rate, parity, register map, and license key location in the project documentation for future maintenance.
Do I need a hardware module to do Modbus between two S7-300 CPUs?
Yes for Modbus RTU – you need a CP 341 (or CP 340) in each rack, plus the licensed Modbus Master/Slave (RTU) library. For Modbus TCP you can use the integrated PROFINET port of an S7-31x-2 PN/DP CPU or a CP 343-1, but you still need the licensed Modbus TCP library. S7-300 firmware has no native Modbus support.
Can I just use GET/PUT instead of Modbus between two S7-300s?
Yes. GET and PUT are part of the S7 CPU firmware, run on the integrated PROFINET or MPI port, and require no license. They are the recommended path whenever both ends are Siemens and there is no third-party Modbus device on the bus.
What is the difference between CP 340 and CP 341 for Modbus RTU?
CP 340 is the lower-cost predecessor with limited Modbus function-code coverage and lower baud-rate support. CP 341 is the reference platform, supports all standard Modbus function codes (FC 01–16), and is the module Siemens documents and tests the Modbus library against. Use CP 341 for new projects.
What license do I need for the Modbus library on S7-300?
For Modbus RTU on CP 341, you need 6AV6 671-1AE01-0AX0 (Master) and/or 6AV6 671-1AE02-0AX0 (Slave). For Modbus TCP on the PROFINET port, you need 6AV6 671-1XC00-0AX0. For Modbus TCP on CP 343-1, you need 6AV6 671-1XC10-0AX0. The license is installed on the S7-300 memory card.
Can the S7-1200 do Modbus TCP without extra hardware or licenses?
Yes. The S7-1200 firmware includes native Modbus TCP master and server function blocks that run on the integrated PROFINET interface. No CP, no library, no runtime license is required. For Modbus RTU, a CM 1241 or CB 1241 RS-485 module is still needed, but the FBs are free.