S7-315-2DP and MICROMASTER 440 VFD System Design for 22 kW Motor

David Krause18 min read
SiemensTechnical ReferenceVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

System Overview and Application Context

The reference design described in this article combines a Siemens SIMATIC S7-300 CPU 315-2DP, a SINAMICS / MICROMASTER 440 (MM440) inverter, and a SIMATIC Mobile Panel 170 (MP170) to drive a 22 kW, four-pole, 1500 rpm asynchronous induction motor through a 28.3:1 speed reducer. The gearbox output shaft runs at 53 rpm and produces 3960 Nm of torque at full motor load. The mechanical load is a bulk-fertilizer loading elevator that draws material from a conveyor and discharges it into a railcar. Because the bulk density of the fertilizer varies significantly from one chemical formula to another, the operator must continuously trade speed against torque to keep the elevator from stalling while still maximizing throughput. The control system must therefore expose an adjustable speed setpoint, protect the motor from thermal overload, and provide a clear visualization of the process on the mobile panel that the loader operator carries along the railcar.

All of the design numbers below come from the motor nameplate, the MM440 operating instructions (6SE6400-5AD00-0BP0), the S7-300 CPU 315-2DP manual (entry ID 12996906 in the Siemens Industry Online Support), and the SIMATIC HMI Mobile Panel 170 manual. Where the design assumes a value that is not stamped on a nameplate, the calculation path is shown explicitly so that you can substitute the actual project value.

Important: Before energizing any drive, confirm that the motor nameplate voltage, frequency, insulation class, and service factor are entered into the MM440 motor data set (P0304, P0305, P0307, P0308, P0310, P0311). The drive's I²t thermal model is only as accurate as these parameters.

System Architecture and Topology

Three logical networks are formed:

  1. PROFIBUS-DP between the S7-300 CPU 315-2DP (master) and the MM440 (slave). The MP170 also drops onto the same DP segment as a slave and is wired in a daisy chain with a terminating resistor enabled at the physical end of the line.
  2. 24 V DC power for the S7-300 PS307, the MP170, the encoder, and the I/O backplane. A SITOP PSU300M 24 V / 10 A is recommended for the control section so that the PLC and HMI remain powered through a short mains dip.
  3. 400 V AC power from the factory feeder through a fused disconnect or molded-case circuit breaker (MCCB) to the MM440 line input (L1, L2, L3), then a 4-core shielded VFD cable from the MM440 output (U2, V2, W2) to the motor junction box. The motor is bonded to the building ground grid at the motor frame and at the VFD end of the cable shield.
S7-300 CPU 315-2DP 6ES7 315-2AG10 MICROMASTER 440 6SE6440-2UD34-5FA1 22 kW, 45 A, 400 V MP170 Touch 6AV6 642-0AA11-0AX0 PROFIBUS-DP slave 22 kW Motor 4-pole, 1500 rpm, 400 V Δ FLA 42 A, IE2/IE3 PROFIBUS-DP PROFIBUS-DP 4-core shielded VFD cable Shield bond 360°

Mechanical, Electrical, and Torque Analysis at 50 Hz vs 60 Hz

The motor nameplate defines the constant-torque operating envelope. With 50 Hz, 400 V, 22 kW, 1500 rpm the motor produces:

T_motor = P / ω = 22 000 W / (2π × 1500/60) = 22 000 / 157.08 = 140.05 Nm at the motor shaft

Through a single-stage helical-bevel reducer with a 28.3:1 ratio and ~95 % mechanical efficiency, the gearbox output torque is:

T_out = 140.05 × 28.3 × 0.95 ≈ 3763 Nm

For a 100 % efficiency assumption the manufacturer quotes 3960 Nm on the gearbox nameplate. Treat 3763 Nm as the design torque and 3960 Nm as a theoretical ceiling.

What happens at 60 Hz without voltage boost

If the line is 380 V at 50 Hz, the V/Hz ratio is 7.6 V/Hz. Pushing the drive to 60 Hz while keeping 380 V gives V/Hz = 6.33, a 16.7 % reduction. The motor's continuous torque capability drops to roughly 83 % of the design value:

T_motor_60 = 140.05 × (6.33 / 7.6) = 116.6 Nm
T_out_60 = 116.6 × 28.3 × 0.95 ≈ 3134 Nm

The synchronous speed of a 4-pole induction motor at 60 Hz is 1800 rpm, so the gearbox output rises to 1800/28.3 = 63.6 rpm. For a constant-torque load (an elevator bucket, not a centrifugal fan) the absorbed power scales linearly with speed, reaching 26.4 kW. This is above the motor's 22 kW thermal limit, so the motor will thermally overload within minutes at full current.

What happens at 60 Hz with voltage boost

If the supply is 460 V (standard in 60 Hz IEC environments such as Saudi Arabia, the Philippines, or the U.S. NEMA region) and the MM440 is parameterized to deliver 460 V at 60 Hz, the V/Hz ratio returns to 7.6 and the full 140.05 Nm of motor torque is available. The MM440 supports this through parameter P0210 (supply voltage) and the auto-detection of the motor's V/Hz profile in P2000 (reference frequency) and P2002 (reference current).

Operating point V_LL f V/Hz Motor torque (Nm) Output torque (Nm, 95 % eff) Output rpm Mechanical power (kW)
Design, 50 Hz 400 V 50 Hz 8.00 140.05 3763 53.0 22.0
60 Hz, no boost 380 V 60 Hz 6.33 116.6 3134 63.6 22.0 (torque-limited)
60 Hz, 460 V boost 460 V 60 Hz 7.67 140.05 3763 63.6 26.4
50 Hz, 380 V low line 380 V 50 Hz 7.60 133.0 3576 53.0 20.9
Application-specific caveat: An elevator bucket is essentially a constant-torque load. Power still scales linearly with speed, so at 60 Hz with 460 V boost the drive will demand 26.4 kW. A 22 kW motor cannot deliver that continuously without de-rating. Either (a) operate the elevator at 50 Hz at full bucket load and use 60 Hz only when the bulk density is light enough that the bucket is below nameplate torque, or (b) select the next motor size up (30 kW, IE2/IE3) and keep the 22 kW MM440 catalog number for output current margin. The variable-density control strategy of this project makes (a) the practical choice.

V/Hz profile curve (SVG)

Frequency (Hz) Voltage (V) Boost (0–3 %) 460 V / 60 Hz, V/Hz = 7.67 380 V / 60 Hz, V/Hz = 6.33 400 V / 50 Hz, V/Hz = 8.00

Motor Thermal Protection and Circuit Protection Sizing

There are two distinct protective devices in this design: the MM440 electronic motor protection (which models the I²t heating of the motor windings) and the short-circuit / overload device on the line side of the VFD (which protects the VFD input rectifier, the cabling, and the panel).

MM440 I²t model parameters

Parameter Name Value for this design Comment
P0304 Motor rated voltage 400 V From nameplate
P0305 Motor rated current 42 A Nameplate FLA at 400 V Δ
P0307 Motor rated power 22 kW Nameplate
P0308 Motor rated cos φ 0.87 Nameplate
P0309 Motor rated efficiency 0.92 (IE2) or 0.94 (IE3) Nameplate
P0310 Motor rated frequency 50 Hz Nameplate
P0311 Motor rated speed 1460 rpm Nameplate (slip 40 rpm)
P0335 Motor cooling 1 (forced ventilation) or 0 (self-cooled) For self-cooled TEFC motors the I²t model must derate above ~30 Hz. Use P0335 = 1 if a separately-powered fan is fitted.
P0601 Motor temp sensor 0 (no sensor), 1 (PTC), 2 (KTY) If the motor has a PTC, wire it to MM440 terminals 14/15 and set P0601 = 1.
P0604 Threshold (warning) 100 % Threshold for the I²t warning
P0610 Reaction to I²t overload 12 (warning + trip) 1 = trip with restart lockout, 2 = current-limit reduce, 12 = warning then trip
Self-cooled motor warning: When P0335 = 0 and the motor is TEFC, the I²t model must be derated above 30 Hz because the shaft-mounted fan produces less cooling airflow at low speed. The MM440 only enforces this rule if P0335 = 0. For a fertilizer elevator that runs at 50–60 Hz almost continuously, set P0335 = 1 and confirm a separate 230 V fan motor is wired to the motor terminal box. Otherwise, thermal trips will occur in the first summer.

Line-side protection (MCCB or fused disconnect)

The line-side device does not protect the motor — the MM440 does. The line-side device protects the rectifier input, the input reactor, the cabling from the panel to the drive, and the upstream busbar. A 22 kW MM440 (6SE6440-2UD34-5FA1) has a recommended input fuse of 63 A (gG/aR class) per the operating instructions. The molded-case circuit breaker should be selected at the next size above 63 A with a C or D trip curve so that the inrush of the DC-link capacitors (peak ≈ 4–6 × FLA for 1–2 ms) does not nuisance-trip:

Component Catalog option Ampere rating Notes
MCCB, line side Siemens 3VA51 25 kA 63 A, C-curve Adjustable thermal 50–63 A; instantaneous ≈ 10 × In
Input fuse (alternative) NH00 gG/aR 63 A 690 V 63 A Class aR limits let-through I²t to 70 kA²s
Input line reactor (recommended) 6SE6400-3CC07-5ED0 45 A Reduces THD on the line side from 45 % to 25 %
Output reactor (recommended) 6SE6400-3TC07-5ED0 (4 mH) 45 A Mitigates dV/dt on long motor cables
du/dt filter (optional) 6SE6400-3BD23-1BA0 For 20 m+ cable or first-generation inverter-duty motors

VFD-to-Motor Cable Selection (20 m, 4-core Shielded)

At 20 m the cable is short enough that the reflected-wave effect (also called standing-wave or transmission-line effect) is usually negligible for 400 V class drives. EMC compliance, however, still requires a symmetric, shielded cable so that the common-mode currents from the IGBT switching do not radiate into the surrounding installation. A 5-wire cable (3 phases + N + PE) is not the right choice for a VFD output. The VFD does not need a neutral, and 3 phases + PE on a four-core shielded cable is the IEC standard arrangement.

Recommended cable construction: XLPE/Cu/SCR/PE, e.g., 2YSLCY-J or similar, with:

  • 3 × power conductors sized for VFD current (45 A → 10 mm² Cu minimum, 16 mm² preferred for voltage margin)
  • 1 × PE conductor (green/yellow, full cross-section per IEC 60364-5-54)
  • Overall tinned-copper braid screen, coverage ≥ 80 %
  • Optional: a smaller control pair inside the screen for the motor PTC and/or the thermal sensor

For the Siemens-branded equivalent, use 6FX8002-5DA-series MOTION-CONNECT cables, e.g., 6FX8002-5DA11-1AF0 (4G4 + 2 × 1.5) or 6FX8002-5DA31-1AF0 (4G6 + 2 × 1.5) depending on the conductor size you need. For this design with 45 A, the 4G6 cable is appropriate.

Shield termination

At the VFD end, expose the braid and clamp it with a 360° EMC gland into the VFD gland plate. At the motor end, terminate the screen to the motor's internal ground bar (or to a separate EMC clamp on the motor terminal box). Do not pigtail the screen to a PE terminal with a flying lead — that defeats the screen at high frequency.

EMC compliance: With a 4-core shielded cable and a 360° bond at both ends, the MM440 can be installed in a C2 environment (industrial, unrestricted distribution) without the optional EMC filter being mandatory. For a C1 environment (residential) an external filter such as 6SE6400-2FA00-6AD0 is required.

PROFIBUS-DP Networking with the MM440 and MP170

The CPU 315-2DP (6ES7315-2AG10-0AB0) has an integrated PROFIBUS-DP master on the first MPI/DP port. The MM440 does not have PROFIBUS on board — you must add the PROFIBUS communication module:

  • 6SE6400-1PB00-0AA0 — MM4 PROFIBUS module (DP-V0, 12 Mbps)

The MP170 has a 9-pin Sub-D PROFIBUS connector on the bottom. The bus is wired as a shielded 2-wire RS-485 segment, terminated at both physical ends with 220 Ω (bus termination) plus 390 Ω pull-up/pull-down for the idle state.

Device PROFIBUS address Connector Terminating resistor
S7-300 CPU 315-2DP (master) 2 6ES7972-0BA12-0XA0 (90° outlet) OFF (master is mid-bus)
MM440 (slave) 3 6SE6400-1PB00-0AA0 module OFF (mid-bus)
MP170 (slave) 4 6AV6 671-0AC00-0AX0 PG-style ON if at end of segment

Set the MM440 PROFIBUS address with parameter P0918 (the rotary switches on the PROFIBUS module override P0918 if not all 10 positions are in the "0" state). Baud rate auto-detects up to 12 Mbps.

PROFIBUS telegram selection

For closed-loop speed control with a single control word and a single status word, select standard telegram 1 (PZD 2/2). For torque control, use telegram 2. For combined speed/torque with the Siemens PPO type 1 (4 PKW + 2 PZD), the MM440 supports it natively. Configure the telegram in the S7-300 hardware configuration by right-clicking the MM440 in HW Config and selecting the PPO type from the catalog.

PROFIBUS PZD layout (PPO type 1) Word 1 Word 2 Word 3 Word 4 Word 5 Word 6
PKW (parameter channel) PKE IND PWE1 PWE2
PZD (process data) STW1 (control word) NSOLL (speed setpoint) ZSW1 (status word) NIST (speed actual)

PKW allows the S7-300 to read/write any MM440 parameter. PZD allows 12 ms cycle-time control of the speed setpoint and a fast read of the actual speed. The reference speed that corresponds to NSOLL = 4000 hex is set in P2000.

USS Protocol as an Alternative to PROFIBUS

If the PROFIBUS option-module cost is a concern, the CPU 315-2DP can drive up to 31 MM440 units over a shielded twisted-pair RS-485 bus running the Siemens USS protocol on the second interface (PtP, RS-485 half-duplex). The Mobile Panel 170 cannot drop on this same RS-485 segment because it has only a PROFIBUS port, so PROFIBUS is the more practical choice for this project.

USS implementation on the S7-300 uses the SIMATIC MICROMASTER USS library (STEP 7 → Drive ES SIMATIC). The two key blocks are FB 60 / FC 60 (USS SEND/RECEIVE) and FB 61 / FC 61 (USS read/write parameters). The baud rate is fixed at 9.6 or 19.2 kbps, the cycle time is 30–60 ms per drive, and only one master is allowed.

Parameterization Software Selection: STARTER vs. Drive ES Basic vs. SIZER

Siemens sells three different tools that overlap in scope. The right choice depends on what stage of the project you are in:

Tool Catalog number Used for Best stage Connection
SIZER 6SL3070-0AA00-0AG0 Engineering — drive selection, network load, line harmonics, motor matching Concept / quoting Offline only
STARTER 6SL3072-0AA00-0AG0 Commissioning and parameterization of drives (MM4, SINAMICS G, S, V) Commissioning / service RS232 serial (USS) or PROFIBUS
Drive ES Basic 6SW1700-5JA00-1AA0 Drive parameterization from inside STEP 7, with parameter list in the S7 project Integrated HMI/PTO config PROFIBUS / Ethernet
Drive ES PCS 7 6SW1700-6AA00-1AB0 APC and faceplate integration into PCS 7 Process plants PROFIBUS / Ethernet

For this project, install both:

  1. SIZER during quotation to size the MM440, the line reactor, and the brake resistor. SIZER will give you a 22 kW MM440 part number, the matching 6SL3000 line filter, and the recommended cable cross-section.
  2. STARTER for offline parameter set creation, then online commissioning. STARTER is the only tool that supports trace recording on the MM4 series (analog scope of speed, current, torque over time).
  3. Drive ES Basic only if you want the MM440 to appear in the STEP 7 hardware catalog and to expose its parameters as DB tags to the S7-300 program.
Ease-of-use ranking for a first-time user: STARTER (offline editing, online commissioning with live trace) > Drive ES Basic (seamless STEP 7 integration) > SIZER (configuration only, no parameter editing). For a one-off project, STARTER alone is sufficient.

Current Measurement: True-RMS Clamp Meter Behavior on VFD Output

The original poster uses a clamp meter on the line side of the motor to measure load current. Once the VFD is installed, the current waveform on the line side of the motor (between the MM440 and the motor) is no longer a 50/60 Hz sine wave — it is a PWM waveform with a fundamental frequency equal to the motor shaft speed and a carrier (switching) frequency of 4 kHz by default in the MM440 (P1800).

A True RMS clamp meter with a bandwidth of at least 1 kHz and a frequency derating curve that extends to 100 kHz will give a reading within ±2 % of the actual RMS current. An average-responding (cheap) clamp meter will read 10–30 % low. The MM440 also exposes r0027 (output current, A RMS) on its BOP, AOP, or the fieldbus, which is the most convenient reading for a PLC program or a panel trend.

Measurement point Waveform Clamp meter requirement
Line side of MM440, L1–L3 50/60 Hz sine + harmonic distortion (THD 35–45 % at full load) True RMS, ≥ 1 kHz bandwidth
MM440 output, U2/V2/W2 to motor 4 kHz PWM, fundamental = motor slip frequency True RMS, ≥ 40 kHz bandwidth for < 1 % error
DC bus (P0010 = 75, r0026) Filtered DC, low ripple Any clamp meter with DC current capability (Hall sensor)

For trend logging, prefer r0027 (output current) read via PROFIBUS or through the MP170 tag from the PLC. This avoids the bandwidth question entirely and gives the operator a live bar on the panel.

Commissioning Sequence

  1. Mechanical pre-checks: verify coupling alignment, free rotation, gearbox oil level, motor earthing.
  2. Electrical pre-checks: insulation test (1000 V Megger, ≥ 100 MΩ phase-to-phase and phase-to-ground), shield continuity from VFD to motor, PE loop impedance ≤ 0.3 Ω, PROFIBUS termination enabled only at the two physical ends.
  3. MM440 quick commissioning (P0010 = 1): enter motor nameplate data P0304–P0311, P0335, then run P3900 = 1 to compute the motor model from the nameplate.
  4. Motor identification (P1910 = 1): with the motor decoupled from the gearbox, run the static motor ID. This measures the stator resistance, leakage inductance, and dead-time compensation.
  5. PROFIBUS check: from STEP 7 → Accessible Nodes, verify that the MM440 (address 3) and MP170 (address 4) come online. Read P0700 / P1000 and confirm P0700 = 6 (fieldbus command source).
  6. First run on the fieldbus: from the S7 program, write control word 0x047E (off, ready to run), then 0x047F (run, ramp enable) and set the speed setpoint to 10 %. Verify that r0021 (DC bus voltage) is ~540 V DC and r0027 (output current) is ≤ 5 A at no load.
  7. Ramp tuning: set P1120 (ramp-up) and P1121 (ramp-down) to the elevator bucket's safe limit, typically 10–20 s for a 22 kW bucket.
  8. Load test: run the elevator empty, then with a half load, then full load. Record r0027 and the gearbox output speed. Adjust the V/Hz boost (P1310, P1311) if the motor stalls under 50 % load.
  9. Safety chain test: verify that the emergency stop, the overspeed trip, and the motor PTC (if fitted) all stop the drive and assert the STW1 bit 7 (acknowledged fault).

Troubleshooting Matrix

Symptom Likely cause Check Remedy
F0001 (overcurrent) on first run Motor nameplate wrong, or output cable short Megger test, recheck P0304–P0307 Re-enter motor data, repair cable
F0002 (DC bus overvoltage) on deceleration Ramp-down too fast for the load's inertia Watch r0026 during decel Extend P1121, or fit a brake resistor 6SE6400-4BD22-2BA0 (22 kW class)
F0005 (I²t overload) after 5–10 min at 60 Hz Self-cooled motor derating not modeled P0335 value, r0034 (heat sink temp) Set P0335 = 1 and add separate fan, or de-rate output to 45 Hz
PROFIBUS fault light on MM440 Wrong PPO type, or address clash HW Config vs. P0918 Set PPO type 1 in HW Config, set P0918 = 3
Clamp meter reads 30 % below nameplate Average-responding meter on PWM output Meter spec Use True RMS, ≥ 40 kHz BW, or read r0027
Output torque lower than expected at 60 Hz V/Hz not boosted, line is 380 V P0210, r0025 (output V) Either boost line to 460 V or run at 50 Hz full power / 60 Hz reduced load only
MP170 does not appear in WinCC flexible Wrong GSD file, or wrong TP type Configured TP version in catalog Install MP170 V6.0 GSD, restart WinCC flexible

Specifications Summary

Item Value
PLC Siemens 6ES7315-2AG10-0AB0 (CPU 315-2DP, 128 kB work memory, MPI/DP and PtP)
VFD Siemens 6SE6440-2UD34-5FA1 (MICROMASTER 440, 22 kW, 45 A, 400 V, frame size D)
PROFIBUS module 6SE6400-1PB00-0AA0
Motor 22 kW, 400 V Δ, 4-pole, 1460 rpm, FLA 42 A, IE2/IE3 TEFC
Gearbox 28.3:1, 3960 Nm output, 53 rpm @ 50 Hz
Mobile panel Siemens 6AV6 642-0AA11-0AX0 (MP170 Touch 6")
Cable, VFD to motor 4G6 shielded VFD cable, 20 m, e.g., 6FX8002-5DA31-1AF0
Line-side protection 3VA51 63 A C-curve MCCB, or 63 A aR fuses
Output reactor 6SE6400-3TC07-5ED0 (4 mH, 45 A)
PROFIBUS cable 6XV1830-0EH10 (violet, 12 Mbps, double-shielded)
Parameterization SIZER (engineering) + STARTER (commissioning)

FAQ

What happens to my 3960 Nm output torque if I run the 22 kW motor at 60 Hz on 380 V?

The V/Hz ratio drops from 7.6 to 6.33, a 16.7 % reduction. Motor shaft torque falls from 140 Nm to 116.6 Nm, and the gearbox output falls to roughly 3134 Nm. To keep full torque at 60 Hz you must boost the line voltage to 460 V so the V/Hz ratio returns to 7.6.

What size thermal-magnetic breaker should I use in front of a 22 kW MM440?

Use a 63 A C-curve MCCB or 63 A aR fuses. The breaker's job is to protect the VFD input rectifier and the supply cable, not the motor. Motor thermal protection is handled by the MM440 I²t model (P0610).

Do I need a 5-wire cable between the VFD and motor, or a 4-core shielded cable?

Use a 4-core shielded cable (3 phases + PE) such as 2YSLCY-J or 6FX8002-5DA. The VFD does not need a neutral, and a shielded cable is required to keep the common-mode PWM currents from radiating into the installation.

Which software is the easiest to commission the MM440 — STARTER, Drive ES Basic, or SIZER?

STARTER is the most general-purpose tool and includes the trace scope. Drive ES Basic only helps if you are also working in STEP 7. SIZER is for engineering/sizing only and does not edit parameters. For a one-off project install STARTER alone.

Will my clamp meter still read correctly once the VFD is installed?

Only if it is a True-RMS meter with at least 40 kHz bandwidth. A cheap average-responding meter reads 10–30 % low on a PWM waveform. As an alternative, the MM440 exposes r0027 (output current) on the BOP, AOP, or over PROFIBUS — use that reading in the PLC program and on the MP170 trend.

Back to blog