S7-400: Configuring Four PLCs in WinCC Flexible via Ethernet

David Krause11 min read
HMI / SCADASiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Architecture Overview

When four SIMATIC S7-400 CPUs must be visualized from a single engineering notebook or operator terminal, the HMI software must hold four simultaneous S7 connections and expose each PLC's data areas as discrete tag namespaces. The two Siemens-native runtime paths are WinCC flexible PC Runtime (legacy) and TIA Portal WinCC RT Professional / WinCC Unified PC RT (current). Both operate as a TCP/IP client that opens ISO-on-TCP (RFC 1006) sessions against CP 443-1 modules mounted in the S7-400 racks.

The most important architectural decision is whether the four PLCs share a single Ethernet subnet or sit on separate subnets. WinCC flexible PC Runtime uses the Windows TCP/IP stack and depends on the S7ONLINE access point for transport; it cannot bridge subnets without an IP router or Layer-3 switch, so the four PLCs must be reachable through a default route. If the production line is segmented, configure static routes or use the S7 routing capability of the CP 443-1.

Prerequisites

Before configuring the runtime, verify the following items.

Item Required Value / Version Notes
WinCC flexible 2008 SP5 HF17 or later Final maintenance release; required for S7-400 firmware ≥ V5.5
Microsoft Windows Windows 7 SP1 / Windows 10 (x64) WinCC flexible 2008 SP5 is 32-bit; runs on x64 via WOW64
SIMATIC S7-400 CPU CPU 412-x, 414-x, 416-x, 417-x, 41xH All current S7-400 CPUs support S7 communication
CP 443-1 Ethernet module 6GK7 443-1EX30-0XE0 (V3) or 6GK7 443-1EX50-0XE0 (V6) Required for ISO-on-TCP; classic S7-400 has no onboard PROFINET
STEP 7 V5.5 + SP4 / HF10 Project editor for S7-400 Needed to download connection configuration to the CP
Ethernet infrastructure 10/100 Mbit managed switch QoS not required; broadcast isolation recommended
IP addresses 4 × S7-400 + 1 × Runtime PC, same subnet Static assignment recommended for plant floor

For current-generation projects, replace WinCC flexible with TIA Portal WinCC V17 / V18 / V19 and use the S7-400 as a "HMI-device capable" partner. WinCC flexible was discontinued by Siemens in 2017 (last public release 2008 SP5 HF17) and remains functional but receives no further patches.

Connection Capacity of WinCC Flexible PC Runtime

WinCC flexible PC Runtime stores its connection limits in the registry under HKLM\SOFTWARE\Siemens\Automation\WinCC flexible\RT\Connections. The maximum number of simultaneously active controller connections is controlled by the MaxConnections value.

Runtime Default Limit Maximum (registry edit) S7 Connections Supported
WinCC flexible 2008 SP5 PC Runtime 8 16 Yes (ISO-on-TCP)
WinCC flexible 2008 Panel RT (e.g. MP 277) 4 16 Yes
WinCC flexible 2004 PC Runtime 4 8 Yes
TIA Portal WinCC RT Professional 128 (configurable) 128 Yes (S7 / OPC UA)
TIA Portal WinCC Unified PC RT 128 128 Yes (S7 / OPC UA)

For four S7-400 PLCs, the default limit (8) is more than sufficient. The limit matters when the same runtime also connects to a third-party device (e.g. a Modbus TCP meter) or to additional HMI stations. If the registry value is exceeded, WinCC flexible logs event 1000202 "Connection not established, maximum number of connections reached" in the Windows event log.

Registry edit caution: Always export the Connections key before modifying. The change does not survive a WinCC flexible reinstall without re-applying.

S7-400 Ethernet Hardware Configuration

Each S7-400 must be equipped with at least one CP 443-1. Insert the CP in the rack (slot 1–4 depending on the power supply configuration), assign an IP address, and enable the S7 protocol with the "S7 communication" checkbox. The CP 443-1 maintains a connection table; WinCC flexible Runtime initiates S7 connections as a PG/PC-type connection, and the CP allows up to 64 S7 connections on the EX30/EX50 modules. Four HMI connections therefore consume 4 of 64 resources, leaving headroom for STEP 7 online, other HMIs, and S7 routing.

STEP 7 V5.5 Hardware Configuration (per PLC)

  1. Open the S7 project in STEP 7 V5.5.
  2. In HW Config, drag the CP 443-1 (e.g. 6GK7 443-1EX30-0XE0) into the rack.
  3. Double-click the CP and assign:
    • IP address: e.g. 192.168.10.41 (PLC 1), 192.168.10.42 (PLC 2), 192.168.10.43 (PLC 3), 192.168.10.44 (PLC 4)
    • Subnet mask: 255.255.255.0
    • Router address: (blank for single subnet)
  4. Under Properties → Interface → S7 Communication, ensure the option is active.
  5. Download the hardware configuration to the PLC.
  6. Test the CP from the engineering station: ping 192.168.10.41. A reply confirms the L2 stack is alive.

Network Topology and Performance

On a single 100 Mbit switch, ISO-on-TCP (RFC 1006) overhead is roughly 20 % of payload. Each S7 poll cycle is typically 2–4 packets (request + ack + ack-data + ack). With four PLCs at 1 s acquisition, bandwidth use is below 0.5 % of the 100 Mbit capacity. Latency budget per PLC: < 10 ms.

WinCC Flexible PC Runtime — Four S7-400 Topology Runtime PC 192.168.10.50 100 Mbit Switch PLC 1 (.41) PLC 2 (.42) PLC 3 (.43) PLC 4 (.44)

If the four PLCs are on separate VLANs/subnets, configure the CP 443-1's S7 routing capability: enable "S7 routing" in the CP properties, then in STEP 7 NetPro → S7 Connection → Properties → Gateway add the IP router. Verify with tracert 192.168.10.41 from the runtime PC.

Configuring WinCC Flexible Connections

In the WinCC flexible project, open Project → Connections and add four S7-400 connections.

Connection Name PLC Partner IP Address Access Point Connection Type TSAP Local / Remote
PLC_LINE1 S7-400 #1 192.168.10.41 S7ONLINE ISO-on-TCP 01.01 / 01.01
PLC_LINE2 S7-400 #2 192.168.10.42 S7ONLINE ISO-on-TCP 01.01 / 01.01
PLC_LINE3 S7-400 #3 192.168.10.43 S7ONLINE ISO-on-TCP 01.01 / 01.01
PLC_LINE4 S7-400 #4 192.168.10.44 S7ONLINE ISO-on-TCP 01.01 / 01.01

TSAP (Transport Service Access Point) on the S7-400 defaults to 01.01; the WinCC flexible Runtime side defaults to 01.01 as well. If the CP has been configured with a non-default TSAP, match it exactly — mismatched TSAPs are the most common cause of "Connection not established" alarms at startup.

For each connection:

  1. Set Communication Driver = "SIMATIC S7 300/400".
  2. Set PLC Address = IP address above.
  3. Set Expansion Slot = rack/slot of the CPU (e.g. 0/3 for slot 3 in rack 0).
  4. Set Connection Type = ISO-on-TCP (Port 102).
  5. Leave Activate connection when starting Runtime = "Yes" so WinCC flexible cycles the connection in case of failure.
Set PG/PC interface: On the runtime PC, open Start → Control Panel → Set PG/PC Interface and select S7ONLINE (STEP 7) → TCP/IP (Auto) as the access point. Do not select "ISO" — the ISO protocol is for MPI/profibus; Ethernet uses TCP/IP.

Change Connection Function

WinCC flexible exposes a system function ChangeConnection that lets the operator switch the runtime's active connection from the HMI. This is useful when the four PLCs perform identical operations on parallel lines and the operator wants to monitor only one line at a time.

Pattern A — All four connections always active (recommended)

Leave the four connections configured as always active. WinCC flexible Runtime maintains ISO-on-TCP sessions with all four PLCs simultaneously and updates tags from each. Tags are namespaced by connection name (e.g. PLC_LINE1\DB10.DBX0.0). Refresh cycles are configured per connection; default is 1 s. With four active connections, expect a CPU load of roughly 3–5 % on a Core i5 / 8 GB notebook.

Pattern B — Switch using ChangeConnection

Use a screen with four buttons, each calling the system function in the click event:

// WinCC flexible ST script (button click)
ChangeConnection("PLC_LINE1");

The function switches the runtime's current connection for the selected screen object. Note that all configured tags remain — only the displayed faceplate is re-bound. To truly free a connection for another device, use the Connect / Disconnect system functions.

Tag and Variable Configuration

Tags must be created under the connection they belong to. WinCC flexible does not aggregate tags from multiple connections into a single namespace.

Tag Name PLC Connection Data Block Address Type Acquisition Cycle
LINE1_Motor_Run PLC_LINE1 DB10 DBX 0.0 Bool 500 ms
LINE1_Temp PLC_LINE1 DB10 DBD 4 Real 1 s
LINE2_Motor_Run PLC_LINE2 DB10 DBX 0.0 Bool 500 ms
LINE3_Temp PLC_LINE3 DB10 DBD 4 Real 1 s
LINE4_Speed_SP PLC_LINE4 DB20 DBD 12 Real 1 s

Naming convention: prefix every tag with the line identifier (LINE1_, LINE2_ …) to avoid collisions when porting screens.

Verification and Commissioning

  1. Compile the project: Project → Compiler → Check Consistency. No warnings should reference missing connections.
  2. Start Runtime in simulation: Project → Start Runtime. Open the Diagnosis window (View → Diagnosis) and verify four green connection icons.
  3. Read a known tag: Insert an I/O field bound to PLC_LINE1\DB10.DBW0 and toggle the value in the PLC (VAT). Confirm the field updates within one acquisition cycle.
  4. Force a connection drop: Disconnect the Ethernet cable from PLC 3. WinCC flexible logs Event 14001 / 14002 ("Connection interrupted"). Reconnect and verify automatic re-establishment within 30 s.
  5. Check CP connection resources: In STEP 7, CP 443-1 → Diagnostics → Connections. Confirm four "PG/PC" entries from the runtime IP.
  6. Stress test: Set all acquisition cycles to 100 ms. Runtime CPU should remain below 15 % on a modern dual-core. If higher, raise the lowest-priority cycle to 500 ms.

Troubleshooting Matrix

Symptom Likely Cause Diagnostic Action Resolution
One PLC shows "Connection not established" Wrong TSAP, wrong slot, CP S7 comm disabled ping then check CP properties Match TSAP 01.01; re-download HW Config
All four fail after WinCC flexible reinstall MaxConnections reset to default 8 Regedit → check MaxConnections Re-apply registry value, restart Runtime
Tags show "#INVALID" DB not loaded on CPU or wrong DB number STEP 7 Monitor/Modify on DB Recompile DB in PLC and download
Runtime starts but CPU usage > 30 % Acquisition cycle too short on many tags Task Manager → Runtime process Raise minimum cycle to 500 ms
Connection drops every ~60 s CP keep-alive mismatch CP → Properties → Keep-Alive Enable keep-alive; matching timeout on CP
Event 1000202 in Windows log Connection limit exceeded Count active connections in WinCC Diagnosis Reduce concurrent connections or raise limit

Alternative HMI / SCADA Platforms

Platform Vendor Max S7 Connections License Model Notes
WinCC V7.5 / V8.0 Siemens Server: 256 / Client: 128 Tag-based (16, 256, 8K, 64K) Preferred for large plants; supports redundant servers
TIA Portal WinCC Professional V19 Siemens 128 HMI connections RC 1024 / RC 8192 tags Modern engineering, Unified namespace, OPC UA optional
WinCC Unified PC RT V19 Siemens 128 Tag-based Web-based panels, multi-user
ABB CP600 series ABB Up to 8 (CP6605/CP676) Per device S7 driver requires S7-300/400 protocol license; see ABB CP600 platform
IDEC HG2J / HG3J all-in-one IDEC 4 PLC tags max (FC6A series) Built-in PLC + HMI See IDEC IHM+PLC integrated HMI+PLC; alternative only if PLC brand is mixed

For an existing four-PLC S7-400 line, sticking with Siemens WinCC (either flexible PC Runtime for retrofits or TIA Portal WinCC for new projects) avoids driver licensing and engineering overhead. Third-party panels from ABB or IDEC only become attractive when one of the four PLCs must be replaced with a non-Siemens controller.

Migration Path: From WinCC Flexible to TIA Portal

For new projects or plants upgrading from Windows 7 / 8 to Windows 10 / 11, migrate the WinCC flexible project to TIA Portal WinCC. The migration is straightforward because the S7 driver is binary-compatible at the wire level.

  1. Install TIA Portal V18 or V19 with the WinCC Professional option.
  2. Open the existing STEP 7 V5.5 project; TIA Portal's migrator ("Project → Migrate to TIA Portal") converts it to a TIA project.
  3. Add a new HMI device: HMI → PC-System → WinCC RT Professional.
  4. In the HMI's Connections editor, add the same four S7-400 partners. TIA Portal pre-fills IP addresses from the migrated PLC configuration.
  5. Transfer tags from the WinCC flexible tag database using the OPC import wizard or the WinCC flexible converter ("WinCC flexible → WinCC" migration tool).
  6. Compile and start RT Professional; verify the four connections in the runtime Diagnosis view.
Migration caveat: Custom scripts written in WinCC flexible's VBScript or ANSI-C must be re-written in TIA Portal's VB or C-script environment — no automatic translation exists. Plan a 10–15 % engineering effort for script conversion.

FAQ

How many S7-400 PLCs can WinCC flexible PC Runtime connect to simultaneously?

Eight by default and up to sixteen after editing the registry key HKLM\SOFTWARE\Siemens\Automation\WinCC flexible\RT\Connections\MaxConnections. Four PLCs is well within the default limit and requires no registry change.

Does WinCC flexible need a special license for each connection?

No. WinCC flexible PC Runtime is licensed per installation and includes unlimited S7-300/400 connections within the configured connection limit. Third-party drivers (e.g. Modbus TCP, OPC) require additional licenses.

What is the difference between ISO-on-TCP and TCP/IP connections in WinCC flexible?

ISO-on-TCP (RFC 1006) uses port 102 and is the standard S7 transport over Ethernet. Plain TCP/IP is used for non-Siemens devices. For S7-400, always select ISO-on-TCP; the CP 443-1 expects port 102 traffic.

Why does the runtime show "Connection not established" for one PLC while the others work?

Most common causes are mismatched TSAP, CP 443-1 S7 communication disabled, wrong expansion slot, or a duplicate IP address on the network. Run ping from the runtime PC to the failing PLC, then verify the TSAP in Project → Connections → Properties matches the CP configuration (default 01.01).

Is WinCC flexible still supported for new S7-400 projects in 2024?

WinCC flexible was discontinued by Siemens in 2017 (last release 2008 SP5 HF17). New projects should use TIA Portal WinCC V18 / V19 with the S7-400 added as a partner; the S7 driver is identical at runtime, but engineering and licensing are managed through TIA Portal.

Can I reuse my existing CP 443-1 when migrating to TIA Portal?

Yes. The CP 443-1 (6GK7 443-1EX30-0XE0 / 6GK7 443-1EX50-0XE0) is fully compatible with TIA Portal WinCC and requires no firmware change. The IP address and TSAP configuration are imported from the migrated STEP 7 project.

Back to blog