S7 Routing to SINAMICS S120 via IBHnet MPI: Configuration

David Krause16 min read
Industrial NetworkingSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

S7 Routing to SINAMICS S120 and G120 via IBH S7++ Link over MPI/PROFIBUS

This reference documents the end-to-end procedure to bring an engineering station online with SINAMICS S120 and SINAMICS G120 drive objects that sit on the PROFIBUS DP port of a SIMATIC S7-400 CPU, when the engineering PC is connected to the S7-400 MPI/DP interface through an IBH S7++ Link adapter. The technique is also valid for SIMOTION D4x5 controllers that share the same bus architecture. The single most important prerequisite is a fully compiled and downloaded PG/PC station in NetPro with the S7 routing tables embedded in the SDB container of the S7-400.

Key principle: S7 routing is a function of the S7-400 CPU (or S7-300 with routing-enabled firmware), not of STARTER, SCOUT, or the IBH adapter. If the routing SDBs are not present in the target CPU, the adapter will happily surface the S7-400 in "Accessible Nodes" but the drives behind the PROFIBUS interface will never appear, and any STARTER/Scout online attempt will fail with a routing error.

1. Topology Overview

The reference architecture has three logical S7 subnets joined by the S7-400 CPU acting as router:

  • Subnet 1 - MPI (engineering station ↔ CPU MPI/DP port 1). The PC connects to this subnet through the IBH S7++ Link adapter on its MPI/PPI channel.
  • Subnet 2 - PROFIBUS DP (CPU MPI/DP port 2 ↔ SINAMICS S120 CU320/CU310, SINAMICS G120 with CU240/CU250 control unit, SIMOTION D4x5). All drive objects are DP slaves on this segment.
  • Optional Subnet 3 - PROFINET/Ethernet (CPU PN/IE port ↔ additional drives or HMI). The same routing rules apply across the PN/IE interface.
Engineering PC STARTER / Scout PG/PC station S7-400 CPU 412-2 / 414-2 / 416-2 MPI/DP port 1 DP/PROFINET port 2 SDB routing table SINAMICS S120 CU320 / CU310 PROFIBUS slave SINAMICS G120 CU240S/E PN-F PROFIBUS slave MPI / IBH S7++ PROFIBUS DP PROFIBUS DP

2. Prerequisites

Component Minimum Version Notes
STEP 7 (SIMATIC Manager) V5.5 + SP2 (or V5.6) Contains NetPro for PG/PC station assignment
STEP 7 (TIA Portal) V15.1 or later Alternative to classic STEP 7; routing tables are built automatically
STARTER V5.4 HF2 or later Commissioning tool for SINAMICS S/G drives
SCOUT / Scout TIA V5.4 or TIA V15.1+ For SIMOTION D4x5 commissioning
IBH S7++ Link adapter Firmware ≥ 1.50 Configure for MPI, 187.5 kbps, station address 0 (PC side)
IBHNet S7 driver Current Set PG/PC interface to "IBHNet MPI"
SINAMICS Support Packages (SSP) Match drive FW Install SSP for S120 V5.x and G120 V4.x used in cabinet
S7-400 CPU firmware V5.3 or later recommended Required for routing across multiple subnets

Verify in the Control Panel "Set PG/PC Interface" applet that the access point S7ONLINE is bound to IBHNet MPI. This binding is what the IBH driver and the S7 routing SDBs both look at.

Note on driver ordering: When multiple S7 adapters are installed (for example IBHnet and Softnet), the active binding is the last one set. Re-confirm the assignment in Control Panel → Set PG/PC Interface after installing new tools. Tools such as TIA Portal, STARTER, and Scout each maintain their own access-point configuration that can override the global setting.

3. S7 Routing Concept and Limitations

S7 routing is the transfer of online-services telegrams beyond the boundary of a single S7 subnet. A telegram is received on the engineering interface of the gateway CPU and re-emitted on a second interface; the CPU acts as a router. Routing is supported on the following SIMATIC CPUs as gateways:

  • All S7-400 CPUs (PN/DP and DP variants)
  • S7-300 CPUs with PN/DP or DP/DP interface and firmware that supports routing (for example CPU 319-3 PN/DP, CPU 315-2 PN/DP)
  • ET 200S / ET 200pro IM with PN/DP interface and routing-capable firmware
  • WinAC RTX and PC-based controllers

Per the Siemens functional manual on S7 routing, the gateway CPU must be configured as a routing node; this configuration is generated by NetPro or by the device configuration in TIA Portal and downloaded to the CPU as part of the System Data Blocks (SDB container, SDB 0 and SDB 999). If the SDBs are missing, the CPU can still execute the user program but the online-services layer has no routing table to consult.

Important constraints:

  • Topology must be known to the project. The drive GSD files must be present in the STEP 7 hardware catalog. Without the GSD, the DP slave cannot be a destination of a route and STARTER/Scout will not enumerate the device under "Accessible Nodes".
  • Accessible Nodes shows direct neighbors only. The PG/PC station on the MPI subnet sees the S7-400. Drives behind PROFIBUS are reachable only when STARTER/Scout is launched and a STARTER/Scout project is opened with the same topology and the same S7 routing path.
  • Routing respects broadcast domains. A drive connected via a non-Siemens DP/DP coupler that does not pass S7 routing telegrams will be invisible.

4. STEP 7 Hardware Configuration

Build the project in the SIMATIC Manager with a PC station that represents the engineering workstation. The PC station is required even when the project is empty, because NetPro uses it to construct the routing SDBs.

  1. Open SIMATIC Manager and create a new project.
  2. Insert a SIMATIC 400 Station and assign the exact order number (MLFB) of the target CPU, for example 6ES7412-2EK06-0AB0 (CPU 412-2 PN) or 6ES7416-3ES06-0AB0 (CPU 416-3 PN/DP).
  3. Insert a SIMATIC PC Station into the project.
  4. Open HW Config on the PC Station and insert an IE General or CP 5611 / CP 5612 or, in the case of an IBH S7++ Link with MPI only, the Application station with the IBH S7 Softnet entry. For pure MPI routing the typical approach is the IE General placeholder bound to the IBH driver.
  5. Open HW Config on the S7-400 Station. Add both interface subnets:
    • On port 1 (MPI/DP) set the interface mode to MPI, transmission rate 187.5 kbps, station address 2 (typical).
    • On port 2 (DP or PN) configure the PROFIBUS or PROFINET subnet and add the SINAMICS drives from the catalog using their GSD files.
  6. For each drive, set the PROFIBUS address to match the hardware (typical values 4…15 for SINAMICS S120, 4…8 for G120).
If the drive firmware on the cabinet does not match any SSP installed on the PC, HW Config still places a generic DP slave slot, but STARTER/Scout will not be able to upload the drive. Install the matching SSP first - see Section 6.

5. PG/PC Station Assignment in NetPro

The PG/PC station in NetPro is what generates the routing SDBs that the gateway CPU needs. Without this step, "Accessible Nodes" will only ever list the S7-400 - never the drives.

  1. Open NetPro on the PC station.
  2. Right-click the PC station interface and choose Assign Interface if not already assigned.
  3. Select the application IBHNet S7 (or IBH S7 Softnet) as the application on the interface.
  4. Right-click the PC station interface and choose Assign Station to PG/PC. This is the critical step - it binds the PC station to the PG/PC role so that the S7 routing SDBs are built for the engineering role.
  5. Verify that the PC station shows the same MPI subnet as the S7-400 and that the PC has a unique MPI address (default 0) on the same subnet.
  6. Save and compile NetPro (Network → Save and Compile or F7).
  7. Download the System Data to the S7-400. The download is a single action: PLC → Download to Target Station on the S7-400 CPU. The CPU must be in STOP or RUN-P, depending on what blocks are being downloaded.

After the SDBs are downloaded, the routing tables inside the S7-400 carry the following information:

  • Engineering interface subnet (MPI)
  • Destination interface subnet (PROFIBUS DP)
  • Final-step DP slave address and slot
If the SDB download reports a routing error such as "0x0302 - The gateway CPU does not have a routing entry" in the diagnostic buffer, the SDBs have not been re-compiled after a topology change. Recompile NetPro (F7) and re-download System Data to the CPU.

6. Installing SINAMICS Support Packages (SSP)

STARTER and Scout can only create online connections to drive objects whose device type is known to the engineering software. The device knowledge is delivered as Support Packages (SSP):

SSP Catalog Path Adds Support For
SSP SINAMICS S120 SIMATIC Manager → Options → Support Packages → Install SINAMICS S120 V4.x / V5.x with CU320, CU310, CU320-2, CU310-2
SSP SINAMICS G120 same path SINAMICS G120 V4.x with CU240S, CU240E, CU250S, G120C
SSP STARTER required base STARTER commissioning tool itself
SSP SIMOTION if D4x5 present SIMOTION D410, D425, D435, D445, D445-1, D455

To install an SSP:

  1. Download the matching SSP from the Siemens Industry Online Support portal product page for SINAMICS S120 / G120.
  2. Close all running SIMATIC tools.
  3. From the SIMATIC Manager main menu choose Options → Support Packages → Install.
  4. Browse to the unpacked SSP folder and select the .spp file (for example SSP_SINAMICS_S120_V5_4_SP3_HeifPackage_2018xx.zip).
  5. Restart STEP 7. The new SINAMICS device versions appear in the HW Config catalog and in the STARTER/Scout device catalog.
Field tip: Verify the drive firmware version by going online to the S7-400 first, opening Accessible Nodes with PG/PC interface set to IBHNet MPI, then connecting STARTER directly through the IBH adapter to one drive via its own DP address (where physical access permits). The firmware version is shown in the STARTER online dialog. Match the SSP version to that number. Mismatches manifest as "Device type Vx.y SPz unknown" in STARTER.

7. Going Online Through S7 Routing from STARTER/Scout

Once the SDBs are downloaded and the SSPs are installed, the S7 routing path is operational. Two methods are commonly used.

7.1 Method A - From the STEP 7 Hardware Project

  1. Open the STEP 7 project containing the S7-400 and the configured drive objects.
  2. Open HW Config and select the S7-400 CPU.
  3. Press PLC → Online to establish the connection. The CPU must be reachable on the MPI subnet through the IBH adapter.
  4. Right-click the drive in the project tree and choose Target Device → Online Access (or Download / Upload to Target Device in TIA Portal terminology). STARTER opens in a child window with the topology pre-filled from the STEP 7 project.
  5. STARTER then performs a routing connection to the SINAMICS drive. Status messages show the gateway hops, for example IBHNet MPI → CPU412 port 1 (MPI) → CPU412 port 2 (DP) → S120 CU320 address 4.

7.2 Method B - From STARTER with Routing-Enabled Access Point

  1. Open STARTER. Set the access point to S7ONLINE with target interface IBHNet MPI.
  2. Open or create a STARTER project. Add the gateway CPU under Insert → SINAMICS_Integrated / S7 routing and enter the destination PROFIBUS address of the drive.
  3. Set the access point of the device to DEVICE (ROUTING) and the device address to the destination DP address.
  4. Press Connect to Target System (the plug icon). STARTER builds the routing SDBs on the fly and connects.

8. Uploading a Drive Without It Appearing in Accessible Nodes

Accessible Nodes on the MPI subnet will never list the SINAMICS drives; only the S7-400 is visible. To upload the drive to the PG, follow this sequence.

  1. Open the STEP 7 project in the SIMATIC Manager.
  2. Open HW Config on the S7-400 station. The drive slots must be present, and the drive GSD must be the same version family as the drive firmware on the cabinet (or the device type is Unknown, in which case install the matching SSP first).
  3. Confirm the PG/PC station is online with the S7-400. The PG/PC must have a node address of its own on the MPI subnet (typically 0) and the SDBs must have been downloaded to the CPU in the previous step.
  4. Right-click the drive object in the project and choose Target Device → Online → Upload to PG/PC. STARTER retrieves the drive parameters via S7 routing. If the drive is a SIMOTION D4x5, the upload may require the additional "target data" that was stored on the device at last download; without it, an upload is not possible.
  5. For SIMOTION: ensure the engineering data is on the CF card. Otherwise, only the online snapshot of the device is available; an offline project is not produced.
Empty project / unknown topology: To upload an empty project (no STEP 7 hardware configuration that matches the cabinet) the PG/PC station still needs an entry in NetPro. Add the PC station with an MPI application bound to the IBH driver, and add a SIMATIC 400 Station with the order number of the gateway CPU. The drive slots can be left empty; STARTER can perform a topology discovery through the CPU's PROFIBUS interface when the routing SDBs are present.

9. Verification Checklist

Run the following checks before declaring the S7 routing path operational.

# Check Pass Criterion
1 PG/PC interface access point S7ONLINE → IBHNet MPI
2 PC station in NetPro PC station assigned to PG/PC role, MPI interface, S7-Online application
3 S7-400 SDBs Compiled and downloaded; routing SDB 999 present in CPU
4 Drive GSD / SSP Drive device type appears in catalog with the same version family as the cabinet
5 Accessible Nodes S7-400 visible on MPI subnet with correct order number
6 Routing test from STARTER Connection to drive established; online parameters update in < 5 s
7 Diagnostic buffer of S7-400 No "0x0302 routing data invalid" or "0x0311 connection aborted" entries

10. Diagnostic Buffer and Common Error Codes

The S7-400 diagnostic buffer reports routing problems in clear text. The most common events observed in this configuration:

Event ID (hex) Meaning Likely Cause Remedy
0x0302 Routing data invalid SDB not downloaded or project topology changed without recompile NetPro → Save+Compile → Download System Data to S7-400
0x0305 Address of the final hop unknown Drive not in HW Config or wrong DP address Re-check DP address and slot in HW Config
0x0311 Connection aborted Timeout across the IBH adapter, or PROFIBUS fault Check MPI baud rate, IBH firmware, bus termination on DP segment
0x0231 Subnet fault on DP DP slave missing or address duplicate Use SFC 13 / DP diagnostics to identify the slave
0xA090 STARTER: device type unknown SSP for drive firmware not installed Install matching SSP; restart STEP 7 and STARTER

11. Troubleshooting Matrix

Symptom Most Likely Cause Action
CPU appears in Accessible Nodes, drives do not Routing SDBs not present in CPU Compile NetPro with PC station assigned, download System Data to S7-400
Accessible Nodes shows CPU as "Unknown" CPU order number does not match project Update HW Config to exact MLFB of the cabinet CPU
Accessible Nodes shows CPU, then disconnects after 5 s MPI baud rate mismatch Set PC station interface to 187.5 kbps; confirm CPU MPI port speed in HW Config
STARTER reports "Device Vx.y SPz unknown" SSP missing or wrong version Install SSP that matches the firmware version printed on the CU parameter page
STARTER shows topology but upload fails SDBs on CPU do not yet include the drive Add the drive to HW Config on the S7-400, recompile, re-download System Data
Routing works for S120, not for G120 G120 GSD file not loaded into STEP 7 Install GSD file from Siemens support and re-import into HW Config
Upload of SIMOTION D4x5 returns blank project Engineering data not stored on the device Re-download the project to the D4x5 once; upload is then possible
Routing timeouts under high DP load Online services are acyclic, but DP cycle is too short Increase DP cycle time on the S7-400 from 1.5 ms to 3 ms minimum when commissioning

12. Special Cases

12.1 S7-400 with Both MPI and PROFIBUS on the Same Physical Port

Some S7-400 CPUs have one combined MPI/DP port. Configure the port as MPI in HW Config; routing across the same physical port to a DP subnet is not possible. Use the second port for PROFIBUS. If the CPU has only one port, an external DP/DP coupler is required, but S7 routing does not pass through non-Siemens couplers in all firmware releases.

12.2 Mixing MPI at 19.2 kbps and PROFIBUS at 1.5 Mbps

Set the IBH S7++ Link to the same baud rate as the S7-400 MPI port. Mismatched rates produce intermittent timeouts. Use the IBHNet Configuration Tool to flash the adapter to 187.5 kbps for typical S7-400 MPI ports; some older plants run 19.2 kbps and require the adapter to be set accordingly.

12.3 Routing Through a CP 443-1 PN

When the S7-400 reaches PROFINET drives through a CP 443-1, the CP firmware must support routing. CP 443-1 EX30 and later support routing transparently. The PC station in NetPro must have an IE interface bound to the same PROFINET subnet; the SDBs are still produced by the S7-400, not by the CP.

12.4 S7 Routing Across PROFINET to G120 with PN Control Unit

For G120 with CU240E PN, the routing path is IBHNet MPI → CPU port 1 (MPI) → CPU port 2 (PN) → G120 PN. The S7-400 SDBs include the PROFINET name and IP of the G120. STARTER then connects across the PROFINET interface. The procedure is otherwise identical to the PROFIBUS case.

13. Reference Documentation

Why do I see the S7-400 in Accessible Nodes but not the SINAMICS drives behind PROFIBUS?

Accessible Nodes only enumerates devices on the local S7 subnet, which is the MPI segment between the IBH S7++ Link adapter and the S7-400 MPI port. The drives are on a separate PROFIBUS subnet and can only be reached through S7 routing. Download the PG/PC station System Data (SDBs) to the S7-400 after a NetPro compile; the CPU then carries the routing table for the PROFIBUS drives.

Do I need a PG/PC station in NetPro to route through the S7-400?

Yes. The PG/PC station must be inserted into the STEP 7 project, the IBHNet S7 application must be bound to its MPI interface, and the System Data must be compiled and downloaded to the S7-400. Without the PC station, the SDBs do not contain routing entries, and STARTER/Scout cannot open a connection to drives on the PROFIBUS segment.

Which order numbers of the S7-400 support S7 routing?

All S7-400 CPUs (6ES7412-..., 6ES7414-..., 6ES7416-..., 6ES7417-...) support S7 routing on the integrated interfaces when running firmware V5.3 or later. The routing is performed by the CPU firmware independent of the user program and does not require a special hardware variant.

What is the minimum STARTER version for routing to SINAMICS S120 V5.x?

STARTER V5.4 HF2 or later, combined with the SSP for SINAMICS S120 V5.x. For V5.2 SP3 and later, install the matching SSP delivered by Siemens Industry Online Support. Mismatched SSP and firmware versions lead to the "device Vx.y SPz unknown" message in STARTER.

Can I upload a SIMOTION D4x5 through the S7-400 routing path?

Yes, but only if the engineering data was stored on the target the last time the project was downloaded. The S7-400 transparently routes the upload telegrams to the SIMOTION PROFINET/PROFIBUS interface. If the engineering data is missing, the upload returns an empty project; the project must be downloaded once and the data must remain on the device for future uploads to succeed.

Back to blog