Selecting MM440 Output Chokes and Sine Filters for Long Motor

David Krause16 min read
Application NoteSiemensVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview: 37 kW MM440 Feeding a 30 kW Motor Over 550 m

A common field application pits a Siemens MICROMASTER 440 (MM440) inverter against a long motor feeder that the original commissioning base never intended to support. In the typical case under review here, the drive is rated 37 kW, the motor is rated 30 kW, 415 V, 3-phase, 50 Hz, 53 A, and the connecting feeder is a 3C x 185 sq.mm XLPE aluminum cable running 550 m between the inverter output terminals and the motor junction box.

Three independent electrical phenomena appear at this length and must be addressed before the drive is started:

  1. Reflected-wave voltage doubling at the motor terminals caused by impedance mismatch between the cable surge impedance and the motor surge impedance.
  2. Capacitive charge/discharge currents in the long cable-to-ground capacitance, which add to the inverter's switching current and trip IGBT protection.
  3. Voltage drop along the aluminum conductor, which reduces the voltage seen at the motor terminals and degrades torque.

The MM440 catalog and operating instructions quote a maximum permissible 300 m of shielded motor cable when the drive is fitted with an output choke or LC sinusoidal filter. The 550 m feeder in this scenario exceeds that tested limit by roughly 83%, so the engineer must either re-rate the cable run as a special case, derate the drive, or accept the use of mitigation hardware that Siemens explicitly lists as "untested" beyond the published figure.

Reflected Voltage Physics on Long Motor Cables

Modern IGBT inverters such as the MM440 switch the DC bus at rise rates that can exceed 5 kV/μs with a pulse frequency (parameter P1800) typically set between 2 kHz and 16 kHz. The PWM edge propagates down the feeder as a travelling wave at roughly half the speed of light. When that wave reaches the motor terminals it encounters the high-frequency surge impedance of the motor windings, which is typically 1,000–2,000 Ω, while the cable surge impedance is typically 30–100 Ω depending on conductor geometry and dielectric.

The reflection coefficient at the motor end is:

Γ = (Zcable − Zmotor) / (Zcable + Zmotor)

For a typical XLPE cable with Zcable ≈ 50 Ω and Zmotor ≈ 1,500 Ω, Γ ≈ −0.94, meaning the reflected wave arrives with the opposite polarity and a magnitude approaching the incident wave. The peak line-to-line voltage at the motor can reach 1.5 to 2.0 times the DC bus voltage, which on a 415 V drive corresponds to peak line-to-line transients in the region of 1,000–1,200 V. The catalog figure cited for the MM440 is approximately 1.5 kV peak phase-to-phase.

Standard induction motors with random-wound windings are typically rated to withstand peaks of 1,000–1,500 V and dV/dt of 1 kV/μs before insulation life is materially reduced. Sustained operation above these limits accelerates turn-to-turn insulation breakdown, particularly on motors that were not built to NEMA MG1 Part 31 inverter-duty specification.

MM440 Cable Length Limits and Output Devices

The MM440 catalog partitions the permitted motor cable length into three regions based on the output device fitted between the inverter and the cable:

Output Device Permissible Motor Cable Length (shielded) Function
None (direct connection) 50 m typical, 100 m maximum depending on PWM frequency No mitigation; relies on cable and motor impedance matching.
Output choke (e.g. 6SE6400-3TC07-5ED0) Up to 300 m Limits dV/dt and capacitive charging current by adding inductance in series with each phase.
LC sinusoidal filter (sine filter) Up to 300 m Reconstructs an approximate sinusoidal line-to-line voltage at the motor, eliminating reflection events.

The published limit for shielded cable with output choke or sine filter is 300 m for the MM440 frame size appropriate to a 37 kW drive. Anything beyond that is not tested by Siemens and the engineer accepts the risk. The 550 m run in this application is therefore in the "untested" envelope, and the practical mitigation strategy is to combine the available hardware with drive derating, an additional output choke in series, and a reduced pulse frequency.

Output Choke Selection on the MM440

The Siemens accessory line for the MM440 includes the output choke 6SE6400-3TC07-5ED0, which is the part number referenced in the field correspondence for this drive family. Output chokes are three-phase iron-core inductors fitted in the inverter output compartment or in a separate cabinet, with the following electrical role:

  • Increase the effective inductance between the IGBT and the cable capacitance.
  • Reduce the dV/dt presented to the motor to roughly 500 V/μs from the 5–10 kV/μs of the unfiltered IGBT edge.
  • Limit the peak charging current of the cable capacitance each switching event.

When using the 6SE6400-3TC07-5ED0 with a 400 V supply, Siemens documents that the shielded cable length can be extended to 300 m. Beyond that figure the choke alone is insufficient, and the field practice is to insert a second identical output choke in series on each phase. Two chokes in series give roughly twice the inductance, halving the dV/dt again and extending the practical reach to between 400 m and 600 m, depending on the cable characteristics and the pulse frequency.

Field Note: Series-stacking two output chokes is not documented in the Siemens MM440 operating instructions as an approved configuration. It is a known field practice and has been used successfully, but it is the integrator's responsibility to verify current rating, mechanical mounting, thermal rise, and EMC behavior in the specific installation.

Sinusoidal (LC) Filter Selection

An LC sinusoidal filter, commonly called a sine filter, is the heavier mitigation option. It consists of a three-phase iron-core reactor in series with the line and a delta- or star-connected capacitor bank at the inverter end, tuned to the pulse frequency. The filter attenuates the switching harmonics so thoroughly that the voltage at the cable sending end approximates a sine wave; the cable then behaves as a transmission line with a well-behaved source impedance and the reflection problem essentially disappears.

The trade-off is the voltage drop across the series reactor. A sine filter typically drops 6–10% of the rated line voltage at full load, which must be added to the cable voltage drop when sizing the supply. For a 415 V system this is roughly 25–40 V lost in the filter alone, on top of the cable drop. The MM440 at 96% of input voltage in V/f control, combined with filter drop and cable drop, can leave the motor terminal at 380 V or less, which is the lower end of the standard motor's tolerance band but is generally acceptable.

Selection parameters for a sine filter on a 37 kW MM440:

Parameter Typical Value
Rated power 37 kW continuous, 110% for 60 s
Rated current 75–90 A (matches inverter output rating)
Rated voltage 400–480 V, 3-phase
Tuning frequency 2 kHz to 4 kHz (must match P1800)
Insertion loss ≥ 30 dB at switching frequency
Voltage drop at rated current 6–10% (≈ 25–40 V at 415 V)
Maximum cable length 300 m tested, 550 m achievable with derating
Critical: The pulse frequency P1800 must be set to match the sine filter tuning frequency. Operating the drive at 8 kHz PWM into a filter tuned for 4 kHz will overheat the filter capacitors and may cause resonance. Verify the filter nameplate and the parameter before commissioning.

Voltage Drop Calculation for the 550 m Aluminum Feeder

For a 3-core XLPE aluminum cable of 185 sq.mm cross-section, the DC resistance per conductor at 90 °C is approximately:

R = ρ × L / A = 0.0313 Ω·mm²/m × 550 m / 185 mm² ≈ 0.093 Ω per conductor

The total loop resistance for two conductors (assuming balanced 3-phase and ignoring neutral):

Rloop = 2 × 0.093 = 0.186 Ω

For the 3-phase voltage drop with motor current of 53 A and a typical motor power factor of 0.85:

Vd(3φ) = √3 × I × R × cos φ = 1.732 × 53 × 0.186 × 0.85 ≈ 14.2 V

The single-phase equivalent (line-to-line drop on one feeder pair):

Vd(1φ) = 2 × I × R × cos φ = 2 × 53 × 0.186 × 0.85 ≈ 16.8 V

The field-calculated figure of 11 V reported in the original correspondence sits at the lower end of this band and is consistent with a 70 °C conductor temperature and a power factor closer to 0.80. Whichever calculation is used, the absolute value of the drop is small (3–4% of 415 V) and is not the controlling problem. The controlling problems are the peak reflected voltage and the capacitive charging current, both of which are independent of the rms voltage drop.

Drive Derating Parameters on the MM440

The MM440 maximum output current is governed by derating curves in the operating instructions that respond to three independent variables. The integrator can trade off each of these to extend the permissible cable length without sacrificing motor torque margin.

Parameter Symbol / MM440 Access Effect on Cable Behavior
Pulse frequency P1800 Reducing from 8 kHz to 2 kHz lowers the effective switching rate by 4×, reducing both the dV/dt and the cable capacitive current. Lower switching frequency also reduces inverter losses and heatsink stress.
Ambient temperature Site-specific Each 10 °C rise above 40 °C requires approximately 5% current derating.
Altitude Site-specific Above 1000 m, insulation and air-cooling derate by ~1% per 100 m. Sites above 2000 m require further reduction.
V/f characteristic P1300 Switching from a sensorless vector mode to a linear V/f curve reduces the controller's gain and slows the response to the reflected-wave disturbance.
Output current limit P0640 Capping at the motor nameplate current (53 A) rather than the drive rating (≈ 75 A) gives headroom for the capacitive current peaks.

The most effective single change is to drop P1800 from the default 4 kHz to 2 kHz. This halves the switching losses, quarters the capacitive charging current per second, and gives the existing output choke roughly twice the time to limit the dV/dt. The cost is a small rise in motor audible noise and a small increase in current ripple, neither of which is material at 30 kW.

Field Impedance Matching: What MM440 Can and Cannot Do

The MM440 firmware does not include a parameter that explicitly matches the drive output impedance to a long cable. There is no "cable length compensation," no "feeder tuning," and no adjustable output impedance network. The MM440 family predates many of the modern long-cable features introduced on the SINAMICS G120 platform, which does include selectable output filter parameters and automatic pulse-frequency management.

The integrator therefore has to achieve impedance matching passively, by selecting the output hardware so that the source impedance of the inverter-plus-choke combination is close to the cable surge impedance. The following practical approach is field-proven:

  1. Fit the Siemens output choke 6SE6400-3TC07-5ED0 at the inverter terminals.
  2. Fit a second identical output choke in series, immediately downstream of the first, on the same three phases.
  3. Set P1800 = 2 kHz.
  4. Set P1300 = 0 (linear V/f with quadratic load characteristic if the load is fan/pump, or linear V/f for constant torque).
  5. Cap P0640 at the motor nameplate FLC of 53 A.
  6. Verify altitude and ambient against the derating tables in the operating instructions and apply any further current reduction.
  7. Set the motor nameplate data into P0304–P0311 exactly, and run the MM440 auto-identify routine (P1910 = 1) with the motor uncoupled if possible.

This combination has been used on MM440 installations up to approximately 550 m of shielded XLPE cable. Beyond that, the only remaining mitigation is to install a sine filter specifically rated and tuned for the application, sized by the panel builder rather than ordered as a Siemens accessory.

Commissioning and Verification Procedure

Once the hardware is installed and the parameters above are set, the following verification steps should be completed before the drive is handed over to production.

  1. Insulation test the cable and motor windings with a 1 kV megohmmeter. Cable capacitance to ground on a 550 m XLPE run typically measures 0.2–0.4 μF per phase; record the value for future reference.
  2. Measure the DC bus voltage at the MM440 with the drive stopped and the supply on. Confirm it is within ±5% of the expected 540–620 V for a 415 V AC supply.
  3. Run the drive uncoupled at 5 Hz, then 25 Hz, then 50 Hz, with a clip-on ammeter on each of the three output phases. The currents should be balanced within ±5% and should not exceed 53 A at any speed.
  4. Measure the motor terminal voltage with a true-RMS voltmeter at the motor junction box at 50 Hz full load. Expect 380–395 V. Below 370 V the motor will lose torque; above 405 V the insulation stress rises.
  5. Measure peak line-to-line transient voltage at the motor terminals with an oscilloscope and a high-voltage probe (1000 V, > 50 MHz bandwidth). Peak should be below 1000 V for standard motor windings.
  6. Thermal check after 2 hours of full load: cable surface temperature should not exceed 75 °C, choke surface temperature should not exceed 110 °C (Class F insulation rating), and motor frame temperature should follow the motor manufacturer's curve.
  7. Record parameter set to a BOP or MMC card via the MM440 Starter/STARTER commissioning tool. Save the project file to the engineering archive.
Safety: The MM440 DC bus retains lethal voltage for several minutes after the supply is removed. Always verify zero energy with a properly rated voltage tester before opening any cabinet. The output chokes and sine filter capacitors also retain charge; discharge per the device's own instruction leaflet before touching terminals.

Alternative Mitigations If Hardware Cannot Be Added

Where the integrator cannot install output chokes or sine filters, the remaining options are limited and should be discussed with the end user as risk-acceptance items.

  • Reduce pulse frequency to 2 kHz. This is the cheapest and most effective single change.
  • Switch to V/f control from sensorless vector. Vector control has higher gain on the current loop and is more sensitive to reflected wave disturbances.
  • Use a 480 V or 500 V frame motor. A motor wound for 460 V or higher has thicker turn-to-turn insulation and tolerates the reflected peak.
  • Install an inverter-duty motor built to NEMA MG1 Part 31, withstanding 1600 V peak and 2 kV/μs.
  • Use a IEC 60034-25 compliant motor, which is the international equivalent of NEMA MG1 Part 31.
  • Move the drive closer to the motor. If the cable run is the only barrier, relocating the inverter into a motor-room-grade enclosure near the motor removes the problem entirely.

These mitigations do not give the same level of protection as a properly sized sine filter, but they reduce the probability of premature motor insulation failure and are acceptable for non-critical loads such as fans, pumps, and conveyors where a controlled shutdown for service is tolerable.

Troubleshooting Matrix

Symptom Likely Cause Diagnostic Action
MM440 trips with F0001 (overcurrent) on acceleration Capacitive charging current exceeds IGBT rating Measure phase currents with clip-on ammeter; look for current spikes coincident with PWM edges Reduce P1800; add or increase output choke inductance
MM440 trips with F0002 (overvoltage) on deceleration Regenerative energy reflected back into DC bus through long cable Check DC bus voltage during decel; compare to 1.35 × Vsupply Extend decel ramp, fit braking chopper + resistor
Motor draws higher current than nameplate at full speed Low terminal voltage from combined filter drop + cable drop Measure V at motor terminals at 50 Hz Check filter is correctly sized; reduce cable length or increase conductor cross-section
Motor winding insulation failure after 3–12 months Sustained over-voltage peaks at terminals Disassemble motor, inspect winding, perform surge test Add sine filter, replace with inverter-duty motor
Output choke temperature > 120 °C Choke undersized for the application or pulse frequency too high Thermal probe on choke body Reduce P1800; specify next-size choke
Audible motor whine that varies with load Resonance between cable capacitance and choke inductance Oscilloscope on motor terminal; FFT of voltage Add damping resistor across choke secondary, or move to sine filter

Recommendations for This Specific 37 kW / 30 kW / 550 m Application

For the parameters stated, the recommended engineering package is:

  1. Fit the Siemens 6SE6400-3TC07-5ED0 output choke at the inverter output.
  2. Add a second identical choke in series to extend practical reach to 550 m.
  3. Set P1800 = 2 kHz, P1300 = 0 (linear V/f), P0640 = 53 A.
  4. Confirm the motor is inverter-duty or replace with one rated to NEMA MG1 Part 31.
  5. Document the cable run as untested by Siemens and obtain end-user sign-off.
  6. Verify with oscilloscope at the motor terminals that the peak line-to-line transient is < 1000 V and the rms voltage is > 370 V at 50 Hz full load.

If the integrator cannot accept an untested configuration, the only fully catalog-compliant alternative is to move the MM440 closer to the motor or to install a sine filter rated and tuned for the specific 550 m run by a panel builder with appropriate Siemens MM440 experience.

What is the maximum motor cable length for an MM440 with an output choke?

The Siemens MM440 catalog specifies 300 m of shielded cable when the drive is fitted with an output choke such as the 6SE6400-3TC07-5ED0 at a 400 V supply. Cable runs beyond 300 m are not tested by Siemens and require additional mitigation such as a second series choke or a sine filter, combined with derating of the pulse frequency parameter P1800.

What voltage peak can the motor terminals see on a long cable from an MM440?

On long motor cables fed by an MM440, the peak phase-to-phase voltage at the motor terminals can reach approximately 1.5 kV due to the reflection of the PWM switching edge at the motor's high surge impedance. Standard induction motors tolerate roughly 1000 V peak; inverter-duty motors rated to NEMA MG1 Part 31 or IEC 60034-25 tolerate up to 1600 V peak and 2 kV/μs.

Can I use two output chokes in series on the MM440 to extend the cable reach to 550 m?

Yes, two Siemens 6SE6400-3TC07-5ED0 chokes in series on each phase is a documented field practice for extending the MM440 cable reach beyond the 300 m tested limit. This configuration is not formally tested or documented by Siemens as an approved arrangement, so the integrator accepts the responsibility for verification of current rating, thermal rise, and EMC behavior.

Why does the MM440 parameter P1800 matter for long cable runs?

P1800 sets the IGBT pulse frequency between 2 kHz and 16 kHz. Each PWM edge delivers a capacitive charging current into the cable capacitance. Halving P1800 halves the number of switching events per second, lowering the average capacitive current and giving the output choke more time to limit the dV/dt. Setting P1800 to 2 kHz is the most effective single derating action for long cable installations.

Is a sine filter better than an output choke for a 550 m motor cable?

A sine filter gives stronger protection than an output choke because it reconstructs an approximately sinusoidal voltage at the cable sending end, eliminating the PWM edges that drive the reflection events. The trade-off is a 6–10% voltage drop across the filter and the need to match the filter tuning to P1800. For a 550 m run where the integrator requires a catalog-compliant solution, a sine filter is the more robust option provided the resulting motor terminal voltage remains above the motor's minimum tolerance (typically 380 V on a 415 V system).

Back to blog