Selecting Phoenix Contact Clipline Terminals for Vibration

Daniel Price11 min read
Other ManufacturerOther TopicTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Follow the conductor. A control signal leaves a PLC output card, lands on a terminal block, crosses a bridge or a jumper wire, and exits toward a field device. Every one of those landings is a mechanical joint, and on equipment shipped by truck, ship, and crane to a rig, the joint is the weakest hop in the path. Layer one first: before anyone blames the I/O card, the drive, or the software, the question is whether copper is still in contact with copper at each block.

Where does a screw terminal actually let go?

A screw clamp holds a conductor with preload. The installer torques the screw, the pressure plate compresses the strands, and the joint stays gas-tight only as long as that preload survives. Three things erode it. Stranded copper cold-flows under clamp pressure, so the bundle gets slightly thinner over the first days in service and the screw is now loose against a smaller cross-section. Thermal cycling works the screw thread against the block body. Vibration does the rest: each cycle is a micro-slip at the thread, and once the clamp force drops below the point where the strands are gripped, the conductor starts fretting against the plate, oxidizes, and the resistance climbs until the signal or the coil current fails intermittently.

That is why screw-terminal vendors recommend a retightening interval; one vendor guidance cited in practice is yearly retightening. Equipment that ships to remote rigs never gets that maintenance, so the loose-wire fault becomes the standing first suspect for every intermittent problem. The symptoms below are the ones that trace back to the terminal strip rather than to the electronics.

Symptom in the field Terminal-level cause How to confirm
Intermittent discrete input, clears when panel door is slammed Screw preload lost; strands fretting under the plate Pull test on the conductor; measure voltage drop across the block under load
Relay or contactor coil chatters High-resistance joint in the coil circuit Millivolt drop across each block in the coil path
Short between adjacent circuits after shipping Stray strands from an unclean strip touching the neighboring terminal Visual inspection under light; insulation test between adjacent points
Fault appears only after the third or fourth transport leg Cumulative torque relaxation, no retightening done Torque check on a sample of screws against the block's rated value
Two circuits fail together Two wires doubled into one screw clamp; one slipped out Look for doubled conductors; count wires per clamp

Check before proceeding: on a returned unit, pull gently on every conductor at the terminal strip before powering it up. Any conductor that moves is the fault, and it tells you the joint type, not the electronics, needs to change.

Which spring clamp type belongs in a shipped panel?

Spring clamp is not one technology. Both Wago and Phoenix Contact sell two distinct mechanisms, and the field experience with them is opposite.

Mechanism How the wire goes in How the wire comes out Field behavior
Push-in spring Conductor (ferruled or solid) pushed directly against a spring leaf Release button or tool must open the spring; a screwdriver jammed in as a substitute damages the block Fast to assemble. On removal without the correct tool the spring edge raises a barb on the conductor and the barb hooks the clip even when it is open; the wire end has to be cut off, shortening the conductor each time
Tool-actuated spring (the type Phoenix Contact promotes in Clipline) Standard narrow screwdriver opens the clamp, conductor inserted, screwdriver withdrawn, spring closes on the conductor Same screwdriver reopens the clamp; conductor slides out Does not damage the conductor, does not vibrate loose, no dedicated release tool required for troubleshooting

The mechanism that matters for vibration is follow-up force. A spring clamp is a spring in compression against the conductor. When the strands cold-flow and the bundle shrinks, the spring follows and clamp force stays essentially constant. There is no thread to back off and nothing to retighten. That is the property a screw joint cannot offer, and it is the entire reason to change block types.

Much of the opposition to spring clamps comes from engineers who lived through the push-in barb problem with an early product and now object to anything labelled "spring." The objection is aimed at the wrong mechanism. Select the tool-actuated variant and confirm it on the datasheet drawing before ordering; both vendors sell both, and the sales literature does not always volunteer the difference.

Check before proceeding: take one sample block, insert a stranded conductor, remove it with a standard screwdriver five times, and inspect the strands under magnification. No barbs, no lost strands, no deformation of the clamp opening. Then bench it: a firm pull on the conductor must not move it.

How do you prepare the conductor for the clamp?

The spring clamp holds stranded wire better than a screw plate does even with bare strands, but bare strands in any clamp are a compromise. Crimp a ferrule on every stranded conductor. The ferrule converts the bundle into a single rigid pin, so the clamp bears on a defined surface, the strands cannot splay into the adjacent terminal, and repeated insertions do not shed copper. The failure pattern of screw strips with strands touching the next terminal over is a preparation failure, and a ferrule removes it.

  1. Strip to the length the ferrule manufacturer specifies for the barrel; no bare copper between insulation and ferrule collar, no strands protruding past the barrel end.
  2. Crimp with a ratcheting ferrule crimper sized to the conductor; a crimp that releases before the ratchet completes is not a crimp.
  3. Open the clamp with the screwdriver, insert the ferrule to the bottom of the clamp cavity, withdraw the screwdriver.
  4. Pull on the conductor. It must not move.
  5. One conductor per clamp point. Never two.

The one-wire-per-terminal rule is not tidiness. Two conductors in one clamp share a single contact force; the thicker or stiffer one takes the load and the other is held by friction only, and friction is what vibration defeats. Where two circuits must meet, use the block's bridging system, covered next.

Check before proceeding: after landing a strip, run a finger along the insulation ends. Every ferrule collar should sit against the block face and every conductor should resist a pull.

How do you bridge and earth without jumper wires?

Follow the path a common rail takes across a strip. On a screw strip it is a daisy chain of jumper wires, each one a doubled conductor in a screw clamp, which is two vibration failure points per block. Clipline blocks accept plug-in bridges that connect adjacent blocks through dedicated bridge shafts, so the conductor terminal is left with exactly one wire and the common is carried in the block body. The layout stays flat, a technician can read it without tracing wires, and there is no jumper to work loose.

Earth is the same problem multiplied. Instead of jumping a ground wire from block to block, use the earth blocks that clamp onto the DIN rail and make the rail itself the earth conductor. Each PE block bonds to the rail on installation; the field wire lands once in that block and the path to the panel earth is metal-to-metal through the rail foot. That removes a row of green-yellow jumpers and their clamp points, and it makes the earth path visible: any technician can see which blocks are PE by color and rail contact.

  1. Group blocks by function and by common; place bridged groups contiguously so the bridge is a single straight bar.
  2. Insert bridges into the bridge shafts, not the conductor entries.
  3. Fit DIN-rail earth blocks at the earth positions and confirm the rail foot is seated and clamped.
  4. Verify the rail itself is bonded to the panel earth stud with a conductor sized for the fault current.

Check before proceeding: measure resistance from each PE block clamp to the panel earth stud with a low-ohm meter. Every reading should be in the milliohm range and consistent across blocks; an outlier is a rail foot that did not seat.

Does the block meet the hazardous-area rating on the rig?

Equipment going to rigs lands in classified areas. Phoenix Contact publishes Class I Division 2 and ATEX certifications for the relevant Clipline blocks, and the documentation for the range is complete enough to include in the panel certification package. That is a selection criterion in its own right, because a spring clamp with no hazardous-area listing does not solve the problem if the panel cannot be installed.

  1. Pull the datasheet for each ordered block part number and confirm the specific marking the rig site requires appears on it; certification is per part, not per family.
  2. Confirm the certification covers the conductor cross-section range and ferrule type you are using.
  3. File the certificates with the panel drawings so the site inspector can match block markings to paper.

Check before proceeding: the marking molded or printed on the installed block matches the marking on the certificate in the package. If it does not, the block is the wrong variant.

How do you defeat the field-tool objection?

The push-in fiasco taught a generation of field technicians that spring blocks need a tool nobody has. The tool-actuated Clipline clamp needs a narrow flat-blade screwdriver, which every technician already carries. The remaining objection is pace: the argument that a spring block takes longer to wire. It takes longer only relative to a screw block that is not ferruled and not cleaned, and that block is the one that shipped loose.

Design for the technician who has never seen the panel. Label every block, keep one conductor per clamp so there is nothing to untangle, let the bridges and rail earth carry the commons so the wire count is minimal, and put a one-line note on the inside of the door: "Spring clamp. Open with flat screwdriver, insert, release." A demonstration on a sample block converts most reasonable objectors; the ones it does not convert are not arguing about the mechanism.

Check before proceeding: hand a sample block and a screwdriver to a technician who has not used one. If they can remove and re-land a ferruled conductor without instruction, the field-tool objection is closed.

Can I pay more per block and still come out ahead?

Yes, and the accounting is straightforward for rig equipment. A spring block, a ferrule, and the extra assembly minutes cost more per point than a bare screw strip. A loose conductor on a rig costs the downtime of the whole unit, the mobilization of a technician, and, when a stray strand shorts a control circuit, the components it destroyed. Wire is cheap and is replaced when it is worn; the components shorted by a control wiring fault and the hours the unit sits idle are not. The retightening interval that screw terminals need is a maintenance task the rig will never perform, so the screw strip's lower unit price buys a fault that arrives on schedule.

Some customers will still specify barrier-strip blocks with ring terminals. A ring terminal under a screw is the one screw joint that cannot fall off when the screw relaxes, so it is a defensible answer to the same vibration problem where a customer specification forces screws. It does not remove the resistance rise from lost preload, only the physical drop-out.

Check before proceeding: the bill of materials shows one ferrule per stranded conductor, bridges for every common, and rail-earth blocks for every PE point. Missing any of those means the design has reintroduced a jumper wire somewhere.

How do you verify the strip before the panel ships?

End to end, in order, before the door closes.

  1. Pull test every conductor on every strip. No movement.
  2. Visual inspection of every entry: ferrule collar against the block face, no bare copper, no strand outside a ferrule, no second conductor in any clamp.
  3. Bridge check: continuity across each bridged group from first block to last, and no continuity to the neighboring group.
  4. Earth check: low-ohm resistance from every PE block to the panel earth stud, all readings consistent.
  5. Certificate check: marking on each installed block matches the certificate in the package.
  6. Functional check with the panel powered: exercise every I/O point and every coil, then rap the panel enclosure sharply beside each strip and watch for any state change or coil chatter. A spring-clamp strip does not respond; a screw strip that is going to fail in transit usually does.

FAQ

Can I use Phoenix Contact Clipline spring terminals on stranded wire without a ferrule?

The spring clamp holds bare stranded conductor better than a screw plate does, but crimp a ferrule anyway. The ferrule stops strand splay into the adjacent terminal and lets the conductor survive repeated removal with a screwdriver without shedding copper.

Does a spring clamp terminal need periodic retightening like a screw terminal?

No. The spring follows the conductor as the strands cold-flow, so clamp force stays constant. Screw terminals lose preload and one vendor guidance calls for yearly retightening, which shipped rig equipment never receives.

Can I remove a wire from a Clipline spring terminal with a normal screwdriver?

Yes, for the tool-actuated variant. A narrow flat-blade screwdriver opens the clamp for both insertion and removal, and the conductor comes out without a barb. Push-in variants need their release button or tool and are damaged by a screwdriver substitute.

Does Phoenix Contact Clipline carry Class I Division 2 and ATEX certification?

Phoenix Contact publishes Class I Division 2 and ATEX certifications for the relevant Clipline blocks. Certification is per part number, so confirm the marking on each ordered block's datasheet against the site requirement.

Can I put two wires in one spring clamp terminal to save space?

No. Two conductors share one clamp force, the stiffer one takes the load and the other is held by friction that vibration defeats. Use plug-in bridges between adjacent blocks and DIN-rail earth blocks for PE so each clamp carries exactly one conductor.

Back to blog