Siemens 7 km PLC Link Options: 4-20mA, SINAUT, Modem Solutions

David Krause22 min read
Application NoteIndustrial NetworkingSiemens
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens 7 km PLC Link Over 0.8 mm Copper: 4-20 mA, SINAUT, Modem, and Cellular Architectures

This application note solves a recurring field problem: two Siemens automation sites are separated by 7 km of existing two-core 0.8 mm telephone-grade copper cable, and each site must exchange two 4-20 mA analog inputs and two 0/4-20 mA analog outputs at low bandwidth. The goal is to identify which of the realistic Siemens-supported link architectures (direct 4-20 mA loop, SINAUT dedicated-line modem, GSM/GPRS cellular, or single-mode fiber) is technically valid, dimension it with hard numbers, and define the I/O, surge-protection, and commissioning steps required to make it work in the field.

Scope warning. The figures below assume the 0.8 mm dimension is the copper conductor diameter (typical for aerial telecom drop and jelly-filled primary cable, IEC 60708 reference constructions), giving ~0.503 mm² cross-section. If the cable is a smaller CSA (e.g. 0.5 or 0.6 mm) all loop-resistance numbers scale proportionally and the conclusions worsen.

1. Problem Definition and Constraints

The original control requirement decomposes into the following engineering constraints, each of which constrains the link design:

Parameter Value Design implication
Distance, end-to-end 7 000 m Exceeds RS-485 (1 200 m) and PROFIBUS DP (with copper, ~9.6 km at 9.6 kbps). Attenuation and capacitance dominate.
Medium 2-core 0.8 mm twisted pair, 10 spare pairs Voice-grade copper; 35 ohm/km DC, ~50 nF/km capacitance. Spare pairs allow a primary link plus a redundant link plus analog fallback if needed.
Site A I/O 2 × AI 4-20 mA, 2 × AO 0/4-20 mA Eight signal values total round trip, polled once per second or slower.
Site B I/O Mirror of Site A True bidirectional telemetry; not a pure master/slave SCADA poll.
Update rate A few values per second at most Link budget can be < 1 kbps if necessary; bandwidth is not a constraint.
Controller family Siemens SIMATIC (user-specified) Solution must use S7-1200, S7-1500, ET 200, or LOGO! 8 BM with valid Siemens CP/TIM module or approved partner product.
Outdoor run Aerial or buried 7 km High lightning exposure, ground potential rise between sites, surge protection mandatory.

Because the data rate is trivial but the distance and the medium are harsh, the design problem is dominated by electrical survivability (surges, ground rise), loop resistance (for the 4-20 mA option), and link availability (for the digital options). The bandwidth question is essentially free.

2. Direct 4-20 mA Loop Over 7 km: When It Fails and When It Might Work

The first reaction is always to send the 4-20 mA signal directly through the available copper. The arithmetic is unforgiving but the boundary conditions decide whether it is even possible.

2.1 Loop resistance of 0.8 mm copper at 7 km

For a 0.8 mm diameter copper conductor (A = π × 0.4² = 0.5027 mm²) with ρ = 1.724 × 10⁻⁸ Ω·m at 20 °C:

Rkm = ρ / A × 10³ = 1.724 × 10⁻⁸ / 5.027 × 10⁻⁷ × 10³ ≈ 34.3 Ω/km

For 7 km one-way = 240 Ω, round-trip (transmit + return on the same pair) = 480 Ω. With temperature coefficient α = 0.00393 /°C referenced to 20 °C, the loop resistance climbs to 555 Ω at 60 °C (typical summer aerial cable temperature) and 606 Ω at 80 °C (a black-jacketed cable in direct sun).

2.2 Voltage drop at 20 mA

At full-scale 20 mA the loop drop is 9.6 V at 20 °C, 11.1 V at 60 °C, and 12.1 V at 80 °C. A 2-wire loop-powered transmitter (e.g. pressure transmitter in 4-20 mA) must generate the loop current and still leave enough headroom for the receiver burden (typically 5-7 V) and for its own compliance. The available budget is therefore:

Vheadroom = Vsupply − Vdrop(cable) − Vburden(receiver) − Vcompliance(transmitter)

With a 24 V supply, 20 °C cable, 7 V burden and 12 V compliance: 24 − 9.6 − 7 − 12 = −4.6 V. A 2-wire 4-20 mA sensor cannot work at 7 km on this cable at 24 V supply, even before considering HART. The same sensor at a 30 V loop supply gives 30 − 9.6 − 7 − 12 = +1.4 V, marginal. At 36 V it is +7.4 V, technically OK at 20 °C but eroded to +0.9 V at 60 °C. Long-term reliability is unacceptable.

2.3 The one scenario that does work

A 4-wire (actively sourced) sensor with separate power and a regulated current output, or a 4-wire valve positioner with a current input, can drive 20 mA through 480 Ω at 24 V because the transmitter's compliance is typically 15-24 V and the receiver's burden is decoupled from the supply. For 4-wire devices, direct analog over the 0.8 mm pair is feasible, but only with:

  • Verified sensor and positioner datasheets showing < 9.6 V compliance at 20 mA.
  • Supply at the receiving PLC end at 24 V minimum, ideally with a 30 V boost.
  • No HART communication (HART requires ~1 Vpp across 250 Ω and is incompatible with 480 Ω of DC loop resistance plus the high cable capacitance at 7 km).
  • Calibration trim to compensate for the absolute copper resistance tolerance (±5 % is typical for telecom-grade cable) and temperature derating.
Conclusion. For 2-wire loop-powered 4-20 mA sensors and standard PLC analog output to a 2-wire valve, direct transmission over 7 km of 0.8 mm copper is not a viable solution. A digital link that transports the digitized mA value is the correct architectural answer. The remainder of this article develops that digital architecture.

3. Link Architecture Options Compared

Three realistic digital options exist for the 7 km, 0.8 mm copper environment. They are summarized in the matrix below; the recommended option depends on whether the existing cable is in good condition and whether a cellular signal is available at both sites.

Attribute SINAUT over dedicated leased line (existing copper) GSM/GPRS cellular + PSTN dial backup Single-mode fiber Ethernet + media converter
Uses 0.8 mm cable Yes (1 pair + 1 spare) No (cellular only) No (requires new fiber pull)
Typical bandwidth 300 - 1 200 bps (FSK modems) GPRS 30 - 50 kbps; LTE 1 - 5 Mbps 100 Mbps full duplex
Latency, typical 100 ms - 1 s 300 ms - 2 s < 5 ms
Lightning exposure High (cable is antenna) Low (cable removed) None (dielectric)
Ground potential rise Coupled between sites, needs isolation Eliminated Eliminated (fiber is dielectric)
Siemens-native module S7-1200/1500 CP family; legacy TIM 3V-IE / TIM 4R-IE on S7-300 CP 1242-7 GPRS, CP 1243-7 LTE SCALANCE XC-/XR-/MM switch or media converter; S7 CP 1542-1
Capital cost (typical 2024 reference, verify with Siemens Industry Mall) Low (modems ~€300-700 per site, S7-1200 + CP ~€700-1 200) Medium (cellular CP ~€600-900 + SIM + data plan) High (fiber pull can dominate; ~€5 - 20 per meter installed + media converters ~€400-800)
Best fit when Cable is intact, no cellular, low OPEX, telemetry-grade data is enough Cable damaged or not available, cellular coverage good, no leased fiber Site has its own power, latency-sensitive control, future-proofing required

4. Option A: SINAUT Over the Existing 0.8 mm Pair (Recommended for This Use Case)

SINAUT (Siemens Network Automation) is the Siemens telemetry stack that historically ran on S7-300 TIM 3V-IE and TIM 4R-IE modules over leased lines, analog telephone, ISDN, GSM, and Ethernet. On the current S7-1200 and S7-1500 generation, the same protocol is exposed by the CP 1243-1 (Ethernet/IPsec) and CP 1242-7 (GPRS) communications processors in combination with the TeleControl server / TIA Portal project, with SINAUT ST7 as the application-layer protocol.

For a 7 km dedicated line of 0.8 mm copper, the modern Siemens-supported path is:

  1. One S7-1200 CPU 1214C (or 1215C) at each site, with the local SM 1231 AI and SM 1232 AO modules wired to the field devices.
  2. One industrial FSK leased-line modem at each end (e.g. Westermo TD-32, Phoenix Contact PSI-MODEM, or a Siemens-recommended equivalent). The S7-1200 serial interface (RS-232 / RS-422) connects to the modem. The modem's line side connects to one 0.8 mm pair.
  3. SINAUT ST7 frames the data; the modem translates them to a 300-1 200 bps FSK signal on the copper pair. With 50 nF/km × 7 km = 350 nF total, the achievable data rate is on the order of 1 200 bps with careful receiver equalization. This is more than enough for 8 analog values every 100-200 ms.
  4. The second twisted pair of the 10 available is used as a hot-standby link, with the S7-1200 selecting the live path on loss-of-carrier.

For reference, the older TIM-based path is still maintained by Siemens for S7-300/400 fleets: the TIM 3V-IE (6NH7800-3BA00) or TIM 4R-IE (6NH7800-4BA00) module plugs into the S7-300 rack and provides dedicated-line, analog dial, ISDN, and Ethernet on a single device. Verify exact catalog numbers, firmware, and availability with the Siemens Industry Mall and the SINAUT system manual at Siemens Industry Online Support.

4.1 Siemens module selection (verify current ordering data with Siemens)

Function Siemens module (family) Notes
CPU, Site A and B SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0 family) Includes 2 AI onboard (not 4-20 mA — verify variant); provides RS-485 for modem or expansion
AI 4-20 mA, 4 ch SM 1231 AI 4 × 13 bit (6ES7231-4HF32-0XB0 family) Configured for 4-20 mA; input burden < 5 V; diagnostics per channel
AO 0/4-20 mA, 2 ch SM 1232 AO 2 × 14 bit (6ES7232-4HB32-0XB0 family) Output selectable 0-20 mA or 4-20 mA; 14-bit resolution; short-circuit proof to signal
Communications processor (serial path) CM 1241 RS-232 / RS-422 / RS-485 (6ES7241-1AH32-0XB0 family) Used to drive the leased-line modem; configure for RS-232 or RS-422 depending on modem interface
Communications processor (cellular backup, optional) CP 1242-7 GPRS (6GK7242-7KX31-0XE0 family) GPRS, CSD fallback for legacy dial; antenna ANT794-4MR
Surge protection on each analog pair SIDAC / Dehn Blitzductor / Phoenix Contact PT-IQ Always required on a 7 km outdoor pair; see Section 8
All Siemens catalog numbers above are representative of the current product family as of this writing. Confirm the exact MLFB, firmware version, and 6ES / 6GK prefix with the Siemens Industry Mall and the relevant entry in the Siemens CA 01 catalog before ordering. Functions and form factors are stable across firmware updates, but specific MLFBs rotate.

5. Option B: GSM/GPRS Cellular with PSTN or CSD Backup

If the 0.8 mm copper is degraded, of unknown integrity, or the operator does not want to maintain surge protection on a 7 km aerial run, the cleanest answer is to remove the long copper path entirely and use cellular. For a 7 km hop the typical cell tower is line-of-sight if the site has elevation, and a high-gain directional LTE antenna (e.g. ANT 794-4MR or a third-party 5-9 dBi Yagi) usually resolves coverage problems.

The Siemens-native components are:

  • CP 1242-7 GPRS for the S7-1200, supporting GPRS (2G/3G) plus CSD fallback for legacy dial-up. Connects to the S7-1200 backplane and is configured from TIA Portal.
  • CP 1243-7 LTE for the S7-1200, supporting 4G LTE in EU bands (B1/B3/B7/B8/B20/B28) plus 2G/3G fallback. Higher data rate and a more future-proof cellular path.
  • Telecontrol Server Basic (SINAUT ST7cc / TeleControl Server) running on a central SCADA host, terminating the SINAUT frames from each site.
  • SINEMA Remote Connect for IPsec-encrypted VPN into a private APN, avoiding the public Internet attack surface.

Redundancy: a CP 1242-7 (cellular) plus a CM 1241 dial-up modem on the existing PSTN service gives true media diversity. The S7-1200 program polls both links and switches on heartbeat timeout. Failover time is 30-90 seconds — acceptable for analog process values at second-scale, unacceptable for motion or safety.

For an isolated 2-sensor / 2-valve plant with a private APN, a typical data plan is 5 MB/month, dominated by SINAUT keep-alive frames.

6. Option C: Single-Mode Fiber Ethernet

If the 0.8 mm cable must be retired or replaced, or if latency and bandwidth drive the design, single-mode 9/125 µm fiber with SCALANCE media converters is the cleanest answer. At 1310 nm a typical SCALANCE XC-100 or third-party media converter reaches 30 km on single-mode fiber with no repeater — 7 km is well within budget.

For Siemens-native Ethernet on the S7-1500, the CP 1542-1 or CP 1543-1 provides PROFINET IO and TCP/IP S7 communication. The SCALANCE XC-200 / XR-200 / MM900 families provide managed switch ports and SFP cages for single-mode optics. Power over Ethernet is not required for this link. Verify SFP module (e.g. 6GK5900-1SD00-0AA0 for LC-LX 1310 nm 10 km or the 30 km LX variant) using the SCALANCE configuration manual on Siemens Industry Online Support.

Note that pulling 7 km of new single-mode aerial or buried fiber is the dominant cost in this option and is usually justified only when the existing 0.8 mm cable is already condemned or when the operator needs future-proofed capacity for video, IIoT, or additional SCADA points.

7. Siemens PLC and I/O Module Configuration

The user requirement is two 4-20 mA inputs and two 0/4-20 mA outputs per site. The minimum S7-1200 configuration that satisfies this without further expansion is:

  • CPU 1214C DC/DC/DC with 14 digital inputs (the onboard 2 analog inputs are 0-10 V on most variants and not 4-20 mA — confirm variant). Digital I/O unused here.
  • SM 1231 AI 4 × 13 bit (4-20 mA variant), occupying the first I/O slot. Only 2 channels used; the other 2 are wired to ground and disabled in TIA Portal to suppress open-circuit diagnostics.
  • SM 1232 AO 2 × 14 bit, in the second I/O slot. Channels 0 and 1 drive the two 4-20 mA valves. The module accepts either 0-20 mA or 4-20 mA per channel and is selected in the device configuration under "Outputs".

7.1 4-20 mA wiring conventions

For the SM 1231 AI in 4-20 mA mode, the channel is a current input; the field loop current flows into the module's I+ terminal and returns on the M terminal. The module provides the loop excitation voltage; the transmitter regulates the current. A 2-wire sensor connects I+ to the sensor's + terminal and M to the sensor's − terminal. A 4-wire sensor uses its own power supply and its regulated output drives the I+ terminal; the M terminal returns to the sensor's signal ground. Shield the cable and ground the shield at the cabinet entry only, leaving the field end floating, to avoid ground-loop currents.

For the SM 1232 AO, the output is a current source. Wire I+ to the valve positioner's + input and M to the − input. Open the valve positioner's input to confirm it is a passive (voltage-input) device, not an active current source; if it is active, the PLC output and the valve output will fight and the 4-20 mA value will be undefined. Most industrial valve positioners are passive current inputs and accept the standard 0/4-20 mA from a PLC.

7.2 Diagnostics and scaling

In TIA Portal, scale the raw 0-27 648 integer to engineering units using the NORM_X and SCALE_X blocks:

PVeng = SCALE_X(IN := NORM_X(VALUE := AI_raw, MIN := 0, MAX := 27648), MIN := 0, MAX := 100.0)

For 4-20 mA, the AI raw value of 0 corresponds to 0 mA (a broken wire) and 27 648 corresponds to 20 mA. Below 0 mA, the module flags "Overflow / underflow" in the channel status word; the user program should treat any raw value < 0 or > 27 648 as a faulty input and force the controlled output to its fail-safe position.

8. Surge Protection and Ground Potential Rise at 7 km

A 7 km outdoor cable is a 7 km lightning antenna. A direct or induced strike on the cable route will inject tens of kiloamperes of surge current into the PLC cabinet unless the cable is properly bonded and protected. Even on a sunny day, the two sites are likely at different ground potentials because the local earth electrodes differ in resistance and the soils differ in moisture.

8.1 Surge protection on the analog pair

At each cabinet entry, install a two-stage surge protector on each analog pair:

  1. Stage 1 (coarse): a gas discharge tube (GDT) rated 230 V or 350 V (sized above the loop voltage) on the line side, with a 10 kA 8/20 µs surge rating. Example: Dehn Blitzductor BXT ML2 BD 180 or Phoenix Contact PT-IQ-2x2-24DC.
  2. Stage 2 (fine): a TVS diode clamp at the module terminal, with a response time < 1 ns, clamping at 30-33 V. Example: Phoenix Contact PT 4- 24DC or Weidmüller VPU series.
  3. Insert an inductor or PTC between stage 1 and stage 2 to decouple the two stages; without this, the stage 2 TVS is the first to fail.

For the SINAUT modem pair, the same treatment applies; an FSK modem front-end is particularly sensitive to surge because the receiver input is at high impedance.

8.2 Ground potential rise

With a 7 km aerial or buried cable, a nearby lightning strike can produce a ground potential rise of several kV between the two site grounds. The PLC and the modem on each side must be galvanically isolated from the long cable pair, and the cable shield must be bonded to local ground at each end through a heavy-gauge bonding conductor, not directly. For SINAUT over a leased-line modem, the modem provides the isolation barrier — confirm the modem's working voltage (typically 1.5-2.5 kV) and surge withstand (5-10 kV) match the calculated site exposure. If the modem is not isolated, fit an isolation transformer (1.5 kV or 2.5 kV) on the line side.

Safety. The 7 km cable shield carries the full site-to-site ground potential. Do not rely on the shield as the only protective earth. Maintain a dedicated PE conductor from each cabinet to the site ground rod, sized per IEC 60364 (typically 6-25 mm² copper depending on soil resistivity and fault clearing time). The shield is for EMC and lightning, not for personnel safety.

9. TIA Portal Configuration: SINAUT and Analog I/O

The following procedure is generic to TIA Portal V16 or later; the exact menu paths vary by firmware but the objects are stable. Verify against the current TIA Portal help and the S7-1200 system manual on Siemens Industry Online Support.

9.1 Add the CP module and define the link

  1. Open the project and the S7-1200 device configuration.
  2. Insert a CM 1241 (RS-232) in slot 101 or wherever free. Configure the port for 1 200 bps, 8E1, no flow control (the FSK modem handles its own link layer).
  3. Insert a CP 1242-7 in slot 102 (only if the cellular backup is used). Under "Mobile wireless settings", enter the APN, SIM PIN, and the SINEMA Remote Connect server address. Activate IPsec and upload the certificate from the SINEMA RC server.
  4. Right-click the S7-1200 and choose "Properties > Telecontrol > SINAUT" to enable the SINAUT application.

9.2 Define the data points and partner

  1. Create a "Partner" entry for the other site; for the SINAUT dedicated-line path, choose "Dedicated line" as the partner type and enter the partner's station number and the local modem's RS-232 port.
  2. Create data points under the local CPU. For each 4-20 mA input, create a "Data point of type Analog input" mapped to the SM 1231 channel's IW address. For each analog output, create "Data point of type Analog output" mapped to the SM 1232 channel's QW address.
  3. Set the SINAUT update time to 1 s. With 8 data points at 1 s, the link payload is trivial; the 1 s heartbeat is the dominant bandwidth consumer.
  4. Compile and download the project to both CPUs.

9.3 Example program: read AI from remote site, scale, write to local AO

The pattern is a periodic fetch from the partner S7-1200's SINAUT mailbox and a write back. The SINAUT blocks are in the "Telecontrol" library that ships with TIA Portal:

// FB "TC_CONFIG" initialized once in OB100 to load the partner list
// FB "TC_SEND" called every 1 s in OB1 to publish local AI
// FB "TC_RECV" called every 1 s in OB1 to receive partner AI
// On each TC_RECV cycle, scale and write to local SM 1232 AO:

IF "TC_RECV_DB".partner_AI[0].status = 16#0000 THEN
    // 0-27648 raw corresponds to 0-100 %
    "Local_AO_raw[0]" := "TC_RECV_DB".partner_AI[0].value;
ELSE
    // Fault: drive valve to fail-safe position (e.g. 4 mA = 0 % scaled to 0)
    "Local_AO_raw[0]" := 0;
END_IF;

"SM1232_AO[0]" := "Local_AO_raw[0]";

The same pattern in reverse handles the 2 local AI published to the partner's AO. The "value" and "status" fields are populated by the SINAUT firmware; the user program does not implement a transport layer.

10. Commissioning and Verification Procedure

The recommended site acceptance test sequence is below. Each step has a pass criterion; do not sign off the link until every step passes.

  1. Cable continuity and insulation. Megger each pair at 500 V DC. Resistance conductor-to-conductor > 100 MΩ / km, resistance conductor-to-shield > 100 MΩ / km. Document for the as-built record.
  2. Loop resistance. Measure DC resistance of the working pair end-to-end. Expected 240-260 Ω one-way (Site A to Site B) at ambient. If significantly higher, the cable is degraded; find the fault with a TDR (time-domain reflectometer) before energizing the modems.
  3. Modem link test. Loop the far-end modem's TX back to its RX; verify a continuous carrier at 0 dBm and no errors over 5 minutes at 1 200 bps. Then remove the loopback and verify the actual link in both directions.
  4. Surge protection verification. With the link active, briefly (≤ 5 s) inject a 1 kV / 2 Ω combination wave per IEC 61000-4-5 at the cabinet terminal block on each pair. The link must remain operational. If it does not, the surge protection needs a series inductor or a heavier GDT.
  5. Analog I/O calibration at 4 mA and 20 mA. Apply a calibrated 4.000 mA source to each SM 1231 input; the engineering value must read 0.0 % ±0.1 %. Apply 20.000 mA; must read 100.0 % ±0.1 %. If not, the channel is misconfigured (most often: still in 0-10 V mode) or the burden resistor is missing.
  6. End-to-end functional test. From Site A, force AI 0 to 4.00 mA; read the partner's value at Site B. Repeat at 12.00 mA and 20.00 mA. Tolerance ±0.02 mA (typical SINAUT round-trip accuracy for a 13-bit analog with second-scale update). Repeat in the reverse direction.
  7. Failover test (if redundant path is used). Disconnect the primary cable pair at the cabinet; confirm failover to backup in < 90 s. Reconnect; confirm return to primary in < 90 s.
  8. Sustained run. Run the link for 24 h with no operator intervention. Log SINAUT heartbeat counters and channel status; zero errors expected.

11. Troubleshooting Matrix

Symptom Most likely cause Diagnostic step Corrective action
No carrier between modems Open or short on the 0.8 mm pair; surge protector failed open DC loop resistance from end to end; check GDT/TVS status indicators Locate the fault with TDR; replace the surge protector; verify ground bonds
Carrier present, SINAUT timeouts Excessive bit errors from surge, EMI, or cable capacitance Check SINAUT statistics for retransmit count; monitor for noisy ground between sites Reduce baud rate to 600 bps; install heavier surge protection; add an isolation transformer
AI reads 0 % even with 4-20 mA applied at 4 mA Channel configured for 0-10 V, or burden resistor missing on a 4-wire sensor Inspect device configuration in TIA Portal; measure voltage at the SM 1231 terminals Reconfigure channel to 4-20 mA; install 250 Ω burden for 4-wire sensor if needed
AO overshoots / undershoots the setpoint Cable resistance + valve positioner input impedance create a non-linear load Measure voltage at the SM 1232 output under load; compare with 4-wire / 2-wire assumptions Verify the positioner is a passive current input (not an active current source); increase supply if compliance is short
Cellular CP 1242-7 will not register APN, SIM PIN, or antenna orientation Check CP diagnostics buffer; check LED state per CP manual; verify signal strength with field test mode Correct APN, enter PIN, rotate the antenna, or fit a high-gain external antenna
Heartbeat OK, values random or frozen SINAUT partner station number mismatch or wrong data point mapping Compare partner DB in TIA Portal at both sites; check the data point names match exactly Re-import the partner and recompile; check for case sensitivity in data point names
Intermittent failures during thunderstorms Insufficient surge protection on the long pair Check surge protector indicators after every storm; inspect the GDT/TVS for physical damage Upgrade to a 10 kA GDT and add a PTC or inductor between stages; bond the cable shield at both ends with heavy gauge
Values occasionally offset by a fixed amount Ground potential difference between sites, with leakage through the cable shield Measure AC voltage between the two cabinet grounds; check shield bonding Break the shield at one end and bond only at the other; or fit a heavy isolation transformer on the modem pair

Can a 4-20 mA loop be sent over 7 km of 0.8 mm telephone cable?

Not reliably for 2-wire loop-powered transmitters at 24 V. The round-trip DC resistance of 7 km of 0.8 mm copper is ~480 Ω at 20 °C (≈ 555 Ω at 60 °C), giving 9.6 V drop at 20 mA alone. After the transmitter compliance (12-15 V) and the receiver burden (5-7 V), the 24 V supply is exhausted. 4-wire actively-sourced sensors can be made to work with a 30-36 V supply and verified compliance, but HART communication is not possible over this loop.

Which Siemens SINAUT module supports a dedicated 2-wire line over 7 km of copper?

On the current S7-1200/1500 generation, the SINAUT application runs on a CP module (e.g. CP 1242-7 GPRS, CP 1243-1 Ethernet, or a CM 1241 driving an external FSK leased-line modem). On the older S7-300/400 generation, the TIM 3V-IE (6NH7800-3BA00) and TIM 4R-IE (6NH7800-4BA00) modules include native dedicated-line ports. Verify current availability, firmware, and exact MLFB with the Siemens Industry Mall.

What data rate is realistic on 7 km of 0.8 mm voice-grade copper?

With ~50 nF/km of cable capacitance, the line cutoff limits FSK modems to about 1 200 bps in practice, often 600 bps for reliable operation across temperature. This is more than enough for 8 analog values per second and a SINAUT heartbeat. Higher baud rates are possible with adaptive equalization in industrial-grade modems (e.g. Westermo TD-32, Phoenix Contact PSI-MODEM) but should be field-verified.

Is cellular (GPRS / LTE) a reliable primary link for two analog values per site?

Yes, with a private APN, an IPsec tunnel (Siemens SINEMA Remote Connect), and a CP 1242-7 GPRS or CP 1243-7 LTE on the S7-1200. Typical latency is 300 ms-2 s; a 5 MB/month data plan covers a heartbeat-only SINAUT service. Add a redundant PSTN or second cellular APN for media diversity if the application is safety-relevant.

What surge protection is mandatory for a 7 km outdoor cable?

Two-stage protection at each cabinet entry: a gas discharge tube (e.g. Dehn Blitzductor BXT, Phoenix Contact PT-IQ) on the line side for the 10 kA 8/20 µs coarse clamping, followed by a TVS diode clamp (≤ 1 ns response) at the module terminal for the fine clamping, with a series inductor or PTC to decouple the two stages. Galvanic isolation between the cable and the PLC, either inside the modem (typical 1.5-2.5 kV working voltage) or via a separate isolation transformer, is mandatory to ride through ground potential rise during a nearby lightning strike.

Back to blog