Siemens LOGO! 0BA8 Communication Port Configuration Guide

David Krause12 min read
PLC HardwareSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens LOGO! 0BA8 Communication Port Configuration and PC Integration

The Siemens LOGO! 0BA8 (order suffix 6ED1052-1MD08-0BA0 for the LOGO! 12/24 RCE variant) integrates a programmable logic relay with a built-in Ethernet interface. Unlike its predecessors, the 0BA8 generation can communicate over TCP/IP using both a web-based user interface and S7-compatible protocol frames. A common engineering question concerns the fixed nature of the LOGO! communication port: the device does not expose a parameter for changing the listening TCP port, but engineers can still reach the LOGO! from a Visual Studio application through the port-forwarding technique documented below.

1. Hardware Identification: 0BA0 vs 0BA8

The Siemens order-number convention for the LOGO! 8 series ends with the generation suffix. The trailing four characters encode both the production batch and the hardware generation:

Order Number Segment Decoded Value Generation
...-0BA0 Series 0BA0 (LOGO! 6) Legacy, no Ethernet
...-0BA6 Series 0BA6 (LOGO! 6) Legacy
...-0BA7 Series 0BA7 (LOGO! 7) Limited Ethernet
...-0BA8 Series 0BA8 (LOGO! 8) Full Ethernet, S7 protocol

The label 6ED1052-1MD08-0BA0 contains the production code 08 immediately before the 0BA0 suffix. That embedded 08 identifies the device as a 0BA8 (LOGO! 8) unit. The final four characters (0BA0) are an internal production/firmware designator, not a generation marker. This is a frequent source of confusion: the device is a LOGO! 8, not a LOGO! 0BA0 (LOGO! 6). Confirming the generation is essential because only the LOGO! 8 (0BA8) supports TCP/IP-based S7 communication on the integrated RJ45 port.

Critical: Verify the part number before assuming TCP/IP communication is available. The 0BA0, 0BA1, 0BA2, 0BA3, 0BA4, 0BA5, and 0BA6 generations do not support Ethernet. Only 0BA7 and 0BA8 support IP-based communication, and only 0BA8 supports the full S7 communication set on port 102.

2. LOGO! 0BA8 Communication Architecture

The LOGO! 8 integrates an Ethernet switch with two RJ45 ports, allowing daisy-chained network topologies without additional hardware. The controller exposes several communication endpoints simultaneously:

Service TCP Port Protocol Purpose
Web server (HTTP) 8080 HTTP/HTML Configuration UI, variable monitoring
S7 Communication 102 ISO-on-TCP (RFC 1006) Read/write process data, programming
LOGO! Web Editor access 8080 HTTP Custom web-page projects
TFTP/LOGOTCP discovery UDP varies Siemens proprietary LOGO! Soft Comfort discovery

The web server on port 8080 is non-standard (default HTTP is port 80) and was chosen to avoid conflicts with corporate firewalls and IIS installations. The S7 communication on port 102 follows the ISO-on-TCP standard (RFC 1006) used across the SIMATIC family. Both ports are hard-coded in the LOGO! firmware; the device does not provide a configuration parameter to remap them.

3. Why Port Numbers Cannot Be Changed on the LOGO! Itself

The LOGO! 0BA8 firmware does not expose a user interface for port remapping. Reasons include:

  1. Fixed firmware implementation: The TCP listener sockets are bound during firmware initialization. There is no retained parameter slot in the LOGO! configuration tree for TCP port numbers.
  2. LOGO! Soft Comfort dependency: The programming tool (LOGO! Soft Comfort V8.x or later) discovers the device and opens a connection on the standard port 8080. Changing the port would break the discovery mechanism unless the tool were updated in lockstep.
  3. Memory constraints: The LOGO! has limited configuration storage. Adding port-mapping parameters would consume resources better allocated to the program and data blocks.
  4. Web-server port collision avoidance: Port 8080 was selected specifically as a non-privileged alternative to port 80 to prevent issues with corporate web servers. The port is part of the product specification, not a user preference.

When a Visual Studio sample (e.g., the LOGO! self-installer that ships with the LOGO! 0BA8 documentation) attempts to connect to port 10001, it cannot establish a session because the LOGO! is not listening on that port. The sample assumes a forwarded port has been set up at the network boundary, not that the LOGO! itself listens on 10001.

4. Port Forwarding Architecture

The canonical solution is to place a small router (a separate, dedicated routing device) between the engineering PC's network and the LOGO!. The router's WAN-side port is configured to forward the desired external port to the LOGO!'s internal port. The LOGO! itself is not modified.

4.1 Typical Topology

Engineering PC 192.168.2.50 Target port 10001 LAN segment A Dedicated Router WAN: 192.168.2.99 LAN: 192.168.1.1 NAT 10001 → 8080 NAT 10002 → 102 LAN segment B LOGO! 0BA8 192.168.1.10 Listens on 8080, 102 (Direct programming port is 8080)

4.2 Step-by-Step Router Configuration

  1. Assign the LOGO! a static IP via the LOGO! menu: Network → IP Address set to 192.168.1.10, subnet mask 255.255.255.0, gateway 192.168.1.1. Disable DHCP on the LOGO! to prevent address drift.
  2. Connect the dedicated router's LAN port directly to the LOGO!'s RJ45 port using a standard Cat5e/Cat6 patch cable.
  3. Configure the dedicated router's LAN side with IP 192.168.1.1, subnet 255.255.255.0, and disable its built-in DHCP server (the LOGO! has a fixed address and no other clients are needed on this segment).
  4. Configure the dedicated router's WAN side as a DHCP client if the engineering network provides addresses, or as a static address (e.g., 192.168.2.99, gateway 192.168.2.1) if the engineering network uses static addressing.
  5. Add port-forwarding rules on the dedicated router:
    • External port 10001 → internal 192.168.1.10:8080 (HTTP web server / programming)
    • External port 10002 → internal 192.168.1.10:102 (S7 communication)
  6. Update the Visual Studio application connection string or socket creation call to point at 192.168.2.99:10001 (or :10002 for S7 data exchange).
  7. Test connectivity from the engineering PC using telnet 192.168.2.99 10001 or by browsing to http://192.168.2.99:10001 in a browser to confirm the LOGO! web UI loads.
Security: The port-forwarding router introduces a network boundary. Disable its remote management interface, change the default admin password, and update its firmware. A misconfigured consumer router exposed to the engineering network can become a pivot point.

5. Visual Studio Integration

Siemens does not provide a first-party .NET library for LOGO! 0BA8 communication. Two open-source libraries are commonly used:

Library Language Protocol Default Port Notes
Snap7 (libnodave successor) C/C++ with .NET wrappers S7 ISO-on-TCP 102 Used by many third-party .NET wrappers
libnodave (legacy) C with Java/.NET bindings S7 PPI/MPI/ISO-on-TCP 102 Older; S7-200/300/400 era
Siemens S7.NET (NuGet) C# S7 ISO-on-TCP 102 Wraps Snap7; widely used in industrial .NET apps

5.1 Connection String in S7.NET

The S7.NET library uses a CpuType enumeration. For LOGO! 0BA8, select CpuType.Logo0BA8 (compatibility mode). The connection example below targets the forwarded port:

using S7.Net;

var plc = new Plc(CpuType.Logo0BA8, "192.168.2.99", 10002, 0, 0);
plc.Open();

// Read a variable block (DB1) at byte 0, length 16 bytes
byte[] buffer = plc.ReadBytes(DataType.DataBlock, 1, 0, 16);

// Write a single bit
plc.WriteBit("DB1.DBX0.0", true);

plc.Close();

Note that port 10002 in the example is the externally forwarded port; the library sends frames on whichever port the connection specifies. The router translates 10002 to internal 102 transparently.

5.2 Reading Web-Server Variables via HTTP

The LOGO! 0BA8 web server exposes a JSON-like variable table at http://<ip>:8080/<variable-tag>. The Visual Studio sample included with LOGO! Soft Comfort uses HttpClient with the redirected port:

using System.Net.Http;

var client = new HttpClient { BaseAddress = new System.Uri("http://192.168.2.99:10001") };
string response = await client.GetStringAsync("/LOGO!+Variable+Table");
// Parse response for tag values
Common mistake: The sample shipped with the documentation hard-codes port 10001 in the connection logic. Engineers often assume the LOGO! listens on 10001 directly, which fails with a ConnectionRefused error. The correct interpretation is that the sample expects the engineer to have set up port forwarding from 10001 to 8080.

6. Network Configuration on the LOGO!

Configure the LOGO! network parameters from the device's onboard display or via LOGO! Soft Comfort V8.x:

Parameter Path on LOGO! Typical Value Notes
IP Address Setup → Network → IP Address 192.168.1.10 Static recommended
Subnet Mask Setup → Network → Subnet 255.255.255.0 Match the router LAN
Gateway Setup → Network → Gateway 192.168.1.1 Router LAN address
DHCP Setup → Network → DHCP Off LOGO! 8 does not support DHCP client
Web Server Setup → Network → Web Server Access On / Password protected Required for HTTP access
S7 Access Setup → Network → S7 Access On Required for S7.NET

The LOGO! 0BA8 does not support DHCP client functionality. The device must be assigned a static IP. This design choice is intentional to keep the device predictable on industrial networks where address stability matters for alarm routing and tag-name resolution in SCADA systems.

7. Direct Connection Without a Router

If the engineering PC is on the same subnet as the LOGO!, no port forwarding is required. The PC can connect directly using the LOGO!'s real IP and port:

  • Web UI: http://192.168.1.10:8080
  • S7 communication: 192.168.1.10:102
  • LOGO! Soft Comfort online mode: 192.168.1.10 (default port 8080)

This direct connection works when both devices share a subnet and no NAT boundary exists between them. For example, a laptop connected directly to the LOGO!'s second Ethernet port (the 0BA8 has two RJ45 jacks in a built-in switch) using a crossover or modern auto-sensing patch cable.

8. Windows COM Port Considerations

If the engineering PC does not have a free Ethernet port and the application is constrained to serial communication, the LOGO! 0BA8 still requires Ethernet. The legacy LOGO! generations (0BA0 through 0BA6) used a proprietary PC-COM cable for LOGO! Soft Comfort programming. The 0BA8 replaced this with Ethernet. If the engineering PC only has COM ports available, configure a USB-to-Ethernet adapter and assign it a static IP in the LOGO! subnet. Windows COM-port configuration details are documented at Microsoft Learn: Communication Port Settings; however, the COM port configuration is unrelated to the LOGO!'s TCP listener. The two are separate physical interfaces.

9. Troubleshooting Matrix

Symptom Probable Cause Diagnostic Resolution
Browser shows ERR_CONNECTION_REFUSED on port 10001 Port forwarding rule missing or wrong internal port From engineering PC: telnet 192.168.2.99 10001 Re-create forwarding rule pointing to 192.168.1.10:8080
Browser shows timeout on port 10001 Router WAN/LAN addresses swapped; firewall blocking Ping the router WAN IP from PC; check router firewall Verify WAN port goes to engineering network, LAN to LOGO!; disable firewall on forwarded ports
S7.NET throws ISO : An error occurred during connection setup Forwarding rule for port 102 missing; or LOGO! S7 Access disabled Check router rules; check LOGO! Setup → Network → S7 Access Add forwarding rule 10002 → 102; enable S7 Access
Connection succeeds, but reads return zeros Wrong DB number, or variable tag not declared in LOGO! program Open LOGO! Soft Comfort online test; verify variable table Correct the DataType.DataBlock index and offset
LOGO! does not respond to ping IP mismatch, wrong subnet, or Ethernet link down Check LINK LEDs on both ports; verify cable Confirm static IP, mask, and gateway on LOGO!; use crossover-aware patch cable
Web UI loads but login fails Default password changed, or Access Control enabled Check LOGO! Setup → Network → Web Server Access Reset access password from device menu or clear the configuration
Visual Studio sample targets port 10001 but fails Sample assumes forwarding, not direct connection Inspect sample source for hard-coded port Either set up forwarding or modify the sample to use 8080/102 directly
Connection drops after a few minutes Router idle-timeout on NAT entry; S7 keep-alive not honored Monitor router NAT table Enable TCP keep-alive in the .NET socket; reduce router NAT timeout

10. Verification Procedure

After configuring the port-forwarding setup and the Visual Studio application, validate each layer of the stack:

  1. Physical layer: Confirm LINK LEDs are lit on both the LOGO! RJ45 ports and the router LAN port. Replace the patch cable if no link is established.
  2. Network layer: From the engineering PC, ping the router WAN address (192.168.2.99), then ping the LOGO! address (192.168.1.10) from a second PC on the LOGO! segment. Both should respond.
  3. Forwarding layer: From the engineering PC, open a browser to http://192.168.2.99:10001. The LOGO! web UI must load. If it does, the 8080 forwarding rule is correct. Repeat for port 10002 with a S7 client tool.
  4. Application layer: Run the Visual Studio application. Verify that it opens the connection without throwing ConnectionRefused or SocketTimeout, and that read/write operations return expected values.
  5. LOGO! Soft Comfort online test: Open LOGO! Soft Comfort V8.x or later, select Tools → Transfer → Online Test, and confirm the LOGO! is discovered at the forwarded IP and port.

11. Field-Commissioning Notes

  • Document the forwarding rules: When a maintenance engineer needs to access the LOGO! in two years, the port-forwarding map should be in the cabinet documentation. A one-line note like "Router WAN port 10001 → LOGO! 192.168.1.10:8080" saves hours of troubleshooting.
  • Use a dedicated, managed router: Consumer-grade "travel routers" work but often lack NAT timeout controls and have aggressive idle disconnects. Industrial firewalls (e.g., Siemens SCALANCE, Phoenix Contact mGuard) support deterministic NAT.
  • Lock the LOGO! configuration: Once the network settings are correct, set a LOGO! program password to prevent accidental changes from the device menu.
  • Avoid double-NAT: If the engineering network already uses NAT at its boundary, adding a second NAT layer at the LOGO! can break discovery. Use routable addressing or place the dedicated router in bridge mode where possible.
  • Monitor NAT sessions: Some routers log dropped sessions. If the S7 connection drops during long-running operations, the router may be aging out the NAT entry. Configure TCP keep-alives in the .NET application to maintain the session.

12. Frequently Asked Questions

What TCP port does the Siemens LOGO! 0BA8 use for S7 communication?

The LOGO! 0BA8 listens on TCP port 102 using ISO-on-TCP (RFC 1006) for S7 communication, and on TCP port 8080 for the integrated web server. Both ports are fixed in firmware and cannot be remapped from the device menu.

Can I change the LOGO! 0BA8 communication port number?

No. The LOGO! 0BA8 does not expose a port-remapping parameter. To reach the LOGO! on a different external port (such as 10001), place a dedicated router between the engineering network and the LOGO! and configure port forwarding from the external port to the LOGO!'s internal port 8080 (or 102 for S7 data exchange).

How do I identify whether my LOGO! is generation 8 (0BA8)?

Inspect the order number printed on the device label. The part number 6ED1052-1MD08-0BA0 ends with 08-0BA0; the embedded 08 identifies it as a 0BA8 (LOGO! 8) unit. The trailing 0BA0 is a production designator, not the generation. Only 0BA7 and 0BA8 support Ethernet.

Which .NET library should I use to communicate with a LOGO! 0BA8 from Visual Studio?

The S7.NET library (a managed wrapper around the open-source Snap7 C library) is the most widely used option. Set the CpuType to Logo0BA8, the IP to the LOGO! or its router's WAN address, and the port to 102 (direct) or the externally forwarded port. For HTTP/web-server variable access, use the standard System.Net.Http.HttpClient against port 8080.

Does the LOGO! 0BA8 support DHCP?

No. The LOGO! 0BA8 does not implement a DHCP client. The device must be assigned a static IP address through its on-device menu (Setup → Network → IP Address) or via LOGO! Soft Comfort. DHCP is unavailable in the firmware.

Why does my Visual Studio sample fail to connect on port 10001?

The sample code targets port 10001 because it assumes a port-forwarding rule is in place (external 10001 → internal 8080). The LOGO! itself never listens on 10001. Either set up the port-forwarding rule on a dedicated router, or modify the sample to connect to the LOGO!'s real IP and port 8080 (or 102 for S7).

Back to blog