Siemens MAG 5000 ###### Error: Totalizer Reset and Noise Fix

David Krause24 min read
Process ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

SITRANS F M MAG 5000 Flowmeter: Resolving the ###### Display and Erroneous Totalizer Count

The Siemens SITRANS F M MAG 5000 is a 4-wire electromagnetic flow transmitter paired with MAG 1100, MAG 3100, and MAG 5100 W sensors in water, wastewater, chemical, food/beverage, and process industries. One of the most frequently reported field issues is the appearance of ###### on the front display paired with a totalizer that continues to count even when the line is genuinely idle. This reference explains why both symptoms occur, how to reset each totalizer independently, and the electrical and parameter checks required to stop the phantom count. The procedures apply to firmware revisions 2.00 through 4.05 of the MAG 5000/MAG 6000 HART transmitter family.

1. Problem Statement and Field Symptoms

The reported symptom set is consistent across multiple installations:

  • Front display shows ###### instead of a numeric flow rate or totalizer value.
  • Totalizer continues to advance even with upstream and downstream block valves closed (no flow).
  • Performing a totalizer reset clears the count temporarily, but ###### returns within seconds and the count resumes.
  • Low flow cut-off is left at the factory default of 1.5% of Qmax.
  • No fault code (F-NN) appears in the status window, only the overflow hash.

The two symptoms are independent failure indicators: ###### is a display-range overflow of an 8-digit totalizer register, while the drifting totalizer indicates that the flow signal channel is non-zero when it should be zero. Treat both as separate root causes; fixing the totalizer does not necessarily clear the hash display, and clearing the hash display does not stop a noisy flow channel.

Important: The MAG 5000 front display always shows one of four windows: Flow Rate, Totalizer A, Totalizer B, or Tag/Status. Confirm which window shows ###### by pressing the ▲ navigation key to scroll through windows. The hash character has different implications on each window, and the same display pattern can be caused by saturation of either the instantaneous flow register or one of the two totalizer registers.

2. SITRANS F M MAG 5000 Display Architecture

The MAG 5000 transmitter uses a 3-row, 16-character alphanumeric display. Each row has its own meaning and behaves differently when the value overflows. The four windows are accessed in sequence using the up arrow key.

MAG 5000 display windows and ###### behavior
Window What it shows Behavior at overflow
Flow rate Instantaneous flow in configured engineering units (m³/h, L/s, kg/min, etc.) If flow exceeds 9,999,999 in current unit + decimals, display shows ######. Indicates the value is outside the configured range or Qmax is set too low.
Totalizer A Cumulative flow, 8-digit register, configurable direction (forward, reverse, net) When the register exceeds 99,999,999 units, the display shows ###### and stops incrementing until reset.
Totalizer B Cumulative flow (forward/reverse/net), 8-digit register, independently configurable Same behavior as Totalizer A; the two totalizers do not share registers.
Status Tag, error code, HART short tag, batch status Does not display ######; shows F-NN (fault) or W-NN (warning) instead. This window is the authoritative source for diagnostic codes.

The 8-digit totalizer overflow is the most common cause of ###### in field reports. Each totalizer has 99,999,999 counts available, with automatic decimal placement based on configured engineering units. If the application flow is, for example, 50 m³/h, the totalizer fills in 8,333 hours, or roughly 347 days. In leak detection, batching, or any application without periodic reset, the register will eventually saturate. After saturation, the totalizer stops incrementing until reset, but the display remains pinned at ###### to indicate the register has been clipped.

3. Root Cause Analysis

Three independent causes can produce the reported symptom set. Diagnose all three before returning the meter to service. A reset that only addresses the display symptom will not fix the phantom-count issue, and a noise fix that does not reset a saturated register will not clear the hash display.

3.1 Saturated Totalizer Register

The totalizer has accumulated more than 8 digits and is parked at ######. This is a normal end-of-life event for an unreleased totalizer. The flow channel may be operating correctly; the issue is purely cosmetic until reset. A reset returns the register to 0.0 and resumes counting.

3.2 Phantom Flow Signal (No-Flow Drift)

With the line blocked, the flow channel should output exactly zero. If the totalizer continues to integrate, the sensor is delivering non-zero counts from one of the following causes:

  • Electrode noise from poor grounding. MAG 5000 sensors must be installed with equipotential bonding. Without it, the electrodes pick up 50/60 Hz mains hum or VFD common-mode noise, integrated as low-level flow.
  • Partially filled pipe. If air pockets or voids exist upstream or downstream of the sensor, the electrodes intermittently see liquid and read the air-liquid interface as flow.
  • Air entrainment. Bubbles crossing the electrodes register as flow peaks. Typical sources: pump cavitation, vertical pipe runs with insufficient backpressure, recently drained and refilled lines.
  • Contaminated electrodes. Oil, grease, scale, or magnetite buildup creates a DC offset on the electrode pair, interpreted as flow even with stationary liquid.
  • Coil driver fault. If the magnetizing current is unstable or the coil driver output is asymmetric, the excitation waveform generates spurious electrode readings.
  • Cross-talk or ground loop from parallel signal cables. Long cable runs in shared conduit with power cables inject common-mode noise.

3.3 Misconfigured Suppression

If the low flow cut-off is set to 0% and empty pipe detection is OFF, the transmitter does not suppress small signals. Even sub-m/s drift from electrical noise registers as flow and is integrated into the totalizer. The default 1.5% of Qmax is designed to suppress thermal noise and minor pickup, but a marginal installation with significant EMI may require 3-5% cut-off to fully suppress drift.

4. Prerequisites and Tools

Required tools and reference documents
Item Specification / Use
MAG 5000 keypad access Local operator password (default 1000); the service-level password is 4-digit and configurable
Multimeter (true RMS, 0.1 mV resolution) For electrode noise voltage, ground continuity, and supply voltage
Clamp-on ammeter or in-loop multimeter For 4-20 mA loop current verification at 0% and 100%
HART communicator or SIMATIC PDM Optional; recommended for parameter backup and totalizer reset. PDM v9.0+ supports MAG 5000 HART 5 and HART 7 device revisions.
Megohmmeter (500 V DC) For electrode-to-ground insulation test; expect > 100 MΩ
Reference document Siemens Industry Online Support - SITRANS F M MAG 5000 Operating Instructions
Product page SITRANS F M Electromagnetic Flow Measurement
Process instrumentation overview Siemens Process Instrumentation Portfolio

5. Totalizer Reset Procedure (Menu 3)

The MAG 5000 has two independent totalizers (A and B). Field reports that reset did not clear the issue almost always refer to one of the totalizers being reset while the other continues to overflow. Both must be cleared to clear all ###### indications on the totalizer windows.

5.1 Local Keypad Reset

  1. Press ENTER to enter the main menu. The display shows the first menu number.
  2. Use ▲ / ▼ to navigate to menu 3 (Totalizers) and press ENTER.
  3. Select 3.1 (Totalizer A) or 3.2 (Totalizer B) and press ENTER.
  4. Choose RESET (clears to zero) and press ENTER.
  5. Enter the operator password (factory default 1000) using the arrow keys and press ENTER.
  6. Confirm YES at the prompt. The totalizer returns to 0.00 in the configured unit.
  7. Repeat steps 3-6 for the second totalizer. Verify both displays show numeric values after reset.
Password lockout: If the user-level password has been changed and forgotten, the master password is fixed in the firmware and is not user-recoverable. A factory reset (menu 6) is required, which erases all configuration including Qmax, units, calibration, and outputs. Back up the configuration to SIMATIC PDM or a HART DD file before any factory reset. The backup can be written back to the device after the reset.

5.2 HART Reset via Universal and Common Practice Commands

From a HART master, read totalizers with the following universal and common-practice commands:

Command 0:  Read unique identifier (manufacturer 0x005A, device type 0x0013)
Command 3:  Read PV (flow) and loop current
Command 13: Read dynamic variables (returns PV, SV, TV, FV with units)
Command 14: Read PV with current and percent of range
Command 48: Read additional device status (bit flags indicate totalizer A/B overflow)
Command 55: Read additional device variables (slot-based diagnostics)

To reset via HART, use SIMATIC PDM (recommended):

  1. Open PDM and connect to the device. Use the device tag or poll address (default 0 for point-to-point).
  2. Navigate to Device → Reset Totalizer A or Reset Totalizer B from the device menu.
  3. Confirm. PDM prompts for write protection; enter password 1000 if required.
  4. After reset, read command 48 and confirm the overflow bit is cleared for both totalizers.

5.3 Preset Value vs Reset vs Hold

The MAG 5000 supports three operations on each totalizer. Choose the operation that matches the field requirement.

Totalizer operations in menu 3
Operation Effect Use case
RESET Sets totalizer to zero Clearing an overflowed register; new billing cycle; commissioning
PRESET Sets totalizer to a configurable starting value (e.g., 1,000,000) Service continuation; replacing a previous meter; maintaining a long-running cumulative value
HOLD Freezes the current value; no further counting Reading value during maintenance; stopping accumulation during calibration
RESUME Continues from held value Returning to operation after a hold

6. Grounding and Electrical Noise Diagnostics

Phantom flow is almost always an electrical issue, not a meter issue. The Faraday law that governs the MAG 5000 measures induced voltage on the electrodes. Any voltage that is not proportional to flow registers as flow. The dominant noise sources are ground loops and 50/60 Hz mains pickup. The MAG 5000 uses bipolar pulse excitation at approximately 12.5 Hz (with 50 Hz mains) or 15 Hz (with 60 Hz mains) specifically to reject line-frequency noise, but this rejection is finite and breaks down with severe noise.

6.1 Grounding Topology Requirements

The sensor and adjacent piping must share a common ground potential. The minimum wiring is:

  • Equipotential bonding strap between sensor flanges and adjacent pipe flanges. Use a 16 mm² (6 AWG) copper braid or stranded cable, as short as practical.
  • Grounding rings (for lined pipes with non-conductive fluid) or grounding electrodes between the sensor and pipe.
  • Functional Earth (FE) terminal on the transmitter connected to the same ground as the adjacent piping.
  • Cable shield terminated at the transmitter end only; do not bond both ends (this creates a ground loop through the shield).
  • PE/ground conductor in the supply cable sized per local electrical code (typically 1.5 mm² / 16 AWG minimum).
MAG 5000 Grounding and Shield Topology Pipe (upstream) Sensor (MAG 1100/3100/5100W) Pipe (downstream) Equipotential bonding (16 mm² braid) MAG 5000 Transmitter Earth ground (PE) Functional Earth (FE) Flange bolt Flange bolt

6.2 Measurement Procedure

  1. Isolate the meter from the process (close block valves upstream and downstream; depressurize if necessary for electrode impedance testing).
  2. With the line full of stationary liquid, measure the AC voltage between each electrode and the equipotential ground strap with a true-RMS multimeter. Acceptable noise level is below 5 mV RMS at 50/60 Hz. Readings above 20 mV indicate severe grounding or shielding issues.
  3. Measure the resistance between each electrode and the equipotential ground strap with a megohmmeter at 500 V DC. Acceptable value: greater than 100 MΩ. Values below 1 MΩ indicate water ingress into the sensor housing or electrode coating.
  4. Measure the resistance between the two electrodes. Expect 5-50 kΩ for clean water at typical conductivity (200-1000 µS/cm). Values outside this range indicate contamination, scaling, or open-circuit failure.
  5. Measure the DC resistance of the magnet coil between terminals 81 and 82. Expect 40-120 Ω depending on sensor size; refer to the sensor nameplate. Open or shorted coil requires sensor replacement.

6.3 Cable Routing

Route the electrode and coil cables in a dedicated conduit, separated from power cables by a minimum of 200 mm (8 in) or by a grounded metal partition. Never run the sensor cable in the same tray as VFD output cables. If the installation is in a VFD-rich environment, use a double-shielded cable such as Siemens 6XV1830 series or equivalent. Maximum cable length between sensor and transmitter: 100 m for standard cable, up to 1000 m with special low-capacitance cable. Voltage drop on the coil circuit becomes the limit at long distances.

6.4 Common EMI Sources in Industrial Environments

Typical noise sources and their signatures
Source Frequency Signature on electrode voltage Mitigation
50/60 Hz mains pickup 50 or 60 Hz Sine wave, 1-50 mV RMS Equipotential bonding, proper shield termination
VFD common-mode 2-16 kHz switching + harmonics High-frequency burst, 10-200 mV peak Double-shielded cable, separation from VFD cables, VFD output filter
Welding equipment DC + transient Random high-energy spikes Suspend flow measurement during welding; relocate welder
Ground loop (multiple grounds) 50/60 Hz Sine wave proportional to ground potential difference Single-point grounding at the transmitter; isolate shield at sensor end
Large motor starting 50/60 Hz + subharmonics Brief transient burst Damping time constant increase, surge protection on supply

7. Parameter Configuration: Low Flow Cut-Off and Empty Pipe

Two suppression parameters stop small signals from reaching the totalizer. The first is a software threshold; the second is an automatic physical sensor check.

Suppression parameters in menu 1
Parameter Menu path Factory default Range Effect
Flow units 1.1 m³/h Configurable Engineering unit for flow display and totalizer
Qmax (full-scale) 1.3 Sensor-dependent 0.1 to 10 m/s velocity Defines 100% flow and 4-20 mA full-scale current
Damping 1.4 10.0 s 0.1 to 100 s Time constant for the flow signal; suppresses transients
Low flow cut-off 1.5 1.5% of Qmax 0.0 to 9.9% of Qmax Below threshold, flow display and outputs are forced to zero
Empty pipe detection 1.6 ON ON / OFF Detects empty pipe condition and forces flow to zero
Low flow alarm 1.7 OFF ON / OFF Indicates when flow drops below cut-off; visible only via HART/PDM
Density (mass units) 1.8 1000 kg/m³ Configurable Used when mass units are selected

For a process with known low-end noise of 1-2% of Qmax, set the low flow cut-off to 3-5% of Qmax to ensure margin. For batch applications where small quantities matter, leave at 1.5% but address the noise source at its origin (grounding, cable routing, EMI suppression). Setting cut-off too high suppresses legitimate low flow and reduces measurement accuracy below the threshold.

Damping interaction: Increasing damping from 10 s to 30 s or 60 s reduces noise-induced totalizer increments, but it slows response to legitimate flow changes. Never set damping higher than 1/10th of the process time constant. For a batch process with 60 s fill time, do not exceed 6 s damping.

8. Empty Pipe Detection and Sensor Health Verification

Empty pipe detection (EPD) relies on a third electrode (or a measurement between the existing electrodes at a special frequency). When the pipe is full, the electrode is in contact with conductive liquid and the impedance to ground is low. When empty, the impedance is high. The transmitter reads this impedance and forces flow to zero when the threshold is crossed.

8.1 Enabling and Tuning EPD

  1. Navigate to menu 1.6 and set to ON.
  2. With the pipe confirmed full (no air pockets, no voids), navigate to 5.4 (EPD calibration) and select CALIBRATE. The transmitter learns the full-pipe impedance and stores it in non-volatile memory.
  3. Confirm by draining the test section (or simulating empty pipe with a known test jig). The flow display should drop to zero within 30 s and the status window should show W-25.
  4. Refill the pipe; flow display should resume within 30 s of refilling.

If EPD cannot be calibrated, the third electrode is contaminated, the EPD cable is damaged, or the process fluid conductivity is below 5 µS/cm. For high-purity water, condensate, or non-conductive fluids (oils, hydrocarbons without water content), EPD will not function reliably and should remain OFF. In these services, an external level switch or different flow technology (Coriolis, vortex) is preferable.

8.2 Sensor Coil and Electrode Health Diagnostics

Using HART command 55, read the following diagnostic variables. These are not visible on the front display and require PDM or a HART master.

Diagnostic variables available via HART command 55
Variable Slot Healthy range Action if out of range
Electrode resistance 1 5-50 kΩ (water), 50 kΩ-2 MΩ (low conductivity) Clean electrodes, check conductivity
Coil current 2 Within ±10% of nominal (per sensor nameplate) Check coil cable, replace sensor
Coil temperature 3 -40 to +180 °C (sensor-dependent) Reduce process temperature or specify high-temp sensor
Electrode temperature 4 -40 to +180 °C (sensor-dependent) Process health, liner integrity
Empty pipe impedance 5 < 100 kΩ full, > 1 MΩ empty Recalibrate EPD; inspect electrode
Sensor electronics temp 6 -20 to +70 °C ambient Improve enclosure ventilation

9. Current Loop, Pulse Output, and HART Verification

After clearing the totalizer and addressing the noise source, verify the outputs reflect the corrected flow channel. A 4-20 mA loop that reads 4.00 mA at zero flow is the strongest indication that the noise source has been addressed.

9.1 4-20 mA Loop Check

  1. Open the current loop at the receiver (or insert a multimeter in series at the transmitter terminals).
  2. Force zero flow (close block valves).
  3. Read current. Expect 4.00 mA ±0.02 mA. If higher than 4.02 mA, the channel is still drifting.
  4. Apply a known flow (use a calibrated reference meter or full-scale Qmax from a test pump). Verify the current matches PV = (Flow/Qmax) × 16 + 4 mA within ±0.1% of span.
  5. For HART, verify the loop has at least 250 Ω total resistance (250 Ω is the minimum for reliable HART communication).

9.2 Pulse Output Check

The pulse output (terminal 41/42) is configured in menu 2.3. Verify the pulse units match the totalizer units. If they are out of sync, the totalizer is integrating correctly but the pulse is on a different scale, leading to counting errors at the receiver PLC or flow computer. Pulse weight is configured as volume per pulse (e.g., 1 m³ per pulse, 10 L per pulse). Maximum pulse frequency is 5 kHz on the standard output; exceeding this causes pulse-stretching or missed pulses.

9.3 HART Verification

From a HART master, run the following sequence:

  1. Command 0: Read unique identifier. Verify manufacturer code 0x005A (Siemens) and device type 0x0013 (MAG 5000 HART 5) or 0x0014 (MAG 6000).
  2. Command 3: Read PV and SV. PV should be 0 with no flow; SV is totalizer A. TV and FV are totalizer B and flow percent of range.
  3. Command 13: Read dynamic variables. Verify loop current matches the multimeter reading.
  4. Command 14: Read PV with current and percent of range.
  5. Command 48: Read additional device status. Look for bit flags indicating totalizer A overflow, totalizer B overflow, empty pipe, and out-of-range flow.
  6. Command 55: Read additional device variables for electrode resistance, coil current, and EPD impedance (slots vary by DD version).

9.4 Burst Mode and Multidrop Considerations

If the meter is in burst mode, the transmitter continuously publishes HART data. This increases current loop noise and can affect the 4-20 mA signal. Disable burst mode for routine verification. If the meter is on a multidrop network (poll address 1-15), the current loop is fixed at 4 mA and cannot be used for flow transmission. Confirm the poll address is 0 for point-to-point analog + HART operation.

10. Fault Code Reference Table

During commissioning, the MAG 5000 status window may display fault (F-NN), warning (W-NN), or service (C-NN) codes. Use the table below to interpret them.

MAG 5000 fault and warning codes (HART 5, device rev 2)
Code Category Description Action
F-22 Fault Flow exceeds 130% of Qmax Reduce flow or increase Qmax setting
F-23 Fault Flow exceeds 150% of Qmax (hard saturation) Same as F-22; check pipe for blockage
F-26 Fault Sensor error: coil or electrode Check coil resistance, electrode resistance
F-80 Fault Converter error Power cycle; if persistent, replace transmitter
W-22 Warning Flow > 105% of Qmax Investigate process upsets
W-25 Warning Empty pipe detected Fill pipe; check EPD calibration
W-30 Warning Totalizer A overflow Reset totalizer A
W-31 Warning Totalizer B overflow Reset totalizer B
W-32 Warning DD version mismatch Update HART DD in PDM
W-50 Warning Pulse output overflow Reduce pulse weight; verify max frequency
C-01 Service Calibration in progress Wait for completion
C-02 Service EPD calibration in progress Wait for completion

11. Sensor Compatibility and Variant Considerations

The MAG 5000 transmitter interfaces with three sensor families. The grounding and noise considerations apply to all, but the mechanical installation requirements differ.

MAG 5000 sensor family overview
Sensor Size range Liner Typical service Special notes
MAG 1100 DN 2 to DN 100 Ceramic (Al₂O₃) Food, beverage, pharma, low conductivity Ceramic liner is highly insulating; grounding rings mandatory for conductive fluids
MAG 1100 F DN 15 to DN 100 PTFE Chemical, aggressive media PTFE liner requires grounding rings; max temperature 130 °C
MAG 3100 DN 15 to DN 2000 EPDM, PTFE, NBR, hard rubber Water, wastewater, process Most common sensor; grounding via flanges typical
MAG 3100 HT DN 15 to DN 300 PTFE High temperature process Up to 180 °C continuous; requires high-temp cable
MAG 5100 W DN 15 to DN 1200 EPDM Water, irrigation, district metering Burial-rated (IP68); no separate transmitter required if integral

For lined sensors (PTFE, ceramic) with non-conductive process fluids, the fluid does not provide an electrical path to ground. Grounding rings (conductive rings installed between the sensor flange and the adjacent pipe flange) are mandatory. Without them, the electrode signal has no reference and the meter drifts or reads zero. For water and other conductive fluids, the fluid itself provides the ground path and grounding rings are optional, but flange bonding is still required.

12. Verification and Commissioning Checklist

After completing the reset and diagnostic steps, walk through this checklist before returning the meter to service. Each item should be confirmed and signed off.

  1. Both totalizers reset to zero. Display confirmed via HART commands 13/14 and front display.
  2. With block valves closed and the line full, totalizer does not advance for 10 minutes.
  3. Flow rate display reads 0.0 in current engineering units.
  4. 4-20 mA loop reads 4.00 mA ±0.02 mA with no flow.
  5. Electrode noise measured below 5 mV RMS at line frequency (true-RMS multimeter).
  6. Grounding resistance measured below 1 Ω between sensor flange and earth ground.
  7. Electrode-to-ground insulation measured above 100 MΩ at 500 V DC.
  8. Empty pipe detection is enabled and calibrated (if process fluid is conductive > 5 µS/cm).
  9. Low flow cut-off is at or above the noise floor; default 1.5% of Qmax minimum.
  10. Damping is appropriate for process time constant (typically 5-30 s).
  11. HART multidrop poll address is 0 for point-to-point, 1-15 for multidrop.
  12. Operator password has been changed from factory default 1000.
  13. Configuration has been uploaded to PDM as a backup file.
  14. Pulse output is configured to match totalizer units.
  15. Alarm relay (if used) is configured for the appropriate trigger (empty pipe, low flow, totalizer overflow).

13. Preventive Measures and Long-Term Maintenance

To prevent recurrence of the ###### and phantom-count symptoms, schedule the following in the maintenance plan.

  • Monthly: verify totalizer A and B values, confirm they are within expected process range; check HART burst or poll data for the totalizer overflow bit (command 48).
  • Quarterly: measure electrode resistance and ground resistance; verify EPD calibration by simulating an empty pipe if the process allows.
  • Annually: perform zero calibration with the line full and the flow at a known zero (e.g., isolated block valves). The MAG 5000 auto-zero is in menu 5.1 and takes 60 s. Verify the zero after a known flow is re-established.
  • After any process change (new pump, new VFD, new pipe material, new valve): re-verify grounding topology and re-check EPD calibration. VFD installation in particular introduces high-frequency common-mode noise that often requires a dedicated drive output filter.
  • During plant shutdowns: inspect sensor electrodes for coating or fouling; clean per the sensor material datasheet (ceramic electrodes tolerate aggressive cleaning; PTFE liners are softer and require care).
HART device revision note: The MAG 5000 HART 5 implementation has device revision 2, while MAG 6000 (added with HART 7 support) is device revision 3. Some older PDM versions default to device revision 1 DD; the device revision mismatch generates W-32. Use the latest DD from the Siemens support portal to avoid this and to access all diagnostic variables via command 55.
Firmware update path: The MAG 5000 firmware is field-upgradeable via SIMATIC PDM using the infrared interface on the display or the HART interface. The latest firmware as of the current production cycle is 4.05. Updates are available through Siemens Industry Online Support and require the device to be in service mode (password-protected).

14. Summary of the Repair Path

MAG 5000 ###### / Phantom Count Diagnostic Flow Symptom: ###### on display, totalizer counts with no flow Step 1: Identify which display window shows ###### (scroll with ▲ key) Totalizer A or B window: ###### Flow rate window: ###### Reset totalizer A and B (menu 3.1, 3.2) Check Qmax setting; verify unit range Both paths converge: verify grounding, EPD, low flow cut-off, 4-20 mA loop

What does ###### mean on the MAG 5000 display?

The ###### symbol on a MAG 5000 display indicates that the value (flow rate or totalizer) has exceeded the 8-digit display capacity of 99,999,999. For totalizers, the register is saturated and must be reset via menu 3.1 (Totalizer A) or 3.2 (Totalizer B). For flow rate, the instantaneous value is out of the configured display range; verify that engineering units and Qmax are set correctly. Confirm which window shows the hash by pressing the up arrow to scroll through the four display windows.

Why does my MAG 5000 totalizer keep counting with no flow?

The most common cause is electrical noise on the electrode signal from poor grounding or electromagnetic interference. Verify equipotential bonding between the sensor flanges and adjacent pipe (16 mm² copper braid minimum), confirm the cable shield is terminated at the transmitter end only, and ensure signal cables are routed at least 200 mm away from VFD or power cables. Enable empty pipe detection (menu 1.6) and raise the low flow cut-off from the 1.5% default to 3-5% of Qmax to suppress residual noise that is integrated into the totalizer.

How do I reset both totalizers on a MAG 5000?

From the keypad, press ENTER to access the menu, navigate to menu 3 (Totalizers), select 3.1 for Totalizer A or 3.2 for Totalizer B, choose RESET, enter the operator password (factory default 1000), and confirm. Repeat for the second totalizer. Resetting only one totalizer does not affect the other; both must be cleared if both have overflowed. After reset, verify by pressing the up arrow to scroll to the totalizer window; the value should be 0.00 in the configured unit.

What is the default password for the MAG 5000?

The factory default operator password for the MAG 5000 is 1000. The service-level password is 4-digit and configurable. The master password is fixed in firmware and is not user-recoverable; a forgotten user password requires a factory reset (menu 6) which erases all configuration including Qmax, units, calibration, and outputs. Always back up the configuration to SIMATIC PDM or to a HART DD file before any reset operation. The backup can be written back to the device after the reset is complete.

What is the factory default low flow cut-off?

The factory default low flow cut-off on the MAG 5000 is 1.5% of Qmax. The range is 0.0 to 9.9% of Qmax. Below this threshold, the flow display and 4-20 mA output are forced to zero, but the totalizer may still increment if the signal is above zero but below the cut-off threshold. For processes with significant electrical noise, raise the cut-off to 3-5% of Qmax to stop noise from being integrated into the totalizer, and address the noise source at its origin (grounding, cable routing, EMI suppression).

What is the difference between the MAG 5000 and MAG 6000?

The MAG 5000 is the standard 4-wire electromagnetic flow transmitter with basic HART 5 communication, while the MAG 6000 adds HART 7 support, advanced diagnostics including trend logging, batch control functions, and additional input/output slots. The hardware platform is similar and the menu structure is largely identical, so this article applies to both with the same reset and parameter procedures. The MAG 6000 also supports PROFIBUS PA and FOUNDATION Fieldbus variants with different device type codes (0x001A for PROFIBUS).

Can I clear ###### without resetting the totalizer value?

No. The ###### on a totalizer window is the visual representation of a saturated register; the only way to clear it is to reset the totalizer to zero or preset it to a new starting value via menu 3.1 or 3.2. If you need to preserve the cumulative value across a service event, use the PRESET function to set the totalizer to a known starting value (e.g., 1,000,000) and document the previous value externally before the reset. PDM can read and log the pre-reset value before issuing the reset command.

Back to blog