Siemens Masterdrive MC Plus F006 Overvoltage Fault Root Cause

David Krause15 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

The Siemens MASTERDRIVES MC PLUS (6SE70/6SE71 series with Motion Control firmware, e.g., version 1.6) reports fault F006 (overvoltage) while the actual DC link voltage at the bus capacitors is normal (~560 V DC for a 400 V class unit). The drive keypad, r006 parameter, and SIMOVIS/DriveMonitor may report an inflated value such as 805 V DC, and the indication persists even after the DC supply is disconnected. The drive typically trips to OFF2 or OFF3, and the motor coasts to a stop. In some installations a companion fault F008 (DC link undervoltage) appears on the same or on parallel drives after a delay of several hours of operation.

F006 on MASTERDRIVES is a latching, hardware-monitored fault sourced in the DC link measurement chain. It cannot be acknowledged until the internal monitoring logic no longer flags an overvoltage condition. The root cause is almost always one of the following, ranked by frequency observed in field service:

  1. DC link voltage measurement circuit drift or contamination (false F006).
  2. Real overvoltage caused by regenerative energy with inadequate dissipation path.
    1. Braking chopper not present, disabled, undersized, or set to a high activation threshold.
    2. Ramp-down time too short for the load inertia / kinetic energy.
    3. Missing or failed braking resistor.
  3. Encoder feedback loss interpreted as motor stall, forcing the drive to assume regenerative behavior.
  4. Udc-max controller (P515) disabled while regen transients are present.
  5. DC link pre-charge or measurement PCB failure on the small-form-factor units with two boards.
Safety: Capacitors in the MASTERDRIVES DC link retain lethal voltage for the discharge time specified on the front of the unit (typically 5 minutes after mains removal on a 400 V class device). Always verify zero energy with a category-rated meter at terminals C and D before opening the cabinet, touching busbars, or inserting a measurement shunt. A stored 805 V reading is consistent with a charged DC link; the same voltage cannot be "generated" by the drive once supply is removed unless the measurement is being taken on the energized signal-conditioning side of the isolation amplifier.

Affected Equipment and Configuration

MASTERDRIVES MC PLUS is the motion-control variant of the SIMOVERT MASTERDRIVES family, distinguished from the standard VC PLUS by the integrated positioning, synchronization, and free-function-block firmware. The 6SE70xx series covers frame sizes 1 (smallest) through 6 (largest), with the F006 measurement-circuit pathology most often reported on the compact, two-PCB chassis (frame size A/B, types 6SE7016/6SE7018 and similar).

Key identifiers for the F006-affected MASTERDRIVES MC PLUS population
Parameter Typical value Notes
MLFB example 6SE7016-1EA61 1.6 kW class, 400 V, 2-quadrant variant
Firmware 1.60 / 1.61 / 1.62 Motion Control (MC) firmware; field-relevant bugs fixed in 2.x and 3.x
Nominal DC link 540-560 V DC For 400 V AC supply at ±10% tolerance
Hardware trip level ~760-820 V DC Hardware monitor threshold; F006 trips at this envelope
Chopper turn-on (P515/P516) 670-720 V DC Configurable via P516 (turn-on) and P517 (turn-off) on VC PLUS; MC PLUS uses P515 family

Fault Code and DC Link Behavior

F006 is defined in the MASTERDRIVES fault list as DC link overvoltage. F008 is its undervoltage counterpart. Both faults can be:

  • Real: The DC link voltage actually exceeds (F006) or falls below (F008) the hardware threshold.
  • Indicated: The hardware is sound but the analog measurement chain reports a wrong value.

Real vs. indicated is the first diagnostic branch. The fastest way to split the two is to compare the keypad/r006 reading to a direct, isolated measurement at terminals C (+) and D (-) on the drive. The disagreement reported in the field case (560 V measured vs. 805 V indicated) places the fault firmly in the indicated branch on first pass; the second pass must then confirm whether the drive's braking system is actually capable of holding the link below the trip envelope under worst-case regen.

F006 vs. F008 diagnostic matrix
Symptom F006 (Overvoltage) F008 (Undervoltage)
DC link nominal 540-560 V (400 V class) 540-560 V (400 V class)
Trip envelope > ~760 V hardware; 1.18 × r006 nominal via firmware < 380 V (firmware); 1.1 × r006 nominal
Common real cause Decel regen without chopper / brake IGBT open / brake resistor failed Supply dip, blown pre-charge, undersized line, blown rectifier
Common indicated cause DC measurement op-amp drift, contaminated PCB, broken isolation amplifier DC measurement divider failure, broken sense wires
Recovery Acknowledge only after reading r006 < trip envelope for > 2 s Acknowledge only after mains restored and pre-charge complete

Key Parameters and Test Points

Use the following parameter set to map the drive before any invasive work. Parameters are accessed from the PMU keypad, the OP1S operator panel, or SIMOVIS / DriveMonitor over the serial USS / PROFIBUS link.

Diagnostic parameter map for F006 / F008
Parameter Description Use in F006 diagnosis
r006 DC link voltage (filtered) Compare to terminals C/D; this is the value the firmware uses for trip decisions
r008 DC link voltage raw / unfiltered Watch for ripple or step excursions during the decel that triggered the fault
P515 Udc-max controller enable / configuration If 0, controller is OFF; enabling it lets the drive extend the ramp to absorb regen
P516 Chopper turn-on threshold Adjusts the Vdc setpoint where the brake IGBT begins switching
P517 Chopper turn-off (hysteresis) threshold Lower than P516 by 10-30 V typically
P464 Ramp-down time 1 Primary deceleration ramp; lengthen if regen is the cause
P469 Ramp-down time 3 (MC firmware) Used by MC profiles for controlled stop
r029 Current controller / brake IGBT status Verify chopper IGBT is actually being gated
n001 / n002 Fault memory (last / second-to-last) Read the actual trip value captured at the instant of the F006
Terminals C and D are the standard MASTERDRIVES test points on the lower terminal strip for direct DC link voltage measurement using an isolated differential probe or a properly rated multimeter. A differential reading within ±2% of r006 confirms a healthy measurement chain. A large mismatch (e.g., 560 V vs. 805 V) confirms the indicated-fault branch and isolates the failure to the DC measurement PCB, the isolation amplifier, or the firmware's ADC handling.

Root Cause 1: Encoder-Induced False Regeneration

A slipped, contaminated, or open encoder can present itself to the speed controller as "motor not following the setpoint." The MC PLUS firmware reacts in two ways:

  1. The current controller pushes the inverter toward the demanded speed, and if the rotor is not rotating at the rate the encoder reports, the drive interprets the slip as motor regenerating into the link.
  2. The DC link rises rapidly, and if the chopper cannot sink the energy, F006 trips.

This root cause is identified by:

  • Fault occurring on the inverter side of a DC-bus-coupled system, with no faults on the line-side regenerative supply unit.
  • Trip happens during steady-state operation or even after the line contactor is opened, because the rotor's residual kinetic energy is dumped into the link through the inverter's anti-parallel diodes feeding the capacitors.
  • Encoder-related warning bits appearing in r047 (speed controller status) or r158 (encoder diagnostic) before the trip.

Resolution:

  1. Replace the encoder with a known-good unit. Verify coupling concentricity with a dial indicator (typical runout < 0.05 mm).
  2. Re-verify encoder wiring shield grounding at the drive end only, with the shield drain wire landed on the SUB-D backshell.
  3. Set the encoder gain in P150 (speed-actual source) and confirm track assignment in P151 for the MC PLUS (TTL/HTL, A/B track, marker).
  4. Capture a speed-actual trace in DriveMonitor (trace function 030 or higher) and confirm no glitches correlate with the F006 timestamp.

Root Cause 2: Braking Chopper Mis-Selection or Disabled

The chopper (braking IGBT module + external braking resistor) is the primary energy sink during deceleration. A common field defect is the chopper configured with a turn-on threshold set too high (e.g., 760 V when the hardware trips at 760 V), meaning the chopper never engages in time. Re-size the chopper to:

Chopper resizing worksheet
Variable Formula Notes
Kinetic energy, Wk 0.5 × J × ω² (J in kg·m², ω in rad/s) Use total inertia reflected to motor shaft, including load
Decel time, tdec From P464 or P469 Longer times reduce peak chopper power
Average regen power, Pavg Wk / tdec This is the power the resistor must dissipate continuously during the stop
Peak regen power, Ppeak τ × ω × Tload / 2 (worst case) Estimate with a margin of 1.5× for inertial shocks
Chopper turn-on, P516 Set ≈ 1.16 × Vdc,nom For 540 V nom, set P516 ≈ 670 V; not higher than 720 V
Chopper turn-off, P517 Set 15-25 V below P516 Provides hysteresis and prevents chopper chattering

Selection of resistor Rbr:

  • Step 1: Decide required peak power Ppeak from the table.
  • Step 2: Set Rbr = Vchopper,on² / Ppeak. Example: at 670 V on and 10 kW peak, Rbr = 670² / 10000 = 44.9 Ω.
  • Step 3: Verify continuous rating Pavg against the resistor's continuous power.
  • Step 4: Verify the chopper module's peak current: Ipeak = Vdc / Rbr must be below the IGBT module rating (typical MASTERDRIVES chopper is rated 100-300 A peak depending on frame).
If a chopper is present and the F006 still occurs, set the chopper to its lowest turn-on threshold as a diagnostic: a properly working chopper will clamp the link to a stable voltage under decel. If the link still climbs to 805 V with the chopper at its lowest setting, the chopper IGBT has failed open, the gate driver is not firing, or the resistor is open. Measure at the chopper output: if Vdc at the chopper terminals equals Vdc at the DC link, the chopper is electrically connected; if the gate signal is present at the IGBT but no current flows, the IGBT is open.

Root Cause 3: Ramp-Down Time Too Short

The MASTERDRIVES MC PLUS ramp generator uses P462-P469 (4 ramp pairs) plus the MC-specific profiles. If the mechanical decel rate is faster than the ramp generator's output, the speed controller commands negative torque and pushes the motor into regen. The simple corrective is to lengthen the decel ramp, then re-size the chopper around the new ramp:

  • P464 (Ramp-Down Time 1) is the most common target. Increase by 2× to 3× and re-test.
  • If the application cannot tolerate a long decel, use P515 Udc-max controller to auto-extend the ramp only when regen threatens to overvoltage the link.

Root Cause 4: Udc-Max Controller (P515) Disabled

P515 controls the Vdc-max regulator, an inner loop that increases the torque-producing current limit when Vdc approaches the chopper turn-on level, effectively giving the drive authority to lengthen the ramp at the precise moment the link would overvoltage. In MASTERDRIVES this is normally OFF.

P515 settings
P515 value Behavior
0 Udc-max controller OFF (default on many MC PLUS builds)
1 Udc-max controller ON, controls via torque limit
2 Udc-max controller ON, controls via ramp integrator

Setting P515 = 1 or 2 is a standard mitigation for installations where the chopper is undersized or absent but the load is constant. The drive will automatically stretch the ramp only as much as required to keep the link below the trip envelope, preserving the original fast decel when no regen is present. Always re-test the F006 trip envelope after enabling P515: if the Vdc at the link climbs above 700 V with P515 active, the controller is not configured correctly for the firmware build (P515 was redefined in 1.6x and again in 2.x; verify with the firmware-specific manual).

Root Cause 5: DC Measurement Circuit Failure (Small-Frame Units)

On the small MASTERDRIVES MC PLUS units (frame A/B, 2-PCB construction), the DC link measurement amplifier is on the power PCB adjacent to the chopper IGBT. Heat, dust, and contamination induce drift in the divider network, producing a falsely high r006. Indications:

  • Keypad shows ~700-820 V at power-up with the drive in standby, no mains.
  • r006 reading is higher than the direct measurement at terminals C/D by > 5%.
  • F006 trips on every cold start regardless of motion profile.

Resolution path:

  1. With the drive de-energized and discharged (verify with meter at C/D), remove the front cover and inspect the power PCB for dust accumulation, especially on the HV divider and around the chopper IGBT heatsink.
  2. Clean with ESD-safe vacuum and a soft, dry antistatic brush. Do not use compressed air on the populated PCB; this can drive conductive dust into the isolation gaps.
  3. Reassemble, apply control voltage only, and read r006 on the keypad. A clean PCB will typically bring the reading within ±2% of a direct measurement at C/D.
  4. If the reading remains inflated after cleaning, replace the measurement-amplifier section of the power PCB. The two-PCB units are not field-repairable at component level for this fault; the PCB assembly is the line-replaceable unit.

F008 (Undervoltage) Companion Fault

F008 on the same drive population usually indicates a different problem on the same measurement chain. When both F006 and F008 appear on the same site (different drives, same DC bus), the cause is often:

  • Supply-side problem: brownouts, undersized line impedance, weak source.
  • Pre-charge resistor / contactor wear: a high-resistance pre-charge will let Vdc fall during load steps, triggering F008 on deceleration-then-acceleration cycles.
  • DC link capacitor end-of-life: ESR rises, and a loaded link collapses faster than the firmware can ride through.

For F008, measure the line voltage under load with a true-RMS meter and compare to r025 (line voltage parameter, if configured). A drop of more than 10% at peak load confirms a supply issue; otherwise, inspect the pre-charge circuit and bulk capacitors.

Step-by-Step Troubleshooting Procedure

  1. Capture the fault memory. Read n001 through n016 before acknowledging. Record the r006 value at trip and the operating state (r047 speed controller, r156/r158 encoder diagnostic).
  2. Measure Vdc at terminals C and D with a properly rated, isolated meter. Compare to r006 with the drive in standby and again under no-load steady state.
  3. Branch decision:
    • If r006 matches the meter reading within ±2%, the measurement chain is OK and the F006 is a real overvoltage. Go to step 4.
    • If r006 disagrees with the meter, the measurement chain has failed. Go to step 6.
  4. Real overvoltage path. Verify the chopper: read r029 during a controlled decel; verify the gate signal is present at the chopper IGBT with an isolated scope probe; verify the resistor with an ohmmeter (de-energized, discharged). If absent, configure or install a chopper. If present but disabled, lower P516 to 670 V and re-test. If correctly configured, enable P515 Udc-max controller and re-test.
  5. Encoder path. Inspect the encoder and coupling. Capture a speed-actual trace. Replace the encoder if any track glitch is observed within 5 s of the F006 timestamp.
  6. Indicated-overvoltage path. De-energize, discharge, open the unit. Inspect and clean the power PCB. Re-test. If still failing, replace the power PCB assembly or send to a Siemens-authorized repair center for component-level repair.
  7. Re-test under worst-case load. Command a fast decel from rated speed to zero with full inertia. Capture r006 and r008 traces. The link should peak at no more than 720 V (chopper on) or ramp-clamped below the F006 trip point (P515 active).
  8. Document and commission. Record final P515, P516, P517, P464 settings; record chopper size and resistor; record encoder replacement details. Update the maintenance log.

Verification and Commissioning

F006 verification checklist
Check Acceptance criterion Method
DC link meter vs. r006 at standby Within ±2% Isolated meter at C/D; keypad read
DC link meter vs. r006 at rated no-load Within ±2% Same as above, with motor at rated speed, no load
Decel peak Vdc with full inertia, rated speed < 720 V (chopper on) OR clamped by P515 DriveMonitor trace on r008
Chopper current during decel Matches calculated Ppeak / Vdc Clamp-on DC current probe on brake lead
No F006 or F008 in 8 h soak test 0 events Run the production cycle, log faults
Encoder signal integrity No glitches, no slip DriveMonitor trace on encoder channels

Preventive Maintenance Notes

  • Inspect the power PCB for dust at every 12-month preventive maintenance visit. Sites with airborne contamination (paper, textile, cement) may need 6-month intervals.
  • Verify the DC link capacitors' ESR at 24-month intervals; a 20% rise in ESR or a 10% drop in capacitance is the typical end-of-life indicator.
  • Replace the encoder coupling set screw with a fresh, thread-locked fastener if the application has any vibration above 5 m/s² RMS.
  • Keep firmware at the latest field-stable version for the frame. The MASTERDRIVES MC PLUS firmware family had a 1.6 → 2.1 → 2.3 → 3.1 progression with several F006-related corrections in the 2.x line; consult the release notes for the installed build before making parameter changes.
Document references: MASTERDRIVES MC PLUS parameter list, fault code reference, and commissioning manual are available from the Siemens Industry Online Support portal (search "6SE70" or "MASTERDRIVES MC"). Always cross-check the parameter numbers (P515, P516, P517) against the firmware-specific manual for the unit; parameter definitions were reorganized between major firmware builds.

What does F006 mean on a Siemens MASTERDRIVES MC PLUS?

F006 is a hardware-monitored overvoltage fault on the DC link. The drive trips when Vdc exceeds approximately 760-820 V on a 400 V class unit, either as a real overvoltage from regenerative energy or as an indicated overvoltage from a failed DC measurement circuit. Compare r006 to a direct measurement at terminals C and D to distinguish the two cases.

Why does my MASTERDRIVES show 805 V on the keypad when the DC bus is only 560 V?

This is an indicated overvoltage caused by a faulty DC measurement amplifier, typically on the power PCB of the small two-PCB chassis. Heat, dust, or component drift inflates the reading. De-energize, discharge, and clean the PCB. If the reading remains high after cleaning, replace the PCB or send the drive to an authorized Siemens repair center.

How do I size a braking chopper and resistor for a MASTERDRIVES MC PLUS?

Calculate the kinetic energy Wk = 0.5 × J × ω² using the total inertia reflected to the motor shaft. Divide by the decel time to get the average regen power. Set the chopper turn-on (P516) to about 1.16 × Vdc,nom (e.g., 670 V for 540 V nominal). Size the resistor to R = Vchopper,on² / Ppeak, and verify continuous power against the resistor's continuous rating.

What does P515 do, and should I enable it?

P515 enables the Udc-max controller, an inner loop that automatically extends the deceleration ramp when Vdc approaches the trip envelope. Set P515 = 1 for torque-limit-based control or P515 = 2 for ramp-integrator-based control. Enable it when the chopper is undersized or absent, and verify with a worst-case decel test that the link stays below 700 V with P515 active.

Why does the drive trip F006 on a DC-bus system even though only the inverter side reports it?

The line-side regenerative supply unit is doing its job, but the inverter-side drive has its own speed controller that can push energy back into the shared DC bus. An encoder fault, a stalled motor, or an aggressive decel ramp on the inverter side can raise the bus above the F006 threshold before the chopper on the inverter side can react. Diagnose by checking for encoder warnings, lengthening the decel ramp (P464), enabling P515, and verifying the inverter-side chopper is correctly configured.

Back to blog