Siemens OP17 Serial Floppy Disk Station: FD20 Driver 6AV3982-1AF26-1AX2 (OFT) Technical Reference

The Siemens OP17 text-display HMI was paired, in many European production lines installed during the late 1990s, with a Sympat GmbH FD20 serial floppy disk station. The FD20 allowed operators and commissioning engineers to back up complete OP17 projects, archive and load recipe data sets, and clone configuration between OP17 units in the field. Because Sympat GmbH no longer exists, the device and its driver are treated as legacy hardware. The original driver order number was 6AV3982-1AF26-1AX2, designation OFT, version v4.xx for the FD20. This reference consolidates the hardware topology, the IF2 (DB-15) interface behavior, the ProTool integration sequence, LED diagnostics, recipe transfer model, and field-proven recovery paths when the original driver media is missing.

System Architecture and Hardware Topology

The OP17 + FD20 pairing is a point-to-point serial system; no hub, terminator, or multi-drop arrangement is supported by the OFT driver. The FD20 connects to the OP17's IF2 port only (not IF1, which is reserved for the engineering PC running ProTool). IF2 is a female DB-15 (DA-15) subminiature connector on the rear of the OP17 housing.

The FD20 chassis is a self-powered external enclosure containing:

  • A standard 3.5" floppy drive mechanism (720 KB or 1.44 MB media)
  • A Sympat-proprietary controller board implementing the OFT link layer
  • A Siemens-specific RS-232 / serial interface on a DB-15 male connector
  • A single front-panel status LED (red or green, depending on FD20 hardware revision)

Field installations show the original Sympat cable is a shielded DB-15 to DB-15 (1:1) cable, generally 1.5 m to 3 m in length. No handshaking lines other than those used by the OFT driver are required. Power is supplied to the FD20 through a separate 24 V DC inlet; the FD20 does not draw operating power from the OP17 IF2 port.

IF2 (DB-15) Interface on the OP17

The OP17 IF2 port was designed primarily to support Siemens "option field" devices such as:

  • The Sympat FD20 serial floppy disk station
  • External serial printers (Siemens option class)
  • Certain barcode readers operating in transparent mode

The 6AV3982-1AF26-1AX2 OFT driver is a ProTool option driver, not a firmware update. OFT in Siemens order-number parlance designates the device driver media (a 3.5" floppy or CD shipped with the ProTool option pack) rather than a Siemens firmware version. The driver archive contains the .pdr (ProTool Driver) file that ProTool imports when configuring the OP17's serial port. The driver also includes a ProTool add-in and a small diagnostic test-pattern generator used during commissioning.

Driver Order Number Decoding

The string 6AV3982-1AF26-1AX2 decodes by Siemens convention as follows:

Segment Value Meaning
6AV3 Product family prefix Siemens HMI product family (legacy SIMATIC HMI)
982 Accessory group Option / accessory group
1AF26 Driver designation 26 = OFT family, AF = serial-floppy class
1AX2 Media format Floppy 3.5", English-language documentation
OFT Driver class ProTool OFT (Option Floppy Terminal) device driver
Engineers ordering the driver from Siemens at the time received a 3.5" floppy disk labeled with the order number and a multi-language printed installation guide. The disk contained the OFT driver, a ProTool add-in for the driver, and diagnostic test patterns. If the disk is lost, the order number is the primary key for sourcing a replacement.

FD20 LED Behavior

The FD20 chassis has a single front-panel LED. Two distinct operating states are observable in field installations of the v4.xx driver:

State LED Pattern Meaning
Power-up / boot LED on for ~10 s, then off FD20 controller is reading the inserted disk and indexing the file allocation table
Recipe read by OP17 LED on for ~2 s OP17 has requested a recipe record; FD20 is streaming the record to the OP17
Idle, disk present LED off Standby, awaiting OP17 command
Idle, no disk LED off Standby, no media
Write to disk LED on, irregular flicker OP17 is writing a recipe or backup to the floppy
Fault LED rapid blink (≤ 5 Hz) Controller self-test failure or unsupported media

These timings are useful as a "the system is alive" check before deeper diagnostics. The 10-second boot delay and 2-second read window are the most reliable indicators that the OFT driver and the FD20 controller are negotiating correctly.

ProTool Integration Sequence

ProTool is the engineering software used to configure the OP17 family. The 6AV3982-1AF26-1AX2 OFT driver is installed as follows:

  1. Start ProTool / ProTool RT on the engineering PC (Windows-based, target PC must have a 3.5" floppy or compatible USB floppy drive to read the OFT media).
  2. Open the target OP17 project (.pdb / .dbs).
  3. Choose Options → Add Option and point the dialog at the 3.5" floppy containing the 6AV3982-1AF26-1AX2 OFT package.
  4. ProTool copies the .pdr file into the project's Drivers subdirectory and adds a new entry under OP17 → Interfaces → IF2 → Protocol.
  5. Set the protocol to OFT (Sympat FD20).
  6. Configure the IF2 serial parameters to 9600 bit/s, 8 data bits, no parity, 1 stop bit (the OFT driver class is fixed to 8N1 at 9600 bit/s; this is the only combination supported by the v4.xx driver).
  7. Compile and download the project to the OP17. The OP17 prompts for a restart after download.
  8. After restart, connect the FD20 to the OP17's IF2 port and power the FD20 before applying OP17 power. The boot sequence is order-sensitive.
The baud rate, data bits, parity, and stop-bit settings above represent the OFT driver class defaults. If the OP17 firmware has been customized, verify the actual settings under OP17 → Interfaces → IF2 → Protocol before commissioning. The OFT driver does not auto-baud.

Wiring and Cable

The FD20 is supplied with a DB-15 (male) to DB-15 (male) cable. Field experience indicates a 1:1 shielded cable is required, with the shield bonded at the OP17 end only. Cable length should not exceed 3 m at 9600 bit/s. Cross-over or null-modem adapters are not required; the FD20 is a DTE-style device that expects a 1:1 cable into the OP17 IF2 port.

If the original cable is missing, the field-typical DB-15 pinout for the OFT driver class on the OP17 IF2 is:

OP17 IF2 (DB-15F) Pin Signal FD20 DB-15 (DB-15M) Pin
2 TxD 3
3 RxD 2
4 RTS 5
5 CTS 4
7 Signal GND 7
1, 6, 8–15 n.c. / shield 1, 6, 8–15
Pin assignments above are field-typical for the OFT driver class on OP17 IF2. Always verify with a continuity tester against the FD20 connector silkscreen before applying power. Different FD20 hardware revisions may use a subset of the handshake lines; consult the FD20 housing label or the Sympat installation drawing if available.

Recipe Transfer Model

The OP17 stores recipes in internal battery-backed RAM. With the FD20 connected and the OFT driver loaded, the operator can:

  • Read a recipe from the floppy to the OP17 (LED ~2 s)
  • Write a recipe from the OP17 to the floppy (LED on, with brief flickers as sectors are written)
  • Backup the entire OP17 project to the floppy
  • Restore the project from the floppy

The recipe file format on the floppy is a sequential record layout. The OFT driver does not use a filesystem-aware layer; it writes raw records and trusts the OP17 to interpret the structure. Record size is determined by the OP17 recipe configuration (configured in ProTool under the recipe object's properties). A typical deployment uses a fixed-length record of either 64, 128, or 256 bytes per recipe entry, depending on the number and type of tags in the recipe.

Because the OFT driver is filesystem-agnostic, the floppy must be formatted as a standard FAT12 1.44 MB or 720 KB DOS floppy, but the OFT driver does not create or read files in the conventional sense. It positions the read/write head to a cylinder/sector offset that matches the recipe index. A floppy formatted on a Windows PC will work, but file-level copying on a PC will not produce a usable OP17 backup.

Recovery When the Driver Is Missing

When the original 6AV3982-1AF26-1AX2 OFT floppy is lost, the following paths have been used in the field:

  1. Industrial surplus / sealed media search — Siemens spare-parts resellers occasionally have sealed OFT media. Search by the exact order number. The order number is the most reliable key.
  2. Siemens legacy support — Older Siemens support packages bundled the OFT driver into the ProTool "Option" CD set. Open a support ticket referencing the order number. Siemens Industry Online Support (search by 6AV3982-1AF26-1AX2) is the authoritative source for legacy part availability.
  3. Engineering reconstruction — The .pdr file structure for ProTool option drivers is documented in the ProTool SDK. Power users have reconstructed a working .pdr by combining the .pdr skeleton from a similar ProTool option driver (for example, the printer driver) with the FD20 protocol tables. This is a last-resort option and is not endorsed by Siemens; the resulting driver may not pass the ProTool option integrity check on newer ProTool service packs.
  4. Substitution — project transfer — Modern replacements for project transfer include:
    • USB floppy drive on a Windows PC running ProTool, transferring project files via ProTool's normal "Transfer → Floppy" dialog instead of the OFT driver
    • Direct serial port on the engineering PC running ProSave to upload the project to the OP17 via IF1
    • Ethernet-attached upload via an OP17 with the optional Ethernet module (only on specific OP17 hardware revisions)
  5. Substitution — recipe handling — For recipe handling specifically, the substitution path is weaker; the OFT driver is the canonical recipe-floppy path on the OP17. Some sites have migrated recipes to a PC-based tool and used a serial printer or barcode reader to move recipe data, but this requires custom integration.

The substitution path is preferred when the OP17 firmware supports standard ProTool upload protocols and the OFT driver is only required for field recipe handling rather than for routine project maintenance.

Verification Procedure

After the OFT driver is installed and the FD20 is connected, verify operation with the following procedure:

  1. Power up the FD20 first, then the OP17. The OP17 should display "FD20 ready" or an equivalent status-line message within 15 seconds.
  2. Insert a 3.5" HD floppy (1.44 MB) into the FD20. The LED should illuminate for ~10 s, then extinguish.
  3. Trigger a recipe read on the OP17 from the floppy. The LED should illuminate for ~2 s, then extinguish.
  4. Read a recipe, modify a tag value on the OP17, and write the recipe back. The LED should flicker during the write.
  5. Power-cycle the OP17 and verify the modified recipe persists in OP17 memory (the floppy was not the source of truth, the OP17 RAM was).
  6. Trigger a full project backup to a separate floppy. Verify the backup completes and the OP17 reports success.

If all six steps pass, the OFT driver and FD20 are operating within specification.

Troubleshooting Matrix

Symptom Likely Cause Action
LED does not light at power-up FD20 not powered, or no disk inserted Check 24 V supply to FD20; insert a formatted disk
LED on continuously FD20 controller hang Power-cycle FD20, then OP17; check floppy media
OP17 reports "FD20 not found" Wrong port (IF1 used), wrong baud, cable fault Switch cable to IF2; verify 9600 8N1; test cable continuity
OP17 reports "OFT driver missing" OFT driver not installed in project Reinstall 6AV3982-1AF26-1AX2 driver via ProTool → Options → Add Option
Recipe read returns garbage values Bad floppy, wrong record format, corrupted project Reformat floppy on PC; re-export recipe from a known-good OP17
OP17 does not restart after download Driver install corrupted project Restore project from backup floppy; reinstall driver on a clean project
LED rapid blink (≤ 5 Hz) Unsupported media or controller self-test failure Use a known-good 1.44 MB HD floppy; if persistent, FD20 controller failure
Recipe read sometimes works, sometimes fails Marginal cable, EMI, or failing FD20 head Replace cable; check shield bonding; if persistent, FD20 drive mechanism end-of-life

Notes on Modern Equivalents

For new installations, the FD20 + OFT driver combination should be considered obsolete. Modern Siemens HMIs (Comfort Panels, Unified Panels) support:

  • Project transfer via Ethernet / PROFINET
  • Recipe handling via the SIMATIC WinCC recipe object (panel-side data medium)
  • USB stick for project backup directly on the panel
  • OPC UA for recipe exchange with higher-level systems

If the OP17 is being maintained rather than replaced, document the FD20 setup carefully: cable pinout, driver version (v4.xx), floppy format, and recipe record size. The FD20 chassis has no user-serviceable parts; failures of the floppy drive mechanism usually mean replacement of the entire FD20 unit. Third-party USB floppy drives on a Windows PC running ProTool can substitute for the FD20 for project transfer only; for recipe transfer on the OP17, the FD20 + OFT driver pairing remains the canonical path.

What is the Siemens order number for the OP17 FD20 driver?

The order number is 6AV3982-1AF26-1AX2 (OFT, v4.xx) for the Sympat FD20 serial floppy disk station.

Which OP17 port is used for the FD20?

IF2 (DB-15) only. IF1 is reserved for the engineering PC running ProTool or ProSave.

What baud rate does the OFT driver use?

9600 bit/s, 8 data bits, no parity, 1 stop bit (8N1). This is the only combination supported by the v4.xx OFT driver; the driver does not auto-baud.

How do I recover the driver if the original 6AV3982-1AF26-1AX2 floppy is lost?

Contact Siemens legacy support with the order number, search industrial surplus for sealed OFT media, or substitute a USB floppy drive on a Windows PC running ProTool for project transfer (the OFT driver is bypassed in that path).

Can a USB floppy drive replace the FD20 on a modern PC running ProTool?

Yes, for project upload/download. A standard USB floppy drive on a Windows PC is recognized by ProTool's "Transfer → Floppy" workflow, bypassing the OFT driver entirely. For Windows-side driver setup on modern systems, see the Microsoft Q&A on external floppy drives on Windows 10. Recipe transfer on the OP17 itself still requires the FD20 + OFT driver combination.

Is the Sympat FD20 still supported by Siemens?

No. Sympat GmbH no longer exists, and the FD20 is end-of-life. The 6AV3982-1AF26-1AX2 OFT driver is the last official release. The driver is a legacy ProTool option; sourcing it requires industrial surplus or Siemens legacy part channels.