Siemens OP27 Transfer Mode Failure: ProTool Download Guide
The Siemens SIMATIC OP27 is a text-based operator panel from the OP series, configured and downloaded with ProTool/Pro V6.x. When the panel refuses to enter transfer mode on power-up, the failure usually traces to one of three areas: a missed or incorrect key sequence, a missing or corrupt firmware image, or an incorrectly wired IF2 serial link to the PC. This guide consolidates field-proven diagnostics, key sequences, the IF2 cable pinout, and recovery procedures for the OP27.
1. Problem Statement
Symptom: 24 V applied to a new or freshly reset OP27, ESC + ArrowUP held throughout the rising edge, and the panel does not respond with the expected "Transfer..." or download prompt. ProTool cannot establish a connection to the panel over the IF2 serial port. The operator panel either boots directly into a blank project screen or displays "No project" without ever offering the transfer handshake.
Affected units and configurations:
- OP27 6AV3 627-1JK00-0AX0 and 6AV3 627-1JK00-1AX0 (mono, text-display variants)
- OP27 / OP37 families configured with ProTool V6.0 or ProTool/Pro V6.0 SP2+
- Brand-new units shipped without preloaded firmware or with empty flash
- Used units that were last configured with a third-party tool or abandoned mid-flash
2. Root Cause Analysis
Three failure modes dominate OP27 transfer-mode issues in field service work:
- Key sequence timing error. The transfer key combination is timing-sensitive. Buttons must be held before 24 V is applied and released only after the transfer prompt appears. A defective or worn ArrowUP membrane produces the same symptom: the bootloader never detects the key, so the runtime boots instead of the transfer dialog.
- Missing firmware on flash. A brand-new OP27 may have its flash file system empty. The bootloader cannot mount the runtime that hosts the transfer dialog. A memory card with the firmware image must first be used to load the runtime, or ProTool V6.0 SP3+ must be used to push firmware over IF2.
- Cable, COM port, or handshake mismatch. A generic 9-pin extension, a USB-to-serial converter without proper RTS/CTS timing, or wrong ProTool COM settings prevent the panel from acknowledging the PC. The OP27 will sit in the transfer prompt indefinitely and ProTool will report "Timeout" or "No response from panel".
3. Prerequisites
- ProTool V6.0 SP2 minimum, SP3 or later strongly recommended, installed on a Windows 2000/XP PC.
- Siemens PC <-> OP serial cable, order number
6XV1 440-2KH10(9-pin female D-sub on the PC end, 15-pin male D-sub on the OP27 IF2 end). - A free native COM port. USB-RS232 adapters from Belkin and generic FTDI-based units have known handshake timing issues with ProTool; prefer native COM1 (IRQ4) or COM2 (IRQ3).
- 24 V DC supply capable of 0.5 A minimum. The OP27 draws approximately 0.35 A typical, with cold-start inrush up to 0.5 A.
- Compiled OP27 runtime file (typically
OP27.binor*.img) and project*.pdzgenerated by ProTool. - For memory-card recovery: a 4 MB minimum, 16 MB maximum Type I/II SRAM or Flash PCMCIA card formatted to the OP27 FAT layout.
4. Standard Transfer-Mode Entry Procedure
- Verify the 24 V supply is OFF at the OP27 L+ and M terminals.
- Press and hold
ESCandArrowUPsimultaneously. Both keys must be physically down before 24 V is applied. - Apply 24 V DC. Within 2-3 seconds the LCD should display a transfer prompt with a flashing cursor.
- Once the prompt appears, release the keys.
- Connect the 6XV1 440-2KH cable between the PC and the OP27 IF2 port only after the transfer prompt is on screen. Hot-plugging IF2 is permitted.
- Start the ProTool transfer:
File > Download > Transfer.
5. Alternate Key Combinations for Stuck or Worn Keys
If the ArrowUP membrane is defective (a known wear item on OP7, OP17, OP27, and OP37 front foils), the standard ESC+ArrowUP sequence will not register. The OP-family bootloader accepts a second combination for panel recovery:
| Action | Key combination | Result |
|---|---|---|
| Enter transfer mode (primary) | ESC + ArrowUP | Boots the transfer dialog while preserving flash contents |
| Force firmware erase | ESC + ArrowRight + ArrowDown | Erases the entire flash and reverts the panel to a transfer-only state |
| Boot to runtime | (no keys held) | Normal project start |
The erase combination is the right tool when the existing runtime has crashed and is no longer responsive to the primary sequence. After erase, the unit must be re-imaged with a PC download or memory card before any project can be loaded.
6. IF2 Cable Wiring (6XV1 440-2KH..)
The OP27 IF2 interface is a 15-pin male D-sub configured as RS-232C, DCE-style. The PC end is a 9-pin female D-sub. The official Siemens cable 6XV1 440-2KH10 implements a full null-modem with hardware-handshake bridging. Pin mapping:
| Signal | PC 9-pin (DB9F) | OP27 15-pin (DB15M, IF2) |
|---|---|---|
| RxD / TxD cross | Pin 2 (RxD) | Pin 3 (TxD from OP) |
| TxD / RxD cross | Pin 3 (TxD) | Pin 2 (RxD at OP) |
| RTS | Pin 7 | Pin 4 (CTS at OP) |
| CTS | Pin 8 | Pin 5 (RTS at OP) |
| DTR | Pin 4 | Pin 6 (DSR) + Pin 8 (DCD, bridged) |
| DSR | Pin 6 | Pin 20 (DTR) |
| Signal Ground | Pin 5 | Pin 7 (GND) |
| Shield | Housing | Housing |
The full wiring diagram and ordering data are published in the Siemens Automation Support entry Entry ID 29034071 - OP panel PC connection cable (6XV1 440-2KH..). Use this reference when building a substitute cable; do not rely on a generic DB9 extension.
7. ProTool PC-Side Configuration
- Open the OP27 project in ProTool/Pro.
- Menu
File > Download > Transfer Settings. - Select the COM port assigned to the cable. On native COM1 or COM2, use the following parameters: baud
9600, data bits8, parityNone, stop bits1, flow controlRTS/CTS(hardware). - XON/XOFF software flow control is not supported by the OP27 bootloader. Selecting it produces a silent timeout.
- Click
Download. ProTool first negotiates firmware version. If the OP27 firmware is older than the project requires, ProTool prompts to update the firmware before downloading the project image. - Confirm the firmware update. The OP27 reboots once the firmware is in place and ProTool re-initiates the transfer automatically.
8. Recovery via Memory Card (No PC Required)
When the OP27 bootloader cannot be reached by any key sequence (for example, all front-panel keys are unresponsive) and the unit ships with empty flash, a PCMCIA memory card is the recovery path:
- Format a Type I/II SRAM or Flash PCMCIA card (4 MB minimum, 16 MB maximum for the OP27) using a card reader on the PC.
- Copy the firmware image to the card root directory. The file must be named exactly as specified in the OP27 firmware release notes (typically
OP27FW.BINorOP27FW.IMG). - Insert the card into the OP27 PCMCIA slot with power OFF.
- Power on. The bootloader auto-detects the card and prompts
Update firmware from card? - Press ENTER to confirm. The firmware loads in 30-60 seconds. The panel reboots automatically when complete.
- After firmware is present, repeat the standard ESC+ArrowUP sequence to enter transfer mode and download the project via ProTool.
For backing up an existing project, the same card slot is used in reverse: with a card inserted, the OP27 will write a BACKUP file at every normal shutdown if enabled under System > Card Functions in ProTool.
9. IF1 vs IF2: Don't Cross the Ports
On the OP27 rear face, two D-sub connectors are present:
| Port | Connector | Function | Connect to |
|---|---|---|---|
| IF1 | 9-pin male, top | MPI / PPI to PLC (S7-200, S7-300/400, LOGO!) | PLC MPI/PPI port with a PROFIBUS cable, e.g. 6XV1 830-0EH10 |
| IF2 | 15-pin male, bottom | RS-232 PC commissioning and ProTool download | PC COM port with 6XV1 440-2KH10 |
10. Cable Continuity Test with a Multimeter
When a substitute cable is in use and ProTool times out, validate the wiring in 60 seconds with a continuity tester:
- With the cable disconnected at both ends, set the meter to continuity (beep) mode.
- Verify the cross pairs: PC pin 2 to OP pin 3, PC pin 3 to OP pin 2, PC pin 7 to OP pin 4, PC pin 8 to OP pin 5.
- Verify the handshake bridge: PC pin 4 to OP pin 6 and OP pin 8 (DTR bridges DSR and DCD at the panel end).
- Verify the return: PC pin 6 to OP pin 20.
- Verify the ground: PC pin 5 to OP pin 7.
- Verify the shield: PC housing to OP housing, with no continuity to any signal pin.
Any open circuit on the cross pairs or the handshake bridge is enough to stall the transfer. The shield must not short to signal ground or the panel will reset on every PC transmit.
11. Verification
- After the download completes, ProTool reports
Transfer successfuland the OP27 reboots automatically into the project. - Check the OP27 LCD: the project start screen should appear within 5 seconds of reboot.
- Press a configured function key. The assigned screen or function should respond. If a tag read returns the expected value, the IF2 link is fully functional for runtime as well as commissioning.
- In ProTool,
Online > OP Diagnosticsshould display the OP27 firmware version and project CRC matching the downloaded file. - Cycle power on the OP27 with no key held. The project should start on its own. If the panel returns to "No project" or "Transfer...", the flash write was interrupted - re-transfer with a fresh 24 V supply.
12. Troubleshooting Matrix
| Symptom | Likely cause | Action |
|---|---|---|
| No response to ESC+ArrowUP at power-on | Keys released too early; or ArrowUP membrane defective | Hold keys before applying 24 V; try ESC+Right+Down to force erase, then re-image |
| Transfer prompt appears but ProTool reports "No connection" | Wrong COM port, wrong cable, or XON/XOFF selected | Verify COM assignment; confirm 6XV1 440-2KH10 cable; force RTS/CTS in ProTool transfer settings |
| Transfer starts, then aborts at firmware stage | Mismatched firmware version between project and panel | Allow ProTool to update firmware; if it fails, retry with ProTool V6.0 SP3 or later |
| Panel shows only "No project", no transfer option | Empty flash, bootloader cannot reach transfer dialog | Use PCMCIA card to load firmware first, then re-attempt transfer |
| ProTool hangs at "Initializing..." with native COM | COM port assigned to another device, or IRQ conflict | Check BIOS/Windows Device Manager; assign COM1 IRQ4 or COM2 IRQ3 exclusively |
| Panel reboots repeatedly after project load | Watchdog not satisfied by project scan time | Reduce tag count or increase scan time in ProTool project settings; reflash |
| USB-RS232 adapter, intermittent link | Adapter does not support full RTS/CTS toggle timing | Replace with native COM port or a Siemens-approved USB-RS232 (6GT2 302-0AA00) |
| Transfer dialog appears, ProTool connects, but download stalls at 12% | 24 V rail sags during flash write | Use a separate 24 V supply for the transfer; add a 470 uF capacitor across L+/M at the panel |
| Panel enters transfer, but ArrowUP key is non-responsive later | Front foil wear | Replace front foil assembly (Siemens spare part 6AV3 627-1JK00-0AX0 membrane kit) |
13. Field-Proven Caveats
- The OP27 IF2 port shares its physical connector style with the IF1 MPI/PPI port. Confirm the connector count (9-pin vs 15-pin) before plugging in. The 15-pin connector is the PC link; the 9-pin is the PLC link.
- ProTool V6.0 SP2 and earlier do not support firmware update over IF2 on a brand-new OP27 with no firmware. SP3 added this capability. If a new panel will not take a transfer, upgrading ProTool to SP3 or later is the first step before opening a support request.
- When the panel is powered from the same 24 V rail as a S7-200 or LOGO!, switching transients on the supply can interrupt the bootloader handshake. Add a decoupling diode or a separate supply during the transfer window.
- The ArrowUP key on the OP27 is the membrane that wears first. A panel with a sticky or non-responsive ArrowUP will never enter transfer mode by the primary sequence. Field repair is to replace the front foil assembly.
- ProTool stores the last-used COM port in the project. If a project was last downloaded on a workstation that no longer has that COM port, the transfer fails before the cable is even queried. Re-assign the COM port in
File > Download > Transfer Settingsbefore each commissioning session. - Some USB-RS232 adapters advertise full RTS/CTS support but tie the handshake lines to a 1 ms debounce that the OP27 bootloader rejects. A native COM port eliminates the variable.
14. ProTool Version Compatibility
| ProTool version | OP27 support | Firmware push over IF2 | Notes |
|---|---|---|---|
| V5.x | Partial | No | Use only for legacy projects; no transfer on new panels |
| V6.0 base | Yes | No | Requires preloaded firmware on panel |
| V6.0 SP2 | Yes | No | Improves serial timing, still requires preloaded firmware |
| V6.0 SP3 | Yes | Yes | Recommended for new OP27 commissioning |
| ProTool/Pro V6.0 SP4+ | Yes | Yes | Latest certified build for OP27 service |
| WinCC flexible 2004+ | Limited | No | OP27 only supported via "Import ProTool project" workflow |
15. Power and Grounding Checklist
OP27 transfer failures with no panel-side error message are frequently a power-quality issue. Confirm the following before replacing the panel:
- 24 V supply measured at the OP27 L+/M terminals is between 20.4 V and 28.8 V under load.
- The supply common (M) is bonded to panel chassis ground at exactly one point.
- The 24 V cable from the supply to the panel is < 3 m, or is sized for < 1 V drop at full load.
- No inductive loads (contactors, solenoid valves) share the same 24 V branch without a freewheeling diode.
- The PC end of the 6XV1 440-2KH cable is grounded to the same protective earth as the OP27 supply, or the PC is on a properly grounded outlet.
A ground loop between the PC and the panel is the most common cause of a transfer that starts, progresses to 12-30%, then drops the link. Floating the PC on a battery-powered laptop with the charger unplugged is a fast diagnostic.
16. Recovery Workflow Summary
- Power off the OP27. Hold ESC + ArrowUP. Power on. Observe the LCD for the transfer prompt.
- If no prompt, suspect a worn ArrowUP. Repeat with ESC + ArrowRight + ArrowDown to force erase, then re-attempt step 1.
- If still no prompt, the flash is empty or corrupt. Insert a PCMCIA card with the OP27 firmware image. Power on, confirm the firmware update.
- Once firmware is in place, repeat step 1 to enter transfer mode.
- Connect the 6XV1 440-2KH10 cable. In ProTool, set COM port to 9600/8/N/1, RTS/CTS, and run
File > Download > Transfer. - Verify the project start screen on reboot, then verify a tag read or function key to confirm full IF2 health.
Frequently Asked Questions
Why does my OP27 ignore the ESC + ArrowUP combination on power-up?
The keys must be pressed and held before 24 V is applied to the panel, and released only after the transfer prompt appears on the LCD. If the ArrowUP membrane is worn, the bootloader will not detect the key. Use the alternate ESC + ArrowRight + ArrowDown combination to force a flash erase, then re-image via PC or PCMCIA card.
Can I download the OP27 firmware from a memory card instead of a PC?
Yes. Copy the OP27 firmware image to the root of a 4-16 MB PCMCIA SRAM or Flash card, insert it with the panel powered off, then apply 24 V. The bootloader will prompt to update the firmware from the card. Press ENTER to confirm. The panel reboots once the load completes, typically in 30-60 seconds.
What is the correct serial cable between a PC and the OP27 IF2 port?
Use the Siemens order number 6XV1 440-2KH10 (9-pin female DB9 on the PC end, 15-pin male DB15 on the OP27 IF2 end). The wiring is a full null-modem with hardware-handshake bridging between DTR, DSR, RTS, CTS, and DCD. Generic DB9 extension cables do not cross TxD/RxD and will not establish a link. The full pinout is published in Siemens Support entry 29034071.
What COM port settings does ProTool need for OP27 download?
Set the COM port to 9600 baud, 8 data bits, no parity, 1 stop bit, with RTS/CTS hardware flow control. XON/XOFF software flow control is not supported by the OP27 bootloader and will cause ProTool to time out. Native COM1 (IRQ4) or COM2 (IRQ3) is recommended over USB-RS232 adapters.
The OP27 shows "No project" and never offers a transfer option. What now?
The flash is empty, so the runtime that would host the transfer dialog is not present. Either load the firmware first via PCMCIA card (recommended when the front-panel keys are not responsive) or use ProTool V6.0 SP3 or later, which can flash the OP27 firmware over IF2 as the first step of a transfer. After firmware is present, restart with ESC + ArrowUP to enter transfer mode.
Can I use a USB to RS-232 adapter for the OP27 download?
Sometimes, but it is not the recommended path. Many USB-RS232 adapters do not toggle RTS/CTS within the timing window the OP27 bootloader expects, and ProTool will report a timeout even though the COM port opens. If a native COM port is not available, use a Siemens-approved USB-RS232 (order number 6GT2 302-0AA00) or an FTDI-based adapter verified for full hardware handshake. As a diagnostic, run the transfer on a battery-powered laptop with the charger unplugged to eliminate a ground loop between the PC and the panel 24 V supply.