Siemens OP37 HMI Data Archiving Limits and MP377 Migration

David Krause13 min read
HMI / SCADASiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. OP37 Platform Overview

The SIMATIC OP37 (and the related OP27) is a text/graphic operator panel from the Siemens ProTool generation, predating the SIMATIC WinCC flexible and TIA Portal HMI lines. The OP37 family was designed as a low-cost operator interface for SIMATIC S7-200, S7-300, and S7-400 controllers over MPI/PROFIBUS, and it is programmed exclusively with Siemens ProTool / ProTool Pro. It does not run WinCC flexible, WinCC, or TIA Portal projects natively.

Engineering teams encountering an OP37 in a brownfield machine must understand three platform constraints before planning a data archiving strategy:

  1. No Ethernet interface is present on the base OP37 hardware.
  2. No integrated logging/archiving subsystem is implemented in the ProTool firmware.
  3. The onboard floppy drive is a service/recovery interface, not a user data store.

These constraints are documented in the Siemens Industry Online Support entry OP27, OP37 Operator Panels, chapter 9, which covers communication, memory model, and supported functions. Engineers evaluating the OP37 should consult that chapter directly when designing any historian or data-export function.

The "OP37" name is also used by Analog Devices for a low-noise precision operational amplifier (see the OP37 op-amp datasheet). Do not cross-reference that datasheet with the Siemens HMI; the two are unrelated products. Use Siemens MLFB numbers (e.g., 6AV3 6XX-1...) to identify the HMI unambiguously.

2. OP37 Hardware Variants and MLFB Identification

Two principal variants exist on the field: the standard OP37 and the higher-feature OP37/PRO. The /PRO suffix indicates additional function keys, expanded message buffer, and an extended recipe/memory model, but the two share the same backplane, the same MPI/PROFIBUS interface, and the same absence of Ethernet.

Before any migration or feature work, capture the full MLFB (Siemens order number) from the rating plate on the rear of the panel. The MLFB determines which ProTool version is required to open the project and whether a migration to WinCC flexible 2008 is viable.

Variant Programming Tool Ethernet Integrated Logging Floppy Drive
OP37 (base) ProTool / ProTool Pro No No Service only (Windows CE install/restore)
OP37/PRO ProTool / ProTool Pro No No Service only (Windows CE install/restore)
MP377 (successor) WinCC flexible 2008 / TIA Portal Yes (PROFINET) Yes (tags, alarms, audit) N/A

3. ProTool Version Selection by MLFB

ProTool/Pro is the only environment that opens an OP37 source file. Compatibility with the OP37 is not uniform across the ProTool release line; field experience and the Siemens migration manual identify two practical operating points:

  • ProTool V4.01 — the earliest release that supports the original OP37. Required for some early MLFBs and for projects that still use ProTool-only objects.
  • ProTool V6.0 / SP3 — the last ProTool release and the recommended baseline for late OP37 / OP37/PRO units. Newer SP levels add bug fixes for MPI/PROFIBUS and for the OP37 / OP37/PRO function-key mapping.

Procedure to confirm the correct ProTool version:

  1. Read the rating plate and record the full MLFB (for example, 6AV3 637-1LL00-0AX0 or similar).
  2. Open the Siemens Industry Online Support entry list and filter by the exact MLFB.
  3. Cross-reference the listed ProTool version against the firmware image stored on the OP37 (System Menu → Version).
  4. Use the highest ProTool release that supports the MLFB; do not install ProTool 6.0 over a 4.01-only project without re-saving it first.

4. Data Archiving Limitations on OP37

The OP37 firmware does not implement a tag archive. It supports process values, messages, and recipes in volatile runtime memory, but it does not write these to a persistent archive on a network share, FTP server, or SQL backend. The limitations are hard limits in the runtime; they cannot be unlocked by configuration, scripting, or add-on packages because:

  • There is no Ethernet MAC, no TCP/IP stack, and no file system suitable for archive handling.
  • ProTool for OP37 does not provide a "Logging" or "Archive" editor comparable to WinCC flexible 2008 or TIA Portal.
  • VBScript, the scripting language introduced in WinCC flexible, is not available in ProTool for OP37.

Consequences for the data historian:

  1. Process values must be logged upstream in the PLC (e.g., DataLog blocks in S7-300/S7-400 or a SIMATIC IPC with WinCC).
  2. Long-term trending on the HMI is limited to the operator-viewable curve object, which is RAM-resident and lost on power cycle.
  3. Any archiving requirement that depends on the HMI being the data source must be re-platformed to MP377, Comfort Panel, or a SCADA before commissioning.

5. The OP37 Floppy Disk Drive — What It Actually Does

The OP37 ships with a 3.5" floppy drive behind a front-panel door. A common misreading of the hardware is that the floppy can be used to store process archives. It cannot. The floppy drive on the OP37 is reserved for:

  • Restoring the Windows CE / ProTool runtime image from a service floppy.
  • Performing a clean firmware re-flash when the internal image is corrupted.
  • Loading factory recovery sets during commissioning or repair.

Archive writes are blocked at the firmware level. Attempting to write user data to the floppy will fail or corrupt the runtime image. If a removable medium is required for export, the panel must be replaced — there is no firmware patch that enables user-mode floppy access on the OP37.

6. Network Communication on the OP37

The OP37 communicates with the controller through its MPI/PROFIBUS interface only. It does not include a TCP/IP stack, an FTP client, an HTTP server, an OPC server, or an SMTP client. ProTool exposes standard SIMATIC protocols (MPI, PROFIBUS-DP, PPI on a subset of builds), but no IP-based service is available on the panel itself.

Interface Available on OP37? Use Case
MPI Yes Programming port, S7-300/S7-400 communication
PROFIBUS-DP Yes (selected MLFBs) Distributed I/O, controller-to-controller
RS-232 (service) Yes ProTool download, debug
Ethernet 10/100 No Not available
PROFINET No Not available
Wi-Fi No Not available

For a network-attached historian, the only valid OP37-era path is to push the data from the PLC to a PC-based logger (e.g., a SIMATIC WinCC single-user station, a SCADA node, or a custom OPC client). The OP37 cannot participate as a data source for that path.

7. Migration Path: OP37 → MP377

The SIMATIC MP377 is the designated successor to the OP37. The MP377 family runs WinCC flexible 2008 (or later, via TIA Portal migration) and includes:

  • PROFINET (Ethernet) interface for controller and network traffic.
  • Integrated tag and alarm logging to internal Flash, SD card, or network share.
  • VBScript for application logic and archive triggers.
  • OPC DA server for SCADA integration.
  • Recipe, audit trail, and user administration objects.

Migration is not a 1:1 conversion. Use the Siemens SIMATIC HMI WinCC flexible 2008 Migration manual as the authoritative reference; it documents which ProTool objects convert cleanly, which require manual rework, and which are simply not available on the target platform. Treat the migration as a project, not a file format operation.

8. ProTool → WinCC flexible 2008 Conversion Procedure

  1. Inventory the project — list screens, tags, messages, recipes, area pointers, schedules, and any ProTool-only objects (e.g., trend curves with a fixed sample count, ProTool-Pro status displays).
  2. Compile the project in ProTool at the highest supported ProTool release. Resolve all warnings. An unclean compile propagates to the converted project.
  3. Install WinCC flexible 2008 SPx on the engineering station. The exact SP is dictated by the target MP377 firmware; consult the Siemens compatibility tool for the panel-image ↔ flexible-version matrix.
  4. Run the Migration Wizard in WinCC flexible 2008 (File → Migration). The wizard consumes the ProTool .pdb/.hmi source and emits a WinCC flexible project. Cross-reference each converted object against the migration manual's table of supported objects.
  5. Resolve non-converting objects — typically: ProTool status/control objects with custom bitmaps, ProTool-Pro language switching, area pointer schemes that depend on ProTool-only flags, and any ProTool "function" calls that lack a WinCC flexible equivalent.
  6. Re-tag with WinCC flexible addressing — the tag DB must be expanded where WinCC flexible expects a wider or differently typed connection (e.g., area pointers for date/time, user login, recipe).
  7. Re-implement logging in WinCC flexible. Add a Tag Logging editor instance, define the archive segments, and configure the storage path (internal Flash, SD card, or network path). This step has no equivalent in the original ProTool project.
  8. Compile, simulate, and transfer to the MP377. Use WinCC flexible's runtime simulator to verify the screens, the logging triggers, and the script behavior before any plant-power transfer.

9. MP377 Selection for an OP37 Replacement

When the OP37 must be replaced, size the MP377 to match the cutout, the resolution, and the operator workflow. Use the Siemens migration tool, or follow these rules of thumb:

OP37 (typical) MP377 successor Cutout (in) Display
OP37 mono (5.7") MP377 12" Touch Cutout adapter required Color TFT
OP37 color (5.7") MP377 12" Touch Cutout adapter required Color TFT
OP37/PRO (10.4") MP377 15" Touch Direct or with adapter Color TFT

Verify the mechanical depth behind the panel — MP377 is deeper than OP37 in most cases — and re-pull the PROFIBUS / PROFINET cable to the new port. The migration from MPI to PROFINET is a separate engineering task and may require the controller's PROFINET port to be enabled and a new device configuration loaded.

10. MP377 Configuration for Networked Archiving

Once the migration is complete, configure the MP377 to send archives to a server or PC:

  1. Set a static IP, subnet, and gateway in the MP377 control panel (Control Panel → Network and Dial-Up Connections → PN-IO).
  2. In WinCC flexible 2008, open the project's Tag Logging editor and add an archive per data point. Configure a circular log with a defined size, or a segmented log with file switches.
  3. Open Schedules and add a trigger that calls a script, e.g., daily at 23:00, to flush and copy the archive to a UNC path such as \\HMI-ARCHIVE\mp377$\plant01.
  4. In the script, use FSO.CopyFile (VBScript) to move the closed archive segment to the target. Example skeleton:
    ' Triggered by schedule, after archive segment closes
    Dim srcPath, dstPath, fso
    srcPath = "\Storage Card\Archives\" & CurrentArchiveName
    dstPath = "\\\\HMI-ARCHIVE\\mp377$\\plant01\\" & CurrentArchiveName
    Set fso = CreateObject("Scripting.FileSystemObject")
    If fso.FileExists(srcPath) Then fso.CopyFile srcPath, dstPath, True
    Set fso = Nothing
  5. On the server, grant the MP377 user (the WinCC flexible runtime user, typically Administrator or a dedicated hmi_service account) write permission on the target share.
  6. Validate the path with a small test script that writes a placeholder file before commissioning the real archive flow.

11. Verification Checklist

Use this matrix to verify a successful OP37 → MP377 migration plus network archiving:

Check Method Pass Criterion
All ProTool screens converted Side-by-side compare in WinCC flexible No missing objects; layout acceptable
Tags read/write Runtime simulator + live controller All tags update within one cycle
Alarms trigger and log Force a fault in the PLC Alarm appears on MP377 and lands in archive
Archive closes on segment end Wait for segment boundary or trigger manually Closed segment appears in target share
UNC path reachable from MP377 Explorer-style test or FSO.FileExists True
No Windows firewall block Check server event log No 4625 / network policy denials
Time sync between MP377 and server Compare NTP times Skew < 1 s
Recipe round-trip Save to MP377, download to PLC, verify values Match

12. Troubleshooting Matrix

Symptom Likely Cause Action
ProTool will not open the OP37 project Wrong ProTool version for the MLFB Confirm MLFB; install ProTool V4.01 or V6.0 to match
WinCC flexible 2008 will not migrate the project Project compiled with errors, or unsupported objects Recompile in ProTool until clean; remove unsupported objects
MP377 cannot reach the archive share Wrong subnet, gateway, or DNS suffix Re-check IP config; ping the server from a PC on the same subnet to confirm reachability
Archive files are not produced Logging not enabled on the tag, or trigger is missing Open Tag Logging; verify "Acquisition" and "Archive" are both enabled on the tag
FSO.CopyFile fails on a network path User lacks write permission on the share Grant the MP377 service user write/modify rights on the share and NTFS path
Time stamps drift in the archive No NTP, or controller and MP377 unsynced Configure NTP on MP377 control panel; ensure the controller is on the same time source
MP377 loses connection to S7 PLC after migration Connection parameters in WinCC flexible differ from ProTool Open the new connection; verify MPI/PROFIBUS slot/rack or PROFINET IP
Display flicker on the new MP377 Resolution mismatch with original screen layout Redraw screens at the new resolution; use the migration tool's scaling preview

13. Field-Proven Caveats

  • The OP37 cannot be re-purposed as an OPC bridge. It is a terminal, not a server. Do not attempt to use it as a data concentrator for downstream historians.
  • ProTool V6.0 is not the same product as WinCC flexible 2005. They share some screens in the help system but they are not interchangeable; a ProTool .pdb project will not open in WinCC flexible directly, only via the migration wizard.
  • If the OP37 image is corrupted, the floppy recovery set is model-specific. Confirm the MLFB and firmware build before ordering a recovery disk set from Siemens.
  • The MP377's PROFINET interface uses the same RJ45 pinout as standard Ethernet, but the panel's IP must be on the IO controller's subnet, not just on the office LAN. Coordinate IP allocation with the controls team, not the IT team.
  • Do not assume the OP37 has a CE image on the floppy. The floppy is a recovery medium; the image on it is the one Siemens shipped at build time, which may not match the version the project requires.

14. Quick-Reference Decision Tree

  1. Is Ethernet or logging required on the panel? → If yes, replace the OP37 with an MP377 (or newer Comfort Panel).
  2. Is the project still maintained in ProTool? → If yes, finish development in ProTool, then plan the migration.
  3. Is the MLFB supported by WinCC flexible 2008 migration? → Verify in the SIMATIC HMI WinCC flexible 2008 Migration manual.
  4. Is the network architecture PROFINET? → The OP37 stays on MPI/PROFIBUS; the MP377 moves to PROFINET. Plan a controller-side PROFINET port and a new device configuration.
  5. Is the data path: PLC → MP377 → server? → If yes, configure Tag Logging on the MP377 plus a scheduled VBScript that copies closed segments to a UNC share.

Can the OP37 archive data and send it to a server or PC over the network?

No. The OP37 has no Ethernet interface and no integrated logging subsystem. Long-term archiving must be implemented in the PLC (DataLog blocks) or in a downstream PC-based SCADA. To enable HMI-side network archiving, replace the OP37 with an MP377 and re-implement logging in WinCC flexible 2008.

Does the OP37 floppy drive accept archive files?

No. The OP37 floppy drive is reserved for service operations: it restores the Windows CE / ProTool runtime image and supports firmware recovery. Writing user data to the floppy is blocked at the firmware level and risks corrupting the runtime image.

What is the difference between OP37 and OP37/PRO?

The /PRO variant adds function keys, expands the message buffer, and provides additional memory for recipes, but it shares the same backplane, the same MPI/PROFIBUS interface, and the same absence of Ethernet. Neither variant supports integrated logging.

Which ProTool version is required to open an OP37 project?

It depends on the MLFB. Most OP37 / OP37/PRO units are supported by ProTool V6.0; some early MLFBs require ProTool V4.01. Confirm by matching the rating plate MLFB against the ProTool compatibility list in the Siemens OP27, OP37 Operator Panels manual, chapter 9.

Which Siemens panel replaces the OP37?

The SIMATIC MP377 is the designated successor. It runs WinCC flexible 2008 (or TIA Portal via a migration), provides PROFINET, and supports tag and alarm archiving. Plan a ProTool-to-WinCC flexible 2008 migration and re-size the cutout; the MP377 is typically deeper than the OP37.

Can the OP37 be programmed with WinCC flexible?

No. The OP37 can only be programmed with ProTool / ProTool Pro. WinCC flexible 2008 is used to migrate the converted project to an MP377 (or newer Comfort Panel). WinCC flexible cannot download to an OP37.

Back to blog