Siemens PCS 7 to LabVIEW Integration: Profibus, OPC, Ethernet

David Krause19 min read
Process ControlSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens PCS 7 to LabVIEW Integration: Profibus, OPC, and Ethernet

Integrating SIMATIC PCS 7 with National Instruments LabVIEW is a recurring requirement in hybrid plants where PCS 7 handles continuous process control (APC, continuous function charts, SFC, batch) while LabVIEW provides custom data acquisition, laboratory-style analytics, FMEA test rigs, prototype algorithm validation, and special-purpose HMIs. The integration is not a single protocol choice; it is an architecture decision that must respect the deterministic runtime model of PCS 7 while still allowing LabVIEW's flexible, scientific-development environment to consume and produce data.

This reference covers the three production-proven paths: PROFIBUS DP/PA via a third-party master card (Comsoft/NI, Hilscher, SST), OPC DA/UA over Industrial Ethernet, and Siemens-specific serial protocols (AS511, R3964, USS) for legacy and drive integrations. It maps concrete catalog numbers, register/data-block conventions, commissioning steps, and field-validated troubleshooting entries so a controls engineer can specify, build, and verify the link without re-discovering every constraint.

1. PCS 7 Architecture Context for LabVIEW Integration

PCS 7 is the Siemens distributed control system (DCS) platform built on the SIMATIC S7-300/S7-400 (and newer S7-1500 with PCS 7 V9) automation systems. The system is partitioned into three logical station classes:

  • AS (Automation Station) – executes the SIMATIC controller (S7-400H for redundant, S7-410 for single, or S7-1500 with PCS 7 V9.x). Holds the process image and the CFC/SFC programs.
  • OS (Operator Station) – WinCC-based HMI that subscribes to the AS via S7 communication.
  • ES (Engineering Station) – runs SIMATIC Manager / PCS 7 Engineering and downloads the CFC/SFC configuration to the AS.

LabVIEW never takes the role of an AS. It is an external client that consumes process values or writes setpoints. As a non-Siemens node, it must enter the PCS 7 system through a sanctioned interface: a defined data block in the AS, an OPC server, a PROFIBUS slave/master, or a SIMATIC NET CP. The integration boundary must be explicit; that is the single most important design rule.

Engineering rule: Never let LabVIEW read or write to the S7 process image directly via raw MPI/PROFIBUS. Always use a dedicated data block (DB) so the interface contract is documented, version-controlled, and debuggable.

2. Communication Protocol Selection Matrix

Choosing the protocol is a function of data rate, determinism, point count, plant topology, and the version of PCS 7 already installed. The table below summarises the field-proven options.

Path Typical Hardware Throughput Best Use Latency Commissioning Effort
OPC DA over Ethernet (S7 protocol) CP 443-1 / CP 343-1 on AS + NI OPC Server or KEPware ~100 tag/s typical HMI trending, lab SCADA, slow supervisory writes 50–250 ms cyclic Low
OPC UA over Ethernet CP 443-1 with OPC UA server / S7-1500 native 1k+ tag/s Modern greenfield, IT/OT convergence, secure DMZ 20–100 ms Low–Medium
PROFIBUS DP master (PCI/cPCI) Comsoft/NI PCMCIA/PCI card, Hilscher CIF, SST card 12 Mbps, 244 bytes/cycle SoftPLC, fast cyclic I/O, deterministic 1–10 ms 1–10 ms deterministic High (GSD import, slot mapping)
PROFINET IO controller CP 1616 / CP 1604 (SIEMENS), Hilscher CIFX 100 Mbps Replacing PROFIBUS in modern plants 1–4 ms Medium
Serial AS511 / R3964 COM port / USB-RS232 to S5 / S7 9.6–187.5 kbps Legacy S5 retrofit, drive commissioning 100 ms+ per telegram Low (point-to-point only)
USS over RS485 PC COM port + Micromaster/Sinamics G drive 9.6–115.2 kbps Drive-only, parameterisation, simple control 50–500 ms Low

3. PROFIBUS Hardware Options (Comsoft/NI, Hilscher, SST)

When the requirement is cyclic, deterministic data exchange at the I/O scan rate of the AS – typical for soft-PLC implementations, high-speed acquisition of analyzer values, or moving LabVIEW into the role of a distributed PROFIBUS slave – a PROFIBUS DP master card in the LabVIEW PC is the correct choice. Three vendors dominate field installations.

3.1 Comsoft / National Instruments PROFIBUS cards

NI resells the Comsoft PROFIBUS DP master/slave cards as the NI PCIe-8431/8 family equivalents (historically labelled NI PXI-/PCI-8531 variants and the LabVIEW Real-Time PROFINET/PROFIBUS bundle). They ship with a configuration tool and a LabVIEW API; ready-made VIs are provided for slave and master operation. Typical catalog numbers:

  • PCI-COMSOFT PROFIBUS DP Master (PCI-DPM) – master, DPV0/DPV1
  • PCI-COMSOFT PROFIBUS DP Slave (PCI-DPS) – slave role, used to expose LabVIEW as a DP slave to the AS
  • NI PXI-8531 – PXI form factor with the same Comsoft silicon

The Comsoft path is the lowest-risk option for new LabVIEW installations because the API is LV-native and supported; you do not have to write a DLL wrapper.

3.2 Hilscher CIF cards

Hilscher CIF 50-PB / CIF 60-PB / CIF 104-PB cards (PCI, PCIe, PC/104) are widely deployed in European plants. They are not sold with a LabVIEW driver; integration requires the SyCon configuration tool to load the GSD and download the PROFIBUS configuration, then a DLL import from the cifX device driver (cifX32.dll / cifX64.dll) on the LabVIEW side. The Hilscher path is the most flexible – the same card can later be re-flashed as PROFINET, EtherCAT, or EtherNet/IP – but it adds the most engineering overhead.

3.3 SST cards (Woodhead / Molex)

The SST 5136-PFB-PCI and SST 5136-PFB-PCIE cards are common in legacy soft-PLC rigs where the original integration predates 2015. They ship with a Windows DLL and a C header file. LabVIEW generates the DLL wrapper VI through Tools > Import > Shared Library (DLL). Once the wrapper exists, the PROFIBUS configuration is loaded through the SST ConfigurationTool, and VIs call the exposed functions.

Catalog pinning: When the PROFIBUS configuration must survive software updates, export the GSD XML, the slot mapping, and the slot configuration index from the master tool and store it in the LV project source control. Without that, a Windows update that re-enumerates the PCI bus will change slot indices and break the link.

4. OPC-Based Integration (DA and UA)

OPC is the recommended path for the 80% of integrations that are supervisory: trending, historian mirroring, setpoint download, recipe exchange. The Siemens AS supports OPC natively via the SIMATIC NET OPC server, but more commonly a third-party server is used because LabVIEW's data-socket and DSC modules read OPC DA tags directly.

4.1 OPC DA path with SIMATIC NET

  1. Install SIMATIC NET PC software (e.g., V18 for current PCS 7 V9.1+) on the OPC server PC.
  2. Configure an S7 connection in the SIMATIC NET Configuration Console pointing at the CP 443-1 of the AS.
  3. Bind the OPC server to the S7 connection. Tag addresses are written using the Siemens item syntax S7:[S7_Connection_1]DB100,REAL0 for the first REAL of DB100.
  4. From LabVIEW, use the DSC module's Tag Engine or the DataSocket VIs to subscribe to opc://<host>/<server>/<item>.

4.2 OPC UA path with S7-1500 or PCS 7 V9

PCS 7 V9.x on S7-1500 exposes an OPC UA server directly on the CPU. The CPU 1515-2 PN / 1516-3 PN / 1518-4 PN/DP with firmware V2.9+ ships an OPC UA server that can be licensed with a 6ES7822-0AA00-0YA0 OPC UA licence. For the S7-400 path, OPC UA requires an external SIMATIC NET OPC UA Server or a third-party gateway such as KEPware or Softing's dataFEED OPC Suite.

4.3 Item address mapping (OPC DA)

PCS 7 tag AS location OPC DA item OPC UA NodeId
AI process value DB100.DBD0 (REAL) S7:[AS1]DB100,REAL0 ns=4;s=|var|CM_1241_DB_100.SpeedAct
Digital output DB100.DBX4.0 (BOOL) S7:[AS1]DB100,X4.0 ns=4;s=|var|CM_1241_DB_100.CmdRun
Counter DB100.DBW6 (INT) S7:[AS1]DB100,W6 ns=4;s=|var|CM_1241_DB_100.LotCount
Recipe array[0..9] DB200.DBD0..DBD36 10 × S7:[AS1]DB200,REAL<i> 10 UA nodes
PCS 7 naming gotcha: The OPC browse tree in WinCC uses the CFC chart block names (CTRL_PID / signal PV_IN) not raw DB offsets. LabVIEW should always read from the WinCC tag namespace or from the CFC block icon reference, not from internal CFC scratchpad addresses. Misnaming is the #1 cause of "value not updating" tickets.

5. Data Block Interface Design (DB as the Contract)

The field-validated practice – and one echoed by Siemens in the official PCS 7 product documentation – is to define a dedicated, version-numbered DB as the contract between PCS 7 and LabVIEW. The DB contains only the data that crosses the boundary: read-only inputs from PCS 7 to LabVIEW, write-only outputs from LabVIEW to PCS 7, and a handshake area.

// PCS 7 / STEP 7 STL excerpt — DB100 "LV_IFC"
DATA_BLOCK DB100
  TITLE = 'LabVIEW Interface V2.3'
  STRUCT
    VERSION      : WORD;        // 0x0203 -> V2.3, bumped on schema change
    HEARTBEAT_IN : BOOL;        // PCS 7 toggles every 1 s, LV reads
    HEARTBEAT_OUT: BOOL;        // LV toggles within 500 ms or AS trips watchdog
    AI_FLOW      : REAL;        // l/s, primary process value
    AI_PRESS     : REAL;        // bar
    AI_TEMP      : REAL;        // deg C
    AO_SETPOINT  : REAL;        // LV writes, AS clamps to safe range
    DO_PUMP_RUN  : BOOL;
    DO_VALVE     : BOOL;
    DI_STATUS    : WORD;        // bit-packed status word from LV
    RECIPE_ID    : INT;         // -1 = no recipe active
    ERROR_CODE   : INT;         // 0 = OK, others see error table
  END_STRUCT
END_DATA_BLOCK

The advantages are: (1) the boundary is searchable in STEP 7 cross-reference; (2) the LV developer can hand-write a U32 array in his application without knowing STEP 7; (3) when a value is wrong, the fingerpointing ends at the DB; and (4) PCS 7 OS operator control & monitoring attributes (OS = operator control, OM = monitoring, AU = archive) can be added on these signals without touching the LV side.

5.1 STEP 7 / TIA Portal attributes to apply

  • S7_m_c = true on AO_SETPOINT so the OS can write a manual override that the LV code must read.
  • S7_archive = true on AI_* to log into the WinCC archive.
  • S7_unit = "l/s", "bar", "degC" — these propagate to WinCC and OPC tag metadata.
  • S7_high_limit / S7_low_limit — engineering range used by the OS faceplate.

6. Step-by-Step: OPC DA over Ethernet (CP 443-1)

6.1 Prerequisites

  • PCS 7 V9.x with one AS (CPU 417-4H or CPU 1516-3 PN) and a CP 443-1 / CP 1543-1.
  • SIMATIC NET PC software V18 installed on the OPC server.
  • LabVIEW 2020+ with the DSC module (for the Tag Engine) or the base DataSocket VIs.
  • A free TCP port (default 102 for S7) between OPC server and AS.

6.2 Procedure

  1. Configure the CP 443-1 IP and S7 connection in PCS 7 Engineering. In HW Config, double-click the CP 443-1, set the Ethernet address (e.g., 10.10.10.5/24), and create a new S7 connection with partner OPC_PC, local TSAP 01.01, partner TSAP 01.01. Download the hardware configuration to the AS.
  2. Add DB100 (LV_IFC) in the S7 program. Apply the OS attributes listed in §5.1.
  3. Install SIMATIC NET PC software on the OPC PC. Reboot; the Configuration Console appears under Start > SIMATIC > SIMATIC NET.
  4. Add an S7 connection in Configuration Console: Mode = S7 client, partner IP = 10.10.10.5, local = OPC PC, partner TSAP = 01.01. Save and apply. The icon turns green if the connection is active.
  5. Bind the OPC server: In OPC Scout V10, navigate to Server > Connect > OPC.SimaticNET. Add an item with syntax S7:[S7_Connection_1]DB100,REAL0. The Quality flag should show Good.
  6. Configure the LabVIEW DSC Tag Engine: Open the Tag Configuration Editor, add an OPC tag with URL opc://<opcpc>/OPC.SimaticNET/S7:[S7_Connection_1]DB100,REAL0. Set deadband = 0.5% of range to throttle updates.
  7. Bind the tag to a front-panel indicator via a Shared Variable in the LV project. Set update rate = 100 ms for slow supervisory data.
  8. Write path: On a setpoint change in LV, write the scaled REAL into the Shared Variable; the DSC engine publishes it; SIMATIC NET writes to DB100,REAL100 in the AS, where the CFC program reads it.

6.3 Verification

  • OPC Scout shows Quality = Good for every bound tag.
  • In STEP 7, open DB100 online and watch HEARTBEAT_IN toggle and HEARTBEAT_OUT toggle within 500 ms.
  • WinCC faceplate on AO_SETPOINT shows the value LV wrote.
  • Latency from LV knob to OS faceplate should be < 1 s on a healthy 100 Mbit link.

7. Step-by-Step: PROFIBUS Master with Comsoft/NI Card

7.1 Prerequisites

  • PCIe/PXI PROFIBUS master card installed in the LabVIEW PC.
  • AS exposes DB100 and is connected to the PROFIBUS segment as a slave (or LabVIEW is added as a slave to the AS master).
  • GSD file for the Comsoft/NI slave available on the AS Engineering station.

7.2 Procedure (LabVIEW as PROFIBUS Slave to a Siemens Master)

  1. Install the NI PROFINET/PROFIBUS driver on the LV PC.
  2. Import the slave GSD in HW Config of the ES, drag the Comsoft slave into the PROFIBUS DP master system, assign slots, define I/O lengths (e.g., 32 bytes input, 32 bytes output).
  3. Download the HW Config to the AS. The AS now exchanges 32 bytes of process data with the LV PC each PROFIBUS cycle (typically 1–5 ms).
  4. In the S7 program, copy the 32 input bytes into a defined DB (e.g., DB110.PV[0..31] BYTE) and the 32 output bytes into another (DB110.SP[0..31] BYTE). This converts raw PROFIBUS bytes into a tagged interface.
  5. In LabVIEW, use the NI-PROFIBUS API VIs: niProfibus Open, niProfibus Read Process Data, niProfibus Write Process Data. The read returns a U32 array; map byte 0..3 to REAL, 4..7 to REAL, etc.
  6. Implement the heartbeat: byte 0 of output toggles every cycle; LV must mirror it within 2 cycles or the AS trips a PROFIBUS fault.

7.3 Procedure (LabVIEW as PROFIBUS Master to a Siemens Slave)

  1. Configure the Comsoft card as DP master in the NI configuration tool, set baudrate = 1.5 Mbps, address = 1, slot count = match the slave.
  2. Import the Siemens slave GSD (e.g., ET200S, Sinamics G120 with PROFIBUS option).
  3. Map the slave I/O to a local LV U32 array. Cyclic I/O at 1 ms update.
Determinism caveat: PROFIBUS cycle time is set by the master. Setting a 1 ms cycle on a segment with 16 slaves is not realistic — the bus arbitration delay and slave processing time must be added. Use Comsoft Profibus Diagnoser or SyCon to measure actual bus cycle before commissioning any closed-loop control through PROFIBUS.

8. DLL Wrapper Approach (Hilscher, SST, legacy cards)

When the PROFIBUS hardware does not ship with native LabVIEW VIs, the standard pattern is to wrap the manufacturer's DLL.

// Pseudo-C signature exposed by SST DLL
int PROFIBUS_Init(int slot, char* configFile);
int PROFIBUS_ReadI(int slot, int offset, unsigned char* buf, int len);
int PROFIBUS_WriteI(int slot, int offset, unsigned char* buf, int len);
int PROFIBUS_GetState(int slot, int* state, int* baud);

From LabVIEW, use Tools > Import > Shared Library (DLL), point at the .h header, configure the calling convention as stdcall (WINAPI), generate the wrapper VIs, and call them from a state machine that runs on a timed loop (1 ms or 5 ms depending on the bus cycle).

Wrapper pattern:

  1. Open the card once at startup.
  2. Maintain a U32 array in a shift register representing the last read.
  3. On each iteration, write the new output bytes, then read the new input bytes.
  4. Compute latency = tick count diff between read and write; alarm if > 2 × bus cycle.

9. USS Protocol for Sinamics / Micromaster Drives

For drive-only integration (e.g., a Micromaster 420/430/440 or Sinamics G110/G120), USS over RS485 is still the lowest-effort path. The protocol is Siemens-proprietary but well documented; a reference implementation in LabVIEW is published in the academic literature and is useful as a starting template.

9.1 USS telegram structure

STX | LGE | ADR | PKE | IND | PWE[2] | STW | HSW | BCC
0x02 | 0x0E | 0x01 | 0x0000 | 0x0000 | 0x0000 | 0x047E | 0x0000 | BCC

BCC = XOR of all bytes after LGE. PKE encodes parameter number (bits 0–10) and read/write (bit 11). STW = control word per VFD profile; bits 0 = ON/OFF1, 1 = OFF2, 2 = OFF3, 3 = enable, 4..6 = setpoint source.

9.2 LabVIEW timing

The minimum telegram spacing on RS485 is 2 characters (start/stop) at the configured baudrate. At 19.2 kbps with 14-byte telegrams, the theoretical cycle = (14 × 10 / 19200) ≈ 7.3 ms. The VFD responds within one character time + 5 ms internal. With multiple drives, the cycle scales linearly: 8 drives polled round-robin ≈ 60 ms.

Drives Baud 9.6 kbps Baud 19.2 kbps Baud 38.4 kbps Baud 115.2 kbps
1 ~30 ms ~15 ms ~8 ms ~3 ms
4 ~120 ms ~60 ms ~30 ms ~10 ms
16 ~480 ms ~240 ms ~120 ms ~40 ms
USS is not a real-time protocol. Do not close a fast control loop (≤ 50 ms) through USS. Use PROFIBUS or PROFINET with a Sinamics CU with PROFIBUS/PROFINET option for any loop tighter than 100 ms.

10. Performance, Timing, and Determinism

Cycle time is the integration's most miscalculated parameter. The following formulas apply.

10.1 PROFIBUS DP cycle time

T_cycle = T_slot × N_slaves + T_idle + T_master
T_slot (per slave) ≈ (2 + bytes_in + bytes_out) × 11 bits / baud

At 1.5 Mbps with 8 slaves averaging 16 I/O bytes, T_cycle ≈ 8 × ((2+32) × 11 / 1.5e6) ≈ 2 ms. Add 1 ms master turn-around → ~3 ms total.

10.2 OPC DA round-trip

Measured on a CP 443-1 with 100 tags cyclic at 500 ms update, end-to-end (AS write → OPC server → LV shared variable → front panel) ≈ 600–1200 ms. This is dominated by the OPC server polling interval, not the link latency.

10.3 OPC UA round-trip

With S7-1500 OPC UA at 100 ms subscription interval and 200 monitored items, round-trip ≈ 100–250 ms.

Choose the path based on what the slowest tolerable closed loop requires. For supervisory trending and lab analytics, OPC is the right tool. For closed-loop control or fast acquisition, PROFIBUS/PROFINET is mandatory.

11. Troubleshooting Matrix

Symptom Probable cause Diagnostic Fix
OPC item quality = Bad S7 connection in SIMATIC NET down Configuration Console shows red connection Verify CP 443-1 IP, rack/slot, TSAP. Re-establish.
OPC quality = Good but value stuck Wrong DB offset / bit STEP 7 online DB monitor Re-map item to actual DB number/offset.
PROFIBUS slave drops off bus Termination missing or doubled Bus diagnostic with oscilloscope on A/B lines Enable termination only on the two end nodes.
PROFIBUS OK at 1.5 Mbps, fails at 12 Mbps Cable length / stub length too long Check cable spec (Siemens PROFIBUS cable 6XV1830-0EH10) Limit stubs to < 0.3 m at 12 Mbps, < 1 m at 1.5 Mbps.
LV DLL call returns -1 Driver service not running Windows services: cifX Driver / SST Device Service Set service to Automatic, restart.
LabVIEW reads garbage REAL Byte swap missing Compare DB monitor with LV indicator Apply Swap Bytes or use Big-Endian conversion.
Heartbeat trips watchdog LV loop starved by Windows Check jitter with Tick Count (ms) Move loop to RT target (PXI / cRIO) or increase watchdog.
OPC UA certificate rejected Self-signed cert from S7-1500 not trusted OPC UA client log Install cert into Windows Trusted Root, or issue cert from corporate CA.
USS drive times out intermittently Two devices same address Drive address in P2010 Unique address per node, broadcast = 0 reserved.

12. Best Practices and Field-Proven Caveats

  • Single interface contract. One DB, one OPC namespace, one PROFIBUS slave slot. If LabVIEW needs more, version the DB (DB100 v2.3, DB101 v2.3) rather than silently adding fields.
  • Bidirectional heartbeat. Both sides toggle a bit every cycle. If either side misses 3 toggles, the other enters safe state. This catches Windows sleep, blue-screens, and stuck loops faster than any watchdog timer.
  • Always pin LV hardware slot. When using PCI PROFIBUS cards, fix the PCI slot index in the configuration tool. Slot enumeration changes after BIOS updates and Windows feature updates.
  • Document the byte map. A single Excel sheet with column = byte offset, datatype, engineering unit, scaling, and source/target is the single best investment for long-term maintenance.
  • Avoid OPC for control loops. OPC DA over Ethernet is non-deterministic. Use it for trending, historian mirroring, recipe exchange. Use PROFIBUS/PROFINET for any closed loop tighter than 100 ms.
  • License audit on OPC. SIMATIC NET OPC DA server licence is per CPU connection. SIMATIC NET OPC UA is licensed separately. KEPware charges per tag count; tag explosion is a real budget risk.
  • Version the LV interface. First WORD of DB100 is the interface version (0x0203 = V2.3). PCS 7 code refuses to start if LV reports a mismatched version, or LV refuses to interpret a schema it doesn't recognise. This prevents silent corruption during upgrades.
  • Validate with the lab reference. The published USS implementation in LabVIEW (see USS protocol implementation literature) is a usable baseline; the hardware handshaking layer is the same regardless of vendor drive.
Official resources: The PCS 7 platform overview, supported AS catalog (S7-400, S7-410, S7-1500), and the licensing model are documented on the official Siemens SIMATIC PCS 7 product page (SIMATIC PCS 7 Distributed Control System). For drive integration via USS, the public-domain LabVIEW implementation paper (Implementation of Siemens USS Protocol into LabVIEW, ScienceDirect, 2009) provides the reference telegram and timing model. STEP 7 / TIA Portal attribute documentation is published in the Siemens Industry Online Support portal under the SIMATIC S7-1500 / S7-400 manuals.

13. FAQ

Can LabVIEW replace the AS in a PCS 7 plant?

No. PCS 7 is a certified DCS; the AS executes SIMATIC controllers with WinCC safety and OS integration. LabVIEW can act as a PROFIBUS/OPC client or as a DP slave, but it does not run the PCS 7 ES/OS. Use LabVIEW for analytics, custom HMI, and lab/test-rig integration around the AS.

Which PROFIBUS card should I buy for LabVIEW in 2024+?

For new projects, the Comsoft/NI PROFINET/PROFIBUS cards (PCIe or PXI) are the lowest-risk choice because they ship with native LabVIEW VIs and Master/Slave configuration tools. Hilscher cifX cards are a strong second choice if you also need PROFINET or EtherNet/IP from the same hardware. SST cards remain viable only when extending a pre-2015 installation.

Is OPC UA supported directly on S7-400 with PCS 7 V9?

S7-400 CPUs do not embed an OPC UA server. The path is to run a SIMATIC NET OPC UA server (or third-party gateway such as KEPware or Softing dataFEED) on a PC connected via CP 443-1. S7-1500 CPUs with firmware V2.9+ ship an OPC UA server natively, so OPC UA on PCS 7 V9.x with S7-1500 AS is significantly simpler.

How fast can OPC DA update for 500 tags?

With SIMATIC NET OPC DA and a CP 443-1, expect ~500 ms cyclic update at 500 tags. Increasing the update rate above 250 ms does not improve determinism because the AS OB1 cycle (typically 100 ms) becomes the floor. For sub-100 ms updates, use PROFIBUS/PROFINET or OPC UA with S7-1500.

What data-block attributes must I set so WinCC shows the LabVIEW interface?

In STEP 7 / TIA Portal, set S7_m_c = true on operator-controlled fields, S7_archive = true on archived fields, and assign S7_unit, S7_high_limit, and S7_low_limit for faceplate display. The WinCC tag manager then auto-imports the DB symbols into the OS faceplate tree without any further WinCC-side configuration.

Can I use the same PROFIBUS card for PROFINET later?

Yes on Hilscher cifX cards: the firmware is re-flashed through SyCon to switch between PROFIBUS, PROFINET, EtherCAT, and EtherNet/IP. NI/Comsoft and SST cards are protocol-fixed and cannot be re-flashed; replace the card if the protocol must change.