Siemens Profibus PA Hardware: S7-300 + ET 200M Selection Guide

David Krause22 min read
ProfibusSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

This technical reference validates and expands a Siemens bill of materials for a remote monitoring installation that reads 25 PROFIBUS PA instruments and 5 4..20 mA analog devices. The architecture combines a SIMATIC S7-300 CPU 314C-2PN/DP, an ET 200M distributed station fronted by an IM 153-2 High Feature interface module, an FDC 157-0 DP/PA field-device coupler, a PS307 / SITOP Modular 24 V supply tree, PROFIBUS FC Process cable, SplitConnect taps, SIMATIC PDM V8.x, STEP 7 Professional 2010 SR4, and WinCC flexible 2008 Advanced for HMI. The complete topology is one PROFIBUS DP segment that terminates at two FDC 157-0 couplers, each driving one PROFIBUS PA segment with multiple SplitConnect taps.

PROFIBUS PA is defined by IEC 61158-2 and operates on the 31.25 kbit/s Manchester Bus Powered (MBP) physical layer. The bus carries both data and 24 V device power on the same twisted pair, which is why the DP/PA coupler (FDC 157-0) supplies a regulated 31 V at up to 1000 mA to the segment while isolating the PA segment from the DP master. For an automation cell of this size the FDC 157-0 is the right component; the alternative FDC 157 (without the trailing 0) is the older, Ex-restricted revision and is generally superseded by the FDC 157-0 in non-Ex installations. An active field distributor (AFD) is only required if you need star topology with more than the linear trunk the FDC supports.

Reference standards: IEC 61158-2 (MBP physical layer), IEC 61784-1 (PROFIBUS profile), PROFIBUS PA Profile 3.01/3.02 for process automation devices. All compliance claims should be verified against the latest edition of the standard before procurement.

System Architecture and Topology

The control cabinet architecture is intentionally simple. The S7-300 CPU hosts a DP master on its integrated PROFIBUS interface (X2), which is wired directly to the IM 153-2 High Feature in the ET 200M. The ET 200M backplane hosts two BM DP/PA bus units; the FDC 157-0 plugs into one of those bus units, isolating the PA segment and converting it to a logical extension of the same DP line. Each PA segment is wired with PROFIBUS FC Process cable and terminated with SplitConnect terminators; instruments are connected through SplitConnect taps so that a device can be removed without breaking the trunk.

S7-300 CPU 314C-2PN/DP6ES7314-6EH04-0AB0 (DP Master)ET 200M IM 153-2 HF6ES7153-2BA02-0XB0FDC 157-0 (DP/PA)6ES7157-0AC83-0XA0PA Tap #1PA Tap #2PA Tap #3PA Tap #4Pressure x 8Temp x 6Flow x 6Level x 5Legend: Blue = PROFIBUS DP (12 Mbit/s), Green = PROFIBUS PA (31.25 kbit/s)

CPU Selection: S7-300 CPU 314C-2PN/DP

Parameter Value
Order code (MLFB) 6ES7314-6EH04-0AB0
Work memory (code + data) 192 KB
Integrated PROFINET interface 2-port switch (X1 P1R, X1 P2R)
Integrated PROFIBUS DP master X2 (DP, RS-485)
Max. PROFIBUS DP slaves 32 (address range 1..125 by parameter)
Bit instruction time 0.06 µs typical
Integrated digital I/O 24 DI / 16 DO / 4 AI / 2 AO on -2PN variant (-2DP has none)
Firmware release V3.3 (matches the EH04 hardware release)
Required MMC SIMATIC Micro Memory Card

The 314C-2PN/DP compact CPU is a balanced choice for a 25-instrument PA plant when no PCS 7 library blocks are required. The integrated PROFIBUS DP master on X2 is used to drive the ET 200M, the FDC 157-0, and (via the PA segments) all 25 PA field devices. The two PROFINET ports are typically reserved for the HMI panel connection and the engineering station; this BOM does not include a Comfort panel, but the PN ports are useful even with WinCC flexible 2008 if you later migrate to TIA Portal / WinCC Professional.

Why not a 315-2 PN/DP or 317-2 PN/DP? A 315-2 PN/DP (6ES7315-2EH14-0AB0, 384 KB work memory) is the more common choice for medium-sized PA cells with HMI redundancy and more DP slaves. The 317-2 PN/DP (6ES7317-2EK14-0AB0, 1 MB) is reserved for PCS 7 AS 410 stations. For a non-PCS 7 single-CPU topology with WinCC flexible 2008 and only one DP segment, the 314C-2PN/DP is the minimum recommended and is fully sufficient.

If the project later grows above 8 DP slaves, or if the OB1 cycle needs more headroom for the PA cyclic data exchange, the next logical step is the 315-2 PN/DP. The order code suffix EH14 denotes the hardware release 14 with PROFINET V2.3 and supports iDevice, MRP, and IRT, all of which are not strictly required for this architecture but useful for future PROFINET migration of the analog devices.

Memory Card and Working Memory

The MMC is mandatory for S7-300 CPUs from the 31x series onward; the load memory is no longer built in.

Option MLFB Size Use case
Selected 6ES7953-8LJ30-0AA0 4 MB Default for 314C with project + recipe
Alternative 6ES7953-8LL30-0AA0 8 MB If WinCC flexible archives are mirrored to the CPU
Alternative 6ES7953-8LM30-0AA0 16 MB Service / multiple project versions
Mandatory: The S7-300 will not retain the user program without an MMC. Always insert the MMC before the first download; a missing MMC generates SF (system fault) and the CPU remains in STOP with diagnostic buffer entry "No memory card inserted".

Distributed I/O: ET 200M with IM 153-2 High Feature

The ET 200M in this BOM acts as the physical home for the FDC 157-0 and (optionally) the SM 331 analog module used for the five 4..20 mA instruments. The IM 153-2 High Feature variant is required because the standard IM 153-1 does not support the active bus module BM DP/PA that the FDC 157-0 needs.

Component MLFB Role
IM 153-2 High Feature 6ES7153-2BA02-0XB0 DP slave interface, supports up to 12 S7-300 I/O modules + active bus modules for FDC
Bus unit for slot 0 (PS/IM) 6ES7195-7HA00-0XA0 Carries 24 V and PROFIBUS onto the backplane
Bus unit BM DP/PA 6ES7195-7HF80-0XA0 Active bus module for FDC 157-0
Rail 483 mm (5 slots) 6ES7195-1GA00-0XA0 Mechanical carrier for up to 5 active bus modules
Bus connector (90°) 6ES7972-0BA12-0XA0 PROFIBUS DP connector with PG socket (qty 2 for IM + FDC)

The IM 153-2 High Feature supports up to 12 I/O modules, supports S7 redundancy in HF mode (with two IM 153-2 HF in parallel, requires STEP 7 redundancy block library), and supports value status / time stamping with the corresponding PROFIBus profile. None of these HF features are required for a non-redundant monitoring station, but the IM 153-2 HF is still the correct choice because the standard IM 153-1 (6ES7153-1AA03-0XB0) physically cannot host an FDC 157-0.

Slot 0 is reserved for the PS/IM bus unit. The FDC 157-0 must be plugged into a slot that has a BM DP/PA active bus unit installed; you cannot plug it into an ordinary I/O slot. Plan the ET 200M rail so that the BM DP/PA and the BM for SM 331 occupy two separate slots. With the 483 mm rail you have five bus module slots, which is enough for one IM, one BM DP/PA (FDC), and one BM for the SM 331 plus two spares.

DP/PA Coupling: FDC 157-0 Field Device Link

The FDC 157-0 (Field Device Coupler) is the translator between the PROFIBUS DP segment at 9.6 kbit/s to 12 Mbit/s and the PROFIBUS PA segment at fixed 31.25 kbit/s. It is not a passive media converter; it has its own address on the DP segment and is configured in STEP 7 Hardware Configuration just like any DP slave. From the DP master's point of view, every PA device behind an FDC appears as a separate DP slave on the same DP line; the FDC itself occupies one DP address.

Parameter Value
Order code 6ES7157-0AC83-0XA0
Mounting Active bus module on ET 200M (BM DP/PA 6ES7195-7HF80-0XA0)
PA supply voltage 31 V DC (regulated from ET 200M 24 V)
Max. PA segment current 1000 mA
Max. PA devices per FDC Up to 31 in non-Ex (limited by current budget and address space)
Ex version 6ES7157-0AD83-0XA0 (FDC 157-0 Ex, FISCO)
Diagnostic DPV0 slave; diagnostics via DP standard diagnostics
Required GSD SIEM8157.GSD (or higher; ships with STEP 7)

For 25 PA devices you do not need two FDCs from a current-budget point of view; the FDC 157-0 can supply up to 1000 mA, and a typical PA instrument draws 10 to 20 mA. 25 devices × 20 mA = 500 mA, well inside the 1000 mA budget. However, the original BOM lists two FDC 157-0 units, which is still a reasonable choice if you split the field devices into two physical segments (one per process area) for faster troubleshooting and a shorter bus cycle. Each FDC occupies one DP address and limits the cyclic data exchange to the PA devices on its segment.

Address budget: 25 PA devices + 1 ET 200M + 2 FDC 157-0 = 28 PROFIBUS addresses. The CPU 314C supports up to 32 DP slaves in DPV0 mode and is not a bottleneck. Each PA device requires a unique PROFIBUS address (1..125). Addresses on the same PA segment must be unique; the address is set either via a DIP switch on the device or via SIMATIC PDM if the device supports software addressing (PROFIBUS PA Profile V3.0+).

Power Supply Architecture

The control cabinet needs two distinct 24 V rails: a clean, regulated 24 V for the S7-300 / ET 200M / FDC 157-0 logic, and a separate SITOP rail for the analog instruments and any third-party loads. Using a separate SITOP rail for the analog instruments prevents ground loops and noise from corrupting the 4..20 mA signals.

Component MLFB Output Use
PS307 (10 A) 6ES7307-1KA02-0AA0 24 V DC / 10 A S7-300 CPU + IM 153-2 + FDC 157-0
SITOP Modular Plus 20 6EP1336-3BA00-8AA0 24 V DC / 20 A PA segment instrumentation supply (in original BOM)
SITOP Modular Plus 40 6EP1437-3BA00-8AA0 24 V DC / 40 A Alternative when PA field supply + analog load total exceeds 20 A

Power budget (24 V DC cabinet rail):

  1. CPU 314C-2PN/DP: typically 0.6 A @ 24 V (from datasheet).
  2. IM 153-2 HF: 0.6 A @ 24 V typical, peak 1.0 A.
  3. FDC 157-0: 0.6 A @ 24 V plus the PA segment current (up to 1.0 A on the PA side).
  4. SM 331 (1KF02) AI8: 0.2 A @ 24 V (transducer feed excluded).
  5. SplitConnect Tap 6GK1905-0AA00: negligible (~10 mA each, for active terminator electronics if used).
  6. Total logic rail budget (worst case): 0.6 + 1.0 + 0.6 + 0.2 = 2.4 A.
  7. Available headroom on PS307 (10 A): 10 - 2.4 = 7.6 A, sufficient.

The PA segment supply current is provided by the FDC 157-0 itself, not by the 24 V rail directly. The FDC accepts 24 V on its ET 200M backplane feed and generates the regulated 31 V needed for MBP. Therefore the SITOP Modular in the BOM is intended for the non-PA loads (analog instruments, relays, fans, lights), not for the FDC. This is a common point of confusion that should be flagged during cabinet design review.

PROFIBUS PA Network Components

Component MLFB Role
SplitConnect Tap 6GK1905-0AA00 Passive T-junction for connecting one PA device to the trunk without interrupting the bus
SplitConnect Terminator 6GK1905-0AE00 Active bus terminator for the PA trunk end
PROFIBUS FC Process Cable (blue) 6XV1830-5EH10 Type A cable, PE sheath, UV-stable, suitable for permanent installation in process plants and outdoors
PROFIBUS FC Standard Cable (violet) 6XV1830-0EH10 Type A cable, PVC sheath, indoor use only (the 2 m in the BOM is for the DP drop to the IM 153-2)
PROFIBUS bus connector 6ES7972-0BA12-0XA0 90° PROFIBUS connector with PG diagnostic socket, terminating resistor switchable

PROFIBUS PA requires two terminators per segment, one at each end of the trunk. With a linear topology, the SplitConnect Terminator (6GK1905-0AE00) is the correct component to terminate the remote end of the trunk; the FDC 157-0 already contains the termination for the cabinet end internally. If you use the SplitConnect Tap on both ends, you also need a terminator block. The 6GK1905-0AA00 tap itself is a passive junction with no internal termination.

PROFIBUS PA Trunk Length Calculation

PROFIBUS PA (31.25 kbit/s) supports a maximum trunk length of 1900 m using Type A cable (PROFIBUS FC Process) when no repeaters are used and the cable parameters meet the IEC 61158-2 specification (impedance 100 Ω ± 20%, loop resistance ≤ 44 Ω/km, attenuation ≤ 3 dB/km at 39 kHz). The original BOM lists 1250 m of FC Process cable, which is comfortably within the 1900 m budget and leaves ~650 m for installation tolerances and spare.

Spur length (from the trunk tap to the field device) is limited by the IEC 61158-2 MBP rules:

Number of devices on the segment Max. spur length (Type A cable)
1..12 120 m
13..14 90 m
15..18 60 m
19..24 30 m
25..32 1 m (essentially daisy-chain only)

For 25 devices you must keep each spur ≤ 1 m, which means physical layout must be a daisy-chain rather than a star. If the field layout forces star topology, the correct alternative is an AFD (Active Field Distributor, 6ES7157-0AG00-0XA0), which repeats the bus and removes the spur-length restriction.

Engineering Software Stack

Component MLFB Purpose
STEP 7 Professional 2010 SR4 / V5.5 SP4 6ES7810-5CC11-0YA5 Hardware Configuration, S7 program, NetPro, PDM integration
SIMATIC PDM V8.0 (100-tag) 6ES7658-3KX08-0YA5 PA device EDD library, parameter assignment, diagnostics
SIMATIC PDM V8.1 (upgrade) 6ES7658-3KD18-0YA5 Upgrade to support latest device EDDs (recommended if newer E+H devices are present)
WinCC flexible 2008 Advanced 6AV6613-0AA51-3CA5 HMI configuration, tags, screens, alarms
WinCC flexible /Archives 6AV6618-7ED01-3AB0 Adds tag logging / alarm logging runtime to WinCC flexible Advanced
TIA Selection Tool Free download Engineering-time validation of the BOM, configuration of the ET 200M, FDC, and PA trunk

Use the TIA Selection Tool to validate the entire BOM before placing the purchase order; the tool flags invalid combinations (e.g., wrong bus unit for the FDC, missing active bus module) and exports an HWCN export that STEP 7 can import.

SIMATIC PDM Integration for PA Device Commissioning

SIMATIC PDM is the Siemens Device Manager and is mandatory for proper commissioning of PROFIBUS PA instruments. The integration steps with STEP 7 V5.5 are documented in detail in the Siemens support article Configuring field devices with SIMATIC PDM V5.2+SP1 and Hardware Configuration in PCS 7 V6.0 (the procedure for non-PCS 7 STEP 7 V5.5 is identical). The lifecycle steps for each PA device are:

  1. Import the device EDD: PDM > Device Integration Manager > install the Endress+Hauser EDD package (or import the GSD if no EDD is available).
  2. Insert the device in HW Config: right-click on the FDC 157-0 > "Insert PROFIBUS PA Slave" > choose the device from the catalog. The device gets a PROFIBUS address automatically; you can edit it.
  3. Open the device in PDM: right-click > "Open Object" (or the "Open in PDM" toolbar button). PDM connects to the live device over PROFIBUS.
  4. Assign the tag: set TAG, descriptor, message, and unit parameters under "Identification".
  5. Parameterize: configure measurement range, damping, output scaling, and HART-style device variables.
  6. Download: "Download to device" writes the parameters into the PA instrument's non-volatile memory.
  7. Diagnostic: use "Online > Diagnostics" to read device status, last calibration date, simulation mode, and write-protected parameters.

When a device is replaced, PDM retains the parameter set as the "plant view" assignment, so a new physical device can be brought into service with a single "Load to PG" / "Download to device" cycle. This is one of the strongest arguments for using PDM in a plant with 25 PA devices.

PROFIBUS PA Network Configuration in STEP 7

Configuration of the PA segment in STEP 7 V5.5 follows a few non-obvious rules; the official procedure is summarized in How do you configure a PROFIBUS PA network in STEP 7?. Key points:

  • PA slaves are always connected to the DP/PA coupler (FDC 157-0) inside HW Config; you cannot attach them directly to a DP line.
  • The FDC 157-0 occupies one DP address and is configured with the GSD file SI08157.GSD (or later SIEM8157.GSD depending on STEP 7 release).
  • Each PA device is configured individually under the FDC node as a sub-slave, with its own address (1..125).
  • The bus cycle time on a PA segment is dominated by the number of devices and the number of cyclic input/output bytes per device; with 25 PA devices at 4 bytes input + 2 bytes output each, the typical acyclic + cyclic cycle is 1..2 seconds. If the application requires faster update, reduce the number of devices per FDC.

The PROFIBUS DP segment between the CPU and the IM 153-2 runs at 1.5 Mbit/s by default (the highest baud that all devices in this BOM support), giving a DP cycle well below 50 ms. The PA cycle is independent of the DP cycle and is the dominant latency for the operator screens.

4..20 mA Device Integration via SM 331

The five 4..20 mA instruments that are not PROFIBUS PA are brought into the S7-300 by an SM 331 analog input module. The original BOM lists the 6ES7331-1KF02-0AB0, which is an 8-channel, 13-bit resolution analog input module with two-wire transducer feed.

Parameter Value
Order code 6ES7331-1KF02-0AB0
Inputs 8 AI, differential
Resolution 13 bits + sign (12 bits usable)
Measurement ranges ±50 mV, ±500 mV, ±1 V, ±5 V, ±10 V, 0..20 mA, 4..20 mA, Pt100, Pt1000, Ni100, thermocouples
Two-wire transducer feed 24 V / 30 mA per channel (resettable fuse)
Required front connector 6ES7392-1AM00-0AA0 (20-pin, screw type)
Galvanic isolation Yes (channel-to-backplane, channels not isolated from each other in groups of 4)

For only five 4..20 mA channels the SM 331 is over-provisioned; an alternative is the 6ES7331-1KF01-0AB0 (8 AI, 12-bit) if 13-bit is not required, or the 6ES7331-7KB02-0AB0 (2 AI, 9/12/14-bit) if you need only two channels and want the highest precision per channel. The original BOM choice is correct and gives you three spare channels.

Wiring rule: Connect the 4..20 mA signal wire to the I+ / I- terminals of the SM 331 and the 24 V transducer supply to the front-connector terminals labelled "M+/M-". For 2-wire loop-powered instruments, use the integrated 24 V transducer feed; for 4-wire active instruments, wire only the signal leads and provide 24 V separately from the SITOP rail.

Engineering Network Stack: WinCC flexible 2008 vs WinCC Professional / TIA Portal

WinCC flexible 2008 Advanced is supported with STEP 7 V5.5 and runs on Comfort Panels, Panels, and IPC-based Runtime. The licensing model is per seat (developer license) with a runtime license per panel. For a remote monitoring station the minimum configuration is:

  • WinCC flexible 2008 Advanced Engineering (6AV6613-0AA51-3CA5): one developer seat.
  • WinCC flexible /Archives option (6AV6618-7ED01-3AB0): enables tag and alarm logging on the panel or on a PC runtime.
  • Runtime license: per-panel runtime license (e.g., 6AV6613-1AA51-3CA5 for a 10" Comfort panel).

The official communication documentation for WinCC flexible 2008 with S7-300 is in two parts (Communication Part 1 and Communication Part 2) on the Siemens support portal. Both documents must be read before commissioning because the protocol selection (PROFINET, PROFIBUS, MPI/DP) and the connection resource configuration in the S7-300 are interlinked.

If a later migration to TIA Portal / WinCC Professional is anticipated, consider keeping the project in STEP 7 V5.5 format for now; WinCC flexible 2008 projects can be migrated to TIA Portal with the WinCC flexible migration tool. A direct TIA Portal commissioning from day one is also valid and recommended for new projects, but it requires WinCC Professional (not WinCC flexible) and a TIA Portal STEP 7 license.

Verification and Commissioning Checklist

  1. Mechanical installation: verify the ET 200M rail length matches the number of bus modules; the 483 mm rail (6ES7195-1GA00-0XA0) fits five active bus modules. Confirm the BM DP/PA (6ES7195-7HF80-0XA0) is plugged into the correct slot for the FDC.
  2. 24 V wiring: verify the PS307 (10 A) feeds only the S7-300 logic. The SITOP Modular 20/40 feeds the analog instruments and any non-PA load.
  3. PROFIBUS DP wiring: check the two PROFIBUS bus connectors (6ES7972-0BA12-0XA0): one at the CPU end (terminated, switch ON), one at the IM 153-2 end (terminated, switch ON). Measure 220 Ω between pins 3 and 8 with the device powered down — you should see ~110 Ω if exactly two terminators are active, or an open circuit if none.
  4. PROFIBUS PA wiring: measure ~100 Ω between the two cores of the PA trunk with all devices disconnected. The FDC 157-0 already terminates one end internally; the SplitConnect Terminator (6GK1905-0AE00) is required at the far end.
  5. Address plan: confirm no duplicate PROFIBUS addresses on the DP segment. CPU is master only (does not consume an address). IM 153-2 = DP address 3 (typical). FDC 157-0 #1 = DP address 4. FDC 157-0 #2 = DP address 5. PA devices = DP addresses 6..30 on each segment.
  6. STEP 7 HW Config: download the HW configuration. Resolve any GSD/EDD warnings before testing cyclic IO.
  7. PDM commissioning: for each PA device, load the EDD, assign the tag, parameterize the device, and download. Verify the value status (good / uncertain / bad) under PDM Online > Diagnostics.
  8. SM 331 calibration: with all five 4..20 mA instruments disconnected, perform the SM 331 "Module Calibration" step in STEP 7 HW Config (right-click the module > "Calibrate"). This removes the module-specific offset.
  9. WinCC flexible screens: download the project to the HMI. Verify each tag is updating with the expected value range. Simulate an alarm and confirm the alarm log is populated.
  10. Long-term stability: run the bus for 24 hours, then check the CPU diagnostic buffer for any transient PROFIBUS errors. Even a single DP station failure on a clean bus indicates a wiring or termination problem.

Common Pitfalls and Configuration Corrections

Pitfall Symptom Correction
FDC 157 (no -0) selected instead of FDC 157-0 Cannot be plugged into the BM DP/PA in current ET 200M Use 6ES7157-0AC83-0XA0 (FDC 157-0, non-Ex) or 6ES7157-0AD83-0XA0 (Ex)
Wrong IM 153 variant FDC 157-0 not recognized, BM DP/PA does not lock Use IM 153-2 High Feature (6ES7153-2BA02-0XB0) — IM 153-1 does not support active bus modules
PS307 used for PA field supply PA segment voltage collapses when CPU powers down Use a dedicated SITOP rail, or rely on the FDC 157-0's internal PA generation
Duplicate DP addresses Random station failures on the DP segment Re-number the offending device, restart the CPU
Missing PA terminator PA devices go on and offline sporadically, FDC reports diagnostic "PA short circuit / open circuit" Install SplitConnect Terminator 6GK1905-0AE00 at the far end of the trunk
WinCC flexible project over the 128 KB limit Tag logging dropped or HMI compile errors Add the WinCC flexible /Archives option (6AV6618-7ED01-3AB0), or move to WinCC Professional
Ex-zone FDC selected for non-Ex zone PA voltage limited, fewer devices per segment Use FDC 157-0 non-Ex (6ES7157-0AC83-0XA0) which supports 1000 mA / 31 V
Wrong cable type outdoors Insulation failure after UV exposure Use PROFIBUS FC Process (6XV1830-5EH10) for outdoor / process installations; FC Standard (6XV1830-0EH10) is PVC indoor only

Source Part Numbers and Default Quantities Summary

MLFB Description Qty
6ES7314-6EH04-0AB0 S7-300 CPU 314C-2PN/DP Compact 1
6ES7953-8LJ30-0AA0 SIMATIC MMC 4 MB 1
6ES7390-1AE80-0AA0 S7-300 mounting rail 480 mm 1
6ES7153-2BA02-0XB0 ET 200M IM 153-2 High Feature 1
6ES7195-7HA00-0XA0 Bus unit for ET 200M (PS/IM slot 0) 1
6ES7195-7HF80-0XA0 Bus unit BM DP/PA for FDC 157-0 1
6ES7195-1GA00-0XA0 Rail 483 mm for ET 200M (5 active slots) 1
6ES7157-0AC83-0XA0 FDC 157-0 DP/PA Coupler (non-Ex, 1000 mA / 31 V) 2
6ES7972-0BA12-0XA0 PROFIBUS bus connector 90° with PG socket 2
6GK1905-0AA00 SplitConnect Tap 2
6GK1905-0AE00 SplitConnect Terminator 1
6ES7307-1KA02-0AA0 PS307 stabilized power supply 24 V / 10 A 1
6EP1336-3BA00-8AA0 SITOP Modular Plus 20 (24 V / 20 A) 1
6EP1437-3BA00-8AA0 SITOP Modular Plus 40 (24 V / 40 A) — optional upgrade (1)
6XV1830-5EH10 PROFIBUS FC Process cable (blue, PE, outdoor) 1250 m
6XV1830-0EH10 PROFIBUS FC Standard cable (violet, PVC, indoor) 2 m
6ES7331-1KF02-0AB0 SM 331 AI8 × 13-bit 1
6ES7392-1AM00-0AA0 20-pin screw front connector for SM 331 3
6ES7658-3KX08-0YA5 SIMATIC PDM V8.0 (100 tags) 1
6ES7658-3KD18-0YA5 SIMATIC PDM V8.1 upgrade 1
6ES7810-5CC11-0YA5 STEP 7 Professional 2010 SR4 / V5.5 1
6AV6613-0AA51-3CA5 WinCC flexible 2008 Advanced (engineering) 1
6AV6618-7ED01-3AB0 WinCC flexible /Archives option 1
6GK1901-1BB10-2AA0 RJ45 plug for IE FC Flexible cable 2
6XV1870-2B IE FC Flexible cable 50 m

FAQ

Do I really need two FDC 157-0 couplers for 25 PROFIBUS PA devices?

Not strictly from a current-budget perspective — one FDC 157-0 (6ES7157-0AC83-0XA0) can supply 1000 mA at 31 V, and 25 PA instruments at 20 mA each only consume 500 mA. Two FDCs are still a reasonable choice to split the plant into two PA segments (e.g., process area A and area B), which shortens the bus cycle and simplifies troubleshooting. If you go to one FDC, ensure the total current does not exceed 1000 mA.

What is the maximum length of the PROFIBUS PA trunk in this topology?

1900 m with Type A cable such as PROFIBUS FC Process (6XV1830-5EH10). The BOM specifies 1250 m, which is well within the limit and leaves margin. Spur length is limited to 1 m when 25..32 devices share a segment; if star topology is required, replace the FDC with an Active Field Distributor (AFD, 6ES7157-0AG00-0XA0).

Can the S7-300 CPU 314C-2PN/DP replace an S7-400 in a PCS 7 project?

No. PCS 7 AS 410 stations require S7-400 CPUs (e.g., CPU 410-5H) with the corresponding PCS 7 release. The S7-300 supports only a subset of the PCS 7 library and is generally limited to non-PCS 7 STEP 7 programs. This BOM is explicitly for a non-PCS 7 project with WinCC flexible 2008 Advanced, so the S7-300 is the correct choice.

Which SIMATIC PDM version matches this hardware?

PDM V8.0 (6ES7658-3KX08-0YA5) supports the entire BOM. PDM V8.1 (6ES7658-3KD18-0YA5) is the recommended upgrade because it ships with newer device EDDs (including recent Endress+Hauser PA instruments) and improved HART-over-PROFIBUS handling. Both versions are compatible with STEP 7 V5.5 SP4 / STEP 7 Professional 2010 SR4.

How do I import a PROFIBUS PA device into STEP 7 and SIMATIC PDM?

First install the device EDD in SIMATIC PDM (Device Integration Manager). In STEP 7 Hardware Configuration, right-click the FDC 157-0 entry and choose "Insert PROFIBUS PA Slave"; select the device from the catalog. Right-click the inserted device and "Open in PDM" to parameterize it. The full procedure is documented in the Siemens support article Configuring field devices with SIMATIC PDM.

What is the difference between the FDC 157 and the FDC 157-0?

The FDC 157 (6ES7157-0AA83-0XA0) is the older revision, limited to Ex applications with reduced segment current. The FDC 157-0 (6ES7157-0AC83-0XA0) is the non-Ex successor, supports up to 1000 mA / 31 V, and is the current catalog product for new installations. The BOM in this article specifies the FDC 157-0, which is correct for non-Ex process plants.

Back to blog