Overview
An S7-300 PLC reporting a 150 ms scan cycle time is operating well outside its expected envelope. A correctly configured S7-300 with a typical automation program, 15 Profibus slaves, and standard communication load should complete a full cyclic scan in 10-30 ms. Values above the configured scan monitoring time (default 100-150 ms depending on CPU class) place the CPU at the edge of a watchdog trip and produce process-visible jitter on the Profibus and optical-fiber uplinks to the master S7-400.
This article walks through field-proven diagnostic steps for the S7-300 cycle-time problem, the OB priority architecture that controls execution order, and program-level optimizations that bring a sluggish CPU back into the 10-30 ms band without changing hardware. All parameter paths reference the standard STEP 7 V5.x / TIA Portal V16+ project layout used with S7-300 stations.
S7-300 CPU Scan Cycle Baselines
Before treating a 150 ms scan time as abnormal, baseline the expected value for the specific CPU in the slot. S7-300 bit-operation times range from 0.01 µs to 0.2 µs depending on the CPU generation. A fully loaded CPU 315-2 DP with a 32 KB MC7 program, 8 Profibus slaves, and HMI communication still typically scans in 10-20 ms.
| CPU | Order number (MLFB) | Bit op time | Work memory | Typical scan @ 32 KB MC7 |
|---|---|---|---|---|
| CPU 312 | 6ES7312-1AE14-0AB0 | 0.2 µs | 32 KB | 25-40 ms |
| CPU 314 | 6ES7314-1AG14-0AB0 | 0.1 µs | 128 KB | 15-25 ms |
| CPU 315-2 DP | 6ES7315-2AH14-0AB0 | 0.1 µs | 256 KB | 10-20 ms |
| CPU 315-2 PN/DP | 6ES7315-2EH14-0AB0 | 0.05 µs | 384 KB | 8-15 ms |
| CPU 317-2 DP | 6ES7317-2AK14-0AB0 | 0.05 µs | 512 KB | 6-12 ms |
| CPU 319-3 PN/DP | 6ES7319-3CL00-0AB0 | 0.01 µs | 1400 KB | 4-8 ms |
If the installed CPU is not in this list, look up the specific order number on Siemens Industry Online Support. A 150 ms scan time on a CPU 315-2 DP with a moderate program is a 6x-10x anomaly. Documented 108-drive Profibus systems on S7-400 routinely run with 11 ms scan time; an S7-300 with 15 slaves has no justification for a 150 ms scan.
Root Causes of Excessive Scan Time
From field experience, the contributors to a 100+ ms S7-300 scan time fall into six categories, ranked by frequency:
- Error OB execution from Profibus slave flapping. OB 86 (rack/slave failure) fires on every slave drop or recovery. If the OB body is non-trivial, each event costs 5-50 ms.
- SFC 47 "WAIT" call in production code. A test artifact that was never removed. SFC 47 with WT = 100 blocks the cyclic OB for 100 ms per call.
- Single-OB architecture (everything in OB 1). Slow tasks such as HMI data preparation, log writing, and Profibus diagnostics run on every cycle and add fixed cost.
- Excessive communication load configured. A 50% communication share halves the time available for the user program, and frequent PUT/GET to peer PLCs adds per-cycle overhead.
- Work memory exhaustion. When the MC7 program is larger than the work memory, the CPU is forced to compress and decompress code, multiplying execution time.
- I/O access errors (OB 122) on missing modules. Each access to a non-existent or failed module triggers OB 122; mass-trigger from a stub program can stall the cyclic.
Prerequisites
Before running diagnostics, verify the following:
- STEP 7 V5.5+ or TIA Portal V16+ with the project matching the target CPU's firmware.
- Online Ethernet or MPI/Profibus connection to the S7-300 CPU.
- The S7-300 project's offline archive, including the hardware configuration (.hw or .hw_0) and the program source files.
- Read access to the CPU's diagnostic buffer and the online program blocks.
- List of all configured Profibus slaves with their expected Profibus addresses and physical locations.
- Optical-fiber link budget documentation if an OLM (Optical Link Module) is in the path between the S7-400 and S7-300.
Step-by-Step Diagnostic Procedure
Follow this sequence in order; do not skip ahead. Each step isolates one variable.
- Read the diagnostic buffer. In STEP 7, right-click the CPU in the project tree and select Online > Diagnostic Buffer. Filter for events in the last 24 hours. Look for entries of class OB 80 Time Error, OB 86 Rack Failure, OB 122 I/O Access Error, and Cycle Time Exceeded. Each is a direct pointer to the next step.
-
Read the online scan time. Open the online block view of OB 1 and observe the system clock values
OB1_PREV_CYCLEandOB1_MIN_CYCLE. The wall-clock scan isOB1_PREV_CYCLEin milliseconds. Confirm the 150 ms value is consistent over a 60-second sample window. - Audit Profibus slave health. In HW Config, right-click the Profibus subnet and select Profibus Diagnostics. Every slave that is configured but not reachable raises OB 86. The cycle-time cost per event is the body of OB 86.
-
Search for SFC 47 calls. In the offline program, use Find in the LAD/FBD/STL editor and search for
SFC 47or the string"WAIT". Any hit is suspicious. Comment out the call (do not delete during diagnostics) and recompile. Re-measure scan time online. -
Measure OB execution time individually. Add a start and end timestamp to each OB. The simplest method is to call SFC 64 "TIME_TCK" at OB start and OB end and store the difference in a marker word:
Note: SFC 64 returns a 1 ms (or 10 ms on older CPUs) tick. Subtract the two values to get the OB execution time. Use the diagnostic buffer to time-error timestamps as a cross-check.CALL SFC 64 // at OB start RET_VAL := MD 100 // ... OB body ... CALL SFC 64 // at OB end RET_VAL := MD 104 L MD 104 L MD 100 -D T MD 108 // delta in ticks - Check the configured scan monitoring time. In HW Config > CPU properties > Cycle/Clock Memory, the Scan Cycle Monitoring Time is the watchdog. The default depends on the CPU class; many S7-300 CPUs ship with 150 ms. If the configured value is 150 ms, the observed scan of 150 ms is at the trip point. Increase to 200 ms temporarily as a diagnostic, not a fix, to give room to instrument.
- Check work memory utilization. In Online > Module Information > Memory, read Work memory used vs Work memory total. If used > 80%, the CPU is memory-pressured and MC7 paging is inflating the cycle.
- Check program size vs CPU class. The MC7 code size is reported in the module info Performance tab. A 250 KB MC7 program on a CPU 312 (32 KB work memory) is physically impossible; the CPU is paging. Match the CPU class to the program size or split the program.
OB Priority Class Architecture
The S7-300 executes organization blocks by fixed priority. Understanding the priority classes is the key to separating fast processes from slow ones; a single OB 1 containing all logic serializes everything.
| OB | Type | Default priority (S7-300) | Trigger |
|---|---|---|---|
| OB 1 | Main cyclic | 1 | End of last cycle (continuous) |
| OB 10-17 | Time-of-day interrupt | 2 | Configured date/time |
| OB 20 | Delay interrupt | 3 | SFC 32 (SRT_DINT) |
| OB 30 | Cyclic interrupt | 9 | Every 5000 ms |
| OB 31 | Cyclic interrupt | 9 | Every 2000 ms |
| OB 32 | Cyclic interrupt | 9 | Every 1000 ms |
| OB 33 | Cyclic interrupt | 10 | Every 500 ms |
| OB 34 | Cyclic interrupt | 11 | Every 200 ms |
| OB 35 | Cyclic interrupt | 12 | Every 100 ms |
| OB 36 | Cyclic interrupt | 13 | Every 50 ms |
| OB 37 | Cyclic interrupt | 14 | Every 20 ms |
| OB 38 | Cyclic interrupt | 15 | Every 10 ms |
| OB 40-47 | Hardware interrupt | 16-23 | Configured I/O event |
| OB 55-57 | DP interrupt | 15 | DP diagnostics / status / vendor |
| OB 80 | Time error | Same as calling OB | Cycle time exceeded |
| OB 82 | Diagnostic interrupt | Same as calling OB | Module diagnostic |
| OB 83 | Insert/remove | Same as calling OB | Module hot-swap |
| OB 85 | Program execution error | Same as calling OB | OB not loaded / I/O update error |
| OB 86 | Rack failure | Same as calling OB | Profibus slave DP failure |
| OB 100 | Warm restart | 27 | Power up / restart |
| OB 121 | Programming error | Priority of calling OB | MC7 error |
| OB 122 | I/O access error | Priority of calling OB | Access to failed I/O |
Error OBs (80, 82, 83, 85, 86, 121, 122) all run at the same priority as the OB that was active when the error fired. If the active OB is OB 1 (priority 1), the error OBs run at priority 1, further extending the cycle. Splitting critical logic into a higher-priority OB 35 (priority 12) keeps the fast path from being delayed by error OB execution.
Watchdog and Communication Load Configuration
Two CPU-level parameters control the headroom available for the user program: the scan cycle monitoring time and the maximum communication load share.
Open HW Config > CPU properties > Cycle/Clock Memory and set:
- Scan cycle monitoring time: 200 ms (diagnostic value; restore to 100-150 ms once scan time is reliably below 50 ms).
- Communication load > Maximum load by communication: 20% (the default is 50%; reducing it increases OB 1 priority share).
- Clock memory: enable and select an unused byte (commonly MB 0) if the program uses clock flags for scheduled logic.
The communication load parameter is the most commonly missed. When set to 50%, the S7-300 splits its time 50/50 between the user program and PG/OP/S7 communication. Heavy HMI polling, partner PLC PUT/GET, and Profibus DP-V1 acyclic services all consume from that 50% pool. If the HMI is polling 50 tags every 100 ms, the cyclic OB never gets a fair share. Set the share to 20% to starve the communication and force batch behavior, then optimize the HMI poll rate as a follow-on.
Program-Level Optimizations
After eliminating the system-level causes, the remaining scan-time load is in the user program. Apply these in order of ROI.
Optimization 1 - Remove SFC 47 "WAIT" Calls
SFC 47 with the parameter WT (wait time in milliseconds, range 1-32767) is a hard delay inserted by the programmer. It is a legacy debugging tool. In production code it is always wrong.
CALL SFC 47
WT := 100 // WAIT 100 ms - REMOVE THIS
BE
Search every FB, FC, and OB for SFC 47. Replace with no operation or a conditional flag if a deliberate stall is required. One WT=100 call in OB 1 alone adds 100 ms to every cycle.
Optimization 2 - Convert SCL and Graph Hot Paths to STL or LAD
SCL (Structured Control Language) and Graph-compiled FBs run 30-100% slower than equivalent LAD or STL in MC7. The STEP 7 compiler for SCL generates a more verbose MC7 sequence with additional stack operations. Where scan time is critical, rewrite hot-path SCL blocks in LAD or STL. S7-Graph state machines add similar overhead; if a state machine runs every 10 ms, it can dominate the cycle.
Optimization 3 - Segregate by OB Priority
Move slow tasks (HMI data preparation, log file writes, batch reports) out of OB 1 and into OB 35 (100 ms) or OB 32 (1 s). Keep OB 1 to the critical-path control logic only. The result is a sharp drop in OB 1 execution time and a stable, predictable response on the fast control loops.
Reference architecture for a 15-slave Profibus plant:
| OB | Period | Contents | Target execution |
|---|---|---|---|
| OB 1 | Continuous | Safety logic, drive enables, fast interlocks, time-critical Profibus DP read/write | < 20 ms |
| OB 35 | 100 ms | Process control loops, regulator setpoints, valve sequencing | < 30 ms |
| OB 32 | 1 s | HMI data block preparation, non-critical I/O, status aggregation | < 50 ms |
| OB 33 | 500 ms | Communication: PUT/GET to peer PLC, partner S7 connections | < 100 ms |
| OB 34 | 200 ms | Diagnostic aggregation, history buffer maintenance | < 20 ms |
| OB 86 | On event | Profibus slave health; set a flag, do not run logic | < 1 ms |
| OB 80 | On event | Set a flag, increment counter, return | < 1 ms |
| OB 122 | On event | Set a flag for the failed I/O address, return | < 1 ms |
Optimization 4 - Audit OB 85 and OB 122 Bodies
OB 85 fires for "OB not loaded" and for I/O update errors. OB 122 fires on every access to a failed I/O point. A common anti-pattern is to put logic inside OB 122 that reads the failed I/O again, causing an infinite loop. Keep OB 85 and OB 122 to three operations: read the start info, set a diagnostic flag, return. Do not perform I/O inside them.
Optimization 5 - Program Size and Work Memory
If work memory used is above 80%, the CPU compresses MC7 segments to fit. Decompression on each cycle is expensive. The fix is either to split the program into modular FBs and remove unused code, or to upgrade the CPU. For an S7-300 with a 32 KB CPU 312, anything over 24 KB user program is risky; target 16 KB or less for stable 10-20 ms scans.
Profibus Network Health and OB 86 Behavior
For a system with 15 configured Profibus slaves, OB 86 is the most likely contributor to a 150 ms scan. Every time a slave drops off the bus, OB 86 fires; if the bus is flapping (connector issue, EMI, terminator, or failing slave), the OB 86 rate can dominate.
| Symptom | Likely cause | Action |
|---|---|---|
| OB 86 fires 1-2 per hour | Normal electrical noise | Keep OB 86 minimal; do nothing |
| OB 86 fires > 1 per minute | Single slave or connector problem | Inspect Profibus diagnostics; check slave address, connector, terminator |
| OB 86 fires > 10 per minute | Cable damage, EMI, terminator missing | Replace cable segment, verify both ends terminated, check shield grounding |
| OB 86 fires constantly on specific slave | Slave power supply or Profibus interface failure | Replace slave; check 24 V supply under load |
| OB 86 fires after every scan | Profibus address conflict | Reassign addresses; check no two slaves share an address |
The Profibus optical-fiber link between the S7-400 and S7-300 is another candidate. An OLM (Optical Link Module) with a weak receiver or dirty connector regenerates the bus but adds latency. A failing OLM can cause retries that show up as OB 86 on the S7-300 side. Measure the optical-fiber power budget with an OLM-specific tool or substitute a known-good fiber pair to isolate.
Troubleshooting Matrix
Use this matrix as a quick triage once the diagnostic buffer is read.
| Diagnostic buffer event | First action | Secondary action | Expected scan-time improvement |
|---|---|---|---|
| OB 80 Time Error | Check watchdog setting vs actual scan | Identify which OB is overrunning | 5-30 ms |
| OB 86 Rack Failure (DP) | Check Profibus diagnostics for affected slave | Repair or replace slave/cable | 10-50 ms |
| OB 122 I/O Access Error | Find the failing I/O address in the OB 122 start info | Remove the access or fix the module | 5-20 ms |
| OB 85 Program Execution Error | Check for OB not loaded; load missing OB | Audit I/O update consistency | 5-15 ms |
| No error events, but scan high | Audit OB 1 body length; check for SFC 47 | Split by priority into OB 35 / OB 32 | 30-80 ms |
| Communication load 50% | Reduce to 20% in CPU properties | Reduce HMI poll rate; batch data | 20-50 ms |
| Work memory > 80% used | Reduce program size; modular FBs | Upgrade CPU | 10-40 ms |
| Heavy SCL / Graph use | Rewrite hot-path in STL or LAD | Move SCL to OB 32 / OB 33 | 15-40 ms |
Verification Procedure
After applying changes, verify the fix in this order:
-
Confirm scan time online. In STEP 7, open the online Monitor/Modify view of OB 1. Watch
OB1_PREV_CYCLEover 5 minutes of normal operation (no faults). The expected value is 10-30 ms for a 15-slave Profibus plant. The maximum should be below 50 ms under peak load. - Confirm diagnostic buffer is clean. After 1 hour of operation, no OB 80, OB 86, OB 85, or OB 122 events should be present in normal steady state. Transient events during startup or slave replacement are expected.
- Confirm watchdog headroom. The actual scan time should be at most 70% of the configured scan monitoring time. For a 100 ms watchdog, target a maximum scan of 70 ms. For a 150 ms watchdog, target a maximum of 100 ms. The buffer absorbs the rare error OB execution.
- Confirm process stability. From the S7-400 operator HMI, monitor the optical-fiber link quality and the Profibus slave diagnostic counters. Slaves that were flapping should show zero retries in the diagnostic buffer.
- Confirm communication load. In Online > Module Information > Performance, observe the communication load percentage. If the HMI is configured for 50% and the actual is below 30%, you can keep the setting; if it is consistently above 30%, the application is over-polling and the HMI should be retuned.
FAQ
What is a normal S7-300 scan cycle time?
A correctly loaded S7-300 with a typical automation program and 8-16 Profibus slaves runs at 10-30 ms. 50 ms is the upper limit of normal. 100+ ms is a clear anomaly and 150 ms places the CPU at the watchdog trip point for many default configurations.
What is SFC 47 "WAIT" and why does it slow down the scan?
SFC 47 with parameter WT inserts a hard delay in milliseconds (range 1-32767). It is a legacy debugging tool that blocks the calling OB for the requested time. A 100 ms WT call adds 100 ms to every cycle. Production code should never contain SFC 47; search the program and remove every call.
How does OB 86 affect scan time on a Profibus network?
OB 86 fires every time a Profibus slave becomes unreachable or recovers. The execution time of the OB body is added to the current scan. If the bus is flapping, OB 86 can fire many times per minute, inflating the scan by 10-50 ms per event. Keep OB 86 to flag-setting and return; fix the underlying slave or cable problem to remove the trigger.
What is the default scan monitoring time on an S7-300?
The default scan cycle monitoring time depends on the CPU. CPU 312 and CPU 314 often default to 150 ms. CPU 315-2 and higher typically default to 100 ms. The value is configured in HW Config > CPU properties > Cycle/Clock Memory. Increase to 200 ms during diagnostics, but restore to 100-150 ms once the scan time is reliably below 50 ms.
Should I program OB 80 to prevent the CPU going to STOP?
Yes, as a safety net. OB 80 is called when the cycle time exceeds the configured monitoring time; if the OB is not present, the CPU goes to STOP. However, OB 80 is a recovery mechanism, not a fix. The root cause (Profibus faults, SFC 47, oversized program) must still be resolved so OB 80 is never called under normal operation. See the Siemens TIA Portal documentation: Settings for the cycle behavior.
Can a high communication load setting cause a 150 ms scan?
Yes. The "Maximum load by communication" parameter in CPU properties is set to 50% by default, which means the CPU splits time evenly between the user program and PG/OP/S7 communication. Heavy HMI polling or partner PUT/GET traffic consumes the communication share and forces the user program to wait. Reducing the load to 20% gives the user program more time, often dropping the scan by 20-50 ms.