Simulate S7-1200 HMI in TIA Portal: PLCSIM and WinCC Runtime

David Krause15 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Overview

Commissioning an S7-1200 CPU 1214 DC/DC/DC without a physical HMI panel (such as a KTP1000 Basic) is a common requirement during project development, factory acceptance tests (FAT), and engineer training. The legacy environment of WinCC Flexible 2008 and the modern TIA Portal (WinCC engineering in the TIA Portal, starting with V11) treat "simulation" differently, which has historically confused engineers migrating from one toolchain to the other. This guide clarifies the architectural difference, shows how to operate an S7-1200 panel project in PC-based Runtime, and walks through PLCSIM integration and the integrated Tag Simulator.

The end state described in this document is a configuration PC running WinCC Runtime that communicates to either a real S7-1200 CPU or to S7-PLCSIM, with a Tag Simulator available to force I/O without manual wiring. The same workflow applies to the KTP1000 Basic, KTP400 Basic, TP1500 Basic, and the Comfort Panel families supported by WinCC in the TIA Portal.

Architectural key point: In WinCC Flexible 2008, the Simulation mode historically runs the panel project offline against a built-in tag engine and does not connect to a real PLC or to PLCSIM. In TIA Portal, Start Runtime is the equivalent of WinCC Flexible's Runtime mode, and it expects a real (or simulated) PLC connection. TIA Portal also offers a separate Simulation with tag simulator path that behaves closer to the legacy "Simulate" button.

2. Prerequisites

Item Specification / Version Purpose
Programming PC Windows 10/11 (64-bit), 8 GB RAM minimum, 16 GB recommended Hosts TIA Portal, PLCSIM, WinCC Runtime
TIA Portal V11, V13 SP1, V15, V15.1, V16, V17, or V18 (matches CPU firmware) Engineering, project build, HMI configuration
STEP 7 Basic / Professional Bundled with TIA Portal S7-1200 program development
WinCC Basic / Comfort / Advanced Bundled with TIA Portal; license required for Runtime on PC HMI configuration and RT (RT128 / RT256 / RT1024 / RT2048)
S7-PLCSIM V11 to V18, included with STEP 7 Simulates the S7-1200 CPU; supported from S7-PLCSIM V13 SP1 for S7-1200
S7-1200 CPU 1214 DC/DC/DC 6ES7214-1AG40-0XB0 (Firmware V4.x) or 6ES7214-1AE30-0XB0 (V1.x/V2.x) Real PLC target (optional in simulation)
Ethernet / PROFINET interface 100 Mbit/s, TCP/IP Communication between TIA Portal / Runtime and CPU or PLCSIM
PC/PPI or PC Ethernet adapter Siemens 6GK1571-1AA00 (PPI/MPI/TCP) or standard Ethernet NIC Online link to physical CPU

The S7-PLCSIM version must match the TIA Portal version. PLCSIM V13 SP1 and later expose S7-1200 CPUs; earlier PLCSIM versions (V11, V12) only support S7-300/S7-400. Confirm your license covers S7-PLCSIM for the S7-1200 if you intend to use the S7-1200/1500 target. Detailed version compatibility is documented in the Siemens Online Support article S7-PLCSIM V18 - Function Overview.

3. S7-1200 CPU 1214 DC/DC/DC: Hardware Reference

The CPU 1214 DC/DC/DC ships in two main variants relevant for simulation work:

  • 6ES7214-1AG40-0XB0 – DC/DC/DC, 14 digital inputs (24 V DC), 10 digital outputs (24 V DC, 0.5 A transistor), 2 analog inputs (0–10 V), work memory 100 KB code / 4 MB data, firmware V4.x. The most common variant in service today.
  • 6ES7214-1AE30-0XB0 – DC/DC/DC, firmware V1.x/V2.x, 75 KB work memory, legacy variant with limited PLCSIM and TIA Portal coverage beyond V13.

Both units expose a single PROFINET interface (X1) with one port. The IP default is 192.168.0.1, subnet mask 255.255.255.0, no router. CPU-to-CPU or PC-to-CPU communication is pure TCP/IP on port 102 (ISO-on-TCP / RFC1006). For the S7-1200, the integrated Ethernet port is the only programming and HMI interface; there is no MPI/DP on the 1214 DC/DC/DC. The full pinout and terminal diagram is in the S7-1200 Programmable Controller System Manual.

For simulation work, you do not need to wire any field I/O. The digital and analog I/O is exercised through the Tag Simulator or through the S7-PLCSIM I/O forcing interface.

4. WinCC Flexible 2008 vs TIA Portal: Simulation Semantics

Engineers familiar with WinCC Flexible 2008 expect a single "Simulate" button (the eyeglass icon in the toolbar) to launch a Runtime that is decoupled from the real PLC and uses a built-in tag engine. In TIA Portal the semantic is split:

Feature WinCC Flexible 2008 TIA Portal (WinCC V11+)
Offline simulation (no PLC connection) Yes – the "Simulate" icon opens RT with a built-in tag engine No direct equivalent. Use Start Runtime after selecting an offline HMI target, or use the simulation launcher with a stand-alone tag table
Runtime on PC against a real PLC Yes – "Start Runtime" option, communicates to live PLC Yes – Online > Simulation > Start opens PC Runtime that talks to the configured PLC
Runtime on PC against PLCSIM Not directly; requires manual IP routing or HMI-as-PLC tag workaround Yes – PLCSIM appears as a S7-1200 instance on the same network and is auto-discovered by the HMI
Tag simulator (force values) Built into the Simulation launcher Accessed via Online > Simulation > Start with tag simulator in the HMI project tree
Toolbar icon Dedicated "Simulate" eyeglass icon No single icon – modes are menu commands under Online

Operationally the workflow is: select the HMI in the project tree, then choose Online > Simulation > Start for connected simulation, or Online > Simulation > Start with tag simulator for the offline-with-forcing mode. The TIA Portal equivalents are documented in the WinCC Engineering in TIA Portal - Simulation Manual.

5. S7-PLCSIM Configuration for S7-1200

S7-PLCSIM (V13 SP1 onward) emulates an S7-1200 CPU as a SoftPLC on the engineering PC. It listens on TCP port 102 like a real CPU and accepts the S7 communication used by WinCC Runtime and STEP 7.

  1. Open the S7-1200 project in TIA Portal.
  2. From the project tree, right-click the S7-1200 device and choose Start simulation. TIA Portal launches S7-PLCSIM (the "SIMATIC S7-PLCSIM" window opens with a soft front panel).
  3. PLCSIM picks the next free IP in the 192.168.0.x range by default. To fix the address, open the PLCSIM soft front panel, click the Ethernet slot, and set IP = 192.168.0.1, mask = 255.255.255.0, gateway = 192.168.0.10. Match the project device configuration.
  4. Download the STEP 7 program to PLCSIM. The S7-1200 program is loaded into the simulated work memory; the LED indicators on the soft front panel turn green when RUN is active.
  5. Confirm the program is executing: open the soft front panel, switch to RUN/RUN-P, and verify the RUN LED is steady green. The MAINT/ERROR LED should be off.

If the download fails with error ERROR: Online: The connection to the target system could not be established, check that no other S7-PLCSIM instance is running, that the Windows firewall allows TCP/102 inbound, and that no real S7-1200 is bound to the same IP on the engineering NIC. The Siemens Knowledge Base PLCSIM S7-1200 connection troubleshooting collects the most common remedies.

6. Configuring the HMI Connection in the TIA Project

The HMI must reference the S7-1200 (or PLCSIM instance) through an HMI connection. The default HMI connection type for a SIMATIC S7-1200 panel is S7ONLINE (ISO-on-TCP) on port 102.

Parameter Value for real CPU Value for PLCSIM
Station S7-1200 station PLCSIM soft station (auto created by TIA when "Start simulation" is invoked)
Interface PROFINET (X1) PLCSIM virtual Ethernet
IP address (PLC) 192.168.0.1 (default) 192.168.0.1 (set in soft front panel)
Rack / Slot 0 / 1 0 / 1 (S7-1200 mapping is fixed)
Connection mechanism Active partner (HMI is active, PLC passive) Active partner
Port 102 102

For the KTP1000 Basic, the connection is configured in the device configuration: Devices & Networks > HMI_1 [KTP1000 Basic] > Connections > S7ONLINE_1. Double-click the connection row, set the partner (PLC) IP, and verify the rack/slot pair is 0/1. If the KTP1000 is replaced by a PC-based Runtime target, the connection remains identical – the Runtime simulator on the PC uses the same HMI connection block.

7. PC-Based Runtime Targets (Replacing the KTP1000)

When no physical KTP1000 is available, you run the HMI image on the PC. TIA Portal exposes the following PC-based Runtime targets:

Runtime target Article number Maximum tags / power tags Typical use
WinCC Runtime Advanced – RT128 6AV2104-0AA00-0AA0 128 power tags Small machines, basic panels
WinCC Runtime Advanced – RT256 6AV2104-0AA10-0AA0 256 power tags Mid-size machines
WinCC Runtime Advanced – RT1024 6AV2104-0AA20-0AA0 1024 power tags Plant-section visualization
WinCC Runtime Advanced – RT2048 6AV2104-0AA30-0AA0 2048 power tags Full plant HMI

Add a new HMI device in the project, choose PC systems > WinCC Runtime Advanced > RT 1024 (example), copy the screens from the KTP1000 project, recompile, and load the compiled HMI image to the PC Runtime directory. The HMI connection remains pointed at the S7-1200 (or PLCSIM) on 192.168.0.1.

Performance note: PC-based Runtime is generally faster than a basic panel, but engineers commonly report that the TIA Portal IDE itself responds more slowly than the legacy STEP 7 + WinCC Flexible 2008 stack. Compilation and download times for large projects can exceed 5 minutes on first build. Plan for this when scheduling FAT windows.

8. Tag Simulator Usage

The Tag Simulator is a forcing tool that lets you drive tags without a live PLC, without wiring, and without PLCSIM. It is the closest TIA Portal equivalent to WinCC Flexible 2008's offline simulation engine.

  1. Open the HMI project in TIA Portal.
  2. Select the HMI device in the project tree.
  3. Choose Online > Simulation > Start with tag simulator.
  4. The HMI Runtime launches in a window. The Tag Simulator pane appears next to it, listing every tag, its current value, quality code, and last update timestamp.
  5. To force a Boolean: double-click the value cell, type 1 or 0, press Enter. The HMI screen responds within one polling cycle (default 1 s).
  6. To force an integer with a sine function: right-click the tag, choose Generate function, and select sine, ramp, random, or step. Set amplitude and period.
  7. To record: right-click the tag, choose Record. The Tag Simulator writes a CSV log to %USERPROFILE%\AppData\Local\Siemens\Automation\WinCCRT\TagSimulator\log.

The Tag Simulator writes directly to the HMI's internal tag image. It does not require the PLC to be online. However, if the HMI connection to a real PLC is active and the PLC is also writing the same tag, the PLC value overrides the simulator value at the next acquisition cycle. Disable the connection (right-click the connection row, set Active = no) for pure offline forcing.

9. Step-by-Step: End-to-End Simulation with PLCSIM and WinCC Runtime

  1. Build the project. Configure the S7-1200 program (ladder, FBD, or SCL), the HMI screens, and the HMI connection. Save and compile both devices (Project tree > right-click device > Compile > Hardware and software (rebuild all)).
  2. Start PLCSIM. Right-click the S7-1200 in the project tree and choose Start simulation. Wait for the PLCSIM soft front panel to open.
  3. Download the S7 program to PLCSIM. Click Download to device in the toolbar. Select the PLCSIM interface, confirm target = PLCSIM, and click Load. Finish by clicking Start module in the next dialog. The PLCSIM soft front panel shows RUN.
  4. Add a PC Runtime target. In the project tree, double-click Add new device > PC systems > WinCC Runtime Advanced > RT 1024. Copy the screens from the KTP1000 device into the PC Runtime device by drag-and-drop. Re-bind the HMI connection to point at the S7-1200 PLCSIM instance (rack 0, slot 1, IP 192.168.0.1).
  5. Compile the PC Runtime project. Right-click the PC Runtime device, choose Compile > Software (rebuild all). TIA Portal emits a *.fwx runtime file.
  6. Start PC Runtime with tag simulator. Right-click the PC Runtime device, choose Online > Simulation > Start with tag simulator. The Runtime window opens, the Tag Simulator pane opens, and the HMI connects to PLCSIM over Ethernet loopback.
  7. Verify the connection. On the HMI, navigate to a screen that displays a tag from the PLC. The tag should show a current value. Open the connection diagnostics (touch the status indicator on the HMI status bar) – the connection state should be Connected, quality code Good.
  8. Force a tag from the Tag Simulator. Locate a Boolean output tag (e.g., "Motor_Start"). Set it to 1. The HMI screen should update within 1 s, and the corresponding input in PLCSIM's I/O view should change to 1.
  9. Run for 10 minutes under load. Cycle through all screens, force every tag at least once, confirm no Runtime exception dialog appears, and confirm no memory leak in Task Manager (Runtime process should stay under 250 MB working set for a small project).
  10. Save the project archive. Project > Archive > Save as. TIA Portal writes a *.zap archive. Store this alongside the FAT report.

10. Verification Checklist

Check Expected result Pass criterion
PLCSIM RUN LED Steady green Yes
PLCSIM ERROR / MAINT LED Off Yes
PC Runtime connection state Connected Yes
HMI tag quality code Good (C0) Yes for at least 95% of tags
Forced Boolean echo to PLCSIM PLCSIM input pin toggles within 1 s Yes
Tag Simulator response time < 1 s for Boolean, < 2 s for analog Yes
PC Runtime memory working set < 250 MB for 1k tag project Yes
Compilation warnings None in HMI tag consistency check Yes

11. Troubleshooting Matrix

Symptom Likely cause Resolution
Runtime opens, all tags show quality "Bad" (00) HMI connection not bound to PLCSIM or wrong rack/slot Open Connections > S7ONLINE_1 and verify partner IP = 192.168.0.1, rack 0, slot 1
"Start with tag simulator" menu item is greyed out Project not compiled, or HMI is a Comfort Panel not a PC Runtime target Compile the HMI first; ensure the target is a PC system
PLCSIM download fails with WSAEADDRINUSE Another PLCSIM instance is bound to the IP Close all PLCSIM windows, restart the TIA Portal instance
Tag Simulator forces a value, HMI does not respond PLC is online and writing the same tag, overriding the simulator Disable the HMI connection, or set the tag to "Read only" in the HMI tag properties
Runtime crashes on screen switch Corrupted screen object or unsupported graphic Recompile the HMI with the "Extended check" option enabled
Connection drops after 30 s of inactivity TCP keepalive not negotiated by PLCSIM Increase the HMI polling cycle from 1 s to 500 ms
CPU 1214 (V1.x) cannot be simulated in PLCSIM V15+ PLCSIM dropped legacy CPU support Use PLCSIM V13 SP1, or upgrade the CPU firmware to V4.x and use PLCSIM V15+

12. Field-Engineer Cautions

  • License sizing. PC Runtime licenses are sized in power tags. The KTP1000 Basic panel itself does not require a Runtime license – it is a hardware device. If you replicate the KTP1000 image on a PC, you must license the PC Runtime with at least RT128 even if the project only uses 16 tags.
  • Time synchronization. PLCSIM and the HMI Runtime share the PC system clock. The S7-1200 in PLCSIM is also synchronized. If you simulate a midnight rollover (e.g., shift counter reset at 00:00), confirm that all three clocks agree, or use a single Time-of-Day tag from the CPU to drive the HMI clock.
  • Retentive behavior. PLCSIM persists retentive tags across simulation restarts. To force a clean state, close PLCSIM, delete the *.s7p working file from %USERPROFILE%\AppData\Roaming\Siemens\Automation\PLCSIM, and restart.
  • Firewall on Windows 10/11. The first PLCSIM start may require explicit firewall approval for S7-PLCSIM.exe on port 102. Click Allow access on the prompt, or pre-create an inbound rule for TCP/102 restricted to the engineering subnet.
  • Real CPU coexistence. If a physical CPU 1214 is connected to the same PC and shares the 192.168.0.1 IP, PLCSIM and the real CPU will collide. Either disconnect the CPU from the network, change the real CPU's IP to 192.168.0.2, or set PLCSIM to a different subnet (e.g., 192.168.1.1) and update the HMI connection.
  • KTP1000 specific. The KTP1000 Basic supports 800 x 480 px and a 10.1 in display. If the PC Runtime screen resolution differs, scale the screen size in the HMI device properties to 800 x 480 before compiling to avoid touch-target misalignment when you later deploy back to the physical panel.

13. FAQ

Can I simulate a KTP1000 Basic panel in TIA Portal without the physical hardware?

Yes. Add a PC system with WinCC Runtime Advanced (RT128 minimum) to the TIA project, copy the KTP1000 screens into the PC Runtime device, recompile, and launch via Online > Simulation > Start (with PLC connection) or Start with tag simulator (offline forcing). The PC Runtime replaces the panel hardware for the duration of the simulation.

What is the difference between WinCC Flexible 2008 Simulation and TIA Portal Simulation?

WinCC Flexible 2008's "Simulate" icon runs the panel offline against a built-in tag engine, with no connection to the real PLC or PLCSIM. TIA Portal's Start with tag simulator command is the closest equivalent, but most TIA Portal engineers use Start Runtime, which connects to a real CPU or to S7-PLCSIM. The legacy "no-PLC simulation" workflow requires an explicit menu choice in TIA Portal, while in WinCC Flexible it was a single toolbar icon.

Does S7-PLCSIM support the S7-1200 CPU 1214 DC/DC/DC?

From S7-PLCSIM V13 SP1 onward. PLCSIM V11 and V12 only emulate S7-300 and S7-400. For the CPU 1214 DC/DC/DC with firmware V4.x (6ES7214-1AG40-0XB0), use PLCSIM V15, V16, V17, or V18 to match your TIA Portal version. Legacy V1.x firmware (6ES7214-1AE30-0XB0) is supported through PLCSIM V13 SP1 only.

How do I force a Boolean output tag in the Tag Simulator?

Open Online > Simulation > Start with tag simulator, locate the tag in the Tag Simulator pane, double-click its value cell, type 1 or 0, and press Enter. The HMI updates within one polling cycle (default 1 s). For cyclic forcing, right-click the tag and assign a sine, ramp, random, or step generator with a configurable period.

What PC Runtime license do I need to run a KTP1000 project on my laptop?

WinCC Runtime Advanced for PC, sold as a power-tag-bounded license: RT128 (6AV2104-0AA00-0AA0) for up to 128 power tags, RT256 (6AV2104-0AA10-0AA0) for 256, RT1024 (6AV2104-0AA20-0AA0) for 1024, or RT2048 (6AV2104-0AA30-0AA0) for 2048. A typical KTP1000 migration with 60 tags is covered by RT128.

Why does the HMI show "Bad" quality for all tags even though PLCSIM is in RUN?

The HMI connection is not bound to the PLCSIM instance. Open Devices & Networks > HMI_1 > Connections > S7ONLINE_1 and verify the partner IP matches PLCSIM (default 192.168.0.1), rack = 0, slot = 1, and that the connection is set to Active. Recompile and restart Runtime.

Back to blog