SINAMICS DCM Field Contactor Control: Parameter Reference and Fault Behavior
The SINAMICS DC Master (DCM) converter controls the armature and field circuits of a DC motor through two independent power sections. The field section requires its own contactor for safe disconnection during commissioning, emergency stop, and certain fault conditions. Selecting the wrong control signal for this contactor — or misconfiguring the field pulse enable during faults — results in unexpected armature or field collapse, failed dynamic braking, and motor coast-down. This reference documents the correct BICO source signal (r53195.0, r53210.2, r53081.0, or r53010.04) for the field contactor, the behavior of the relevant parameters (p50082, p50097, p50071, p50094) under fault conditions, and the recommended parameterization for 2-quadrant (2Q) and 4-quadrant (4Q) drive topologies.
1. Field Supply Architecture in SINAMICS DCM
The SINAMICS DCM (6RA80 series and 6RA70 legacy) consists of a fully-controlled thyristor bridge for the armature circuit and a separate, single-phase half-controlled or fully-controlled bridge for the field circuit. The field bridge draws its supply from the same three-phase AC line feeding the armature bridge, but operates at a lower current rating (typically 5 % to 10 % of the armature rated current). For details on the field supply unit ratings, refer to the SINAMICS DCM as Field Supply Unit application document.
Key ratings of the field section:
| Symbol | Quantity | Typical Range |
|---|---|---|
| UFN | Rated field voltage | 80 V to 420 V (model dependent) |
| IFN | Rated field current | 3 A to 30 A (B6 bridge); up to 60 A on parallel configurations |
| PV | Power loss of the field rectifier | Function of IFN² × RS |
| UV | Line-to-line voltage at the field input | Must match armature input ±10 % |
The field section includes an integrated field contactor (or external contactor commanded by a drive output). The contactor's coil is driven through terminal X177 (or a digital output on a Terminal Module TM15/TM31) and the source of the command signal is selected via BICO interconnection. The contactor must close before the field thyristors are fired and must not open while current is circulating in the field winding to avoid contact welding.
2. Why a Field Contactor Is Required
The field contactor performs three functions:
- Isolation during maintenance: Provides a visible break in the field circuit, satisfying EN 60204-1 §5.5 for safe isolation.
- Field reversal in 2Q drives: In a 2-quadrant (single converter bridge) topology, reverse rotation is achieved by reversing field polarity with a reversing contactor. The field contactor in this case is actually a field-reversing contactor pair.
- Pre-charge and demagnetization: Closes only after the field capacitors have charged and the firing pulses are inhibited; opens only after the firing pulses are inhibited and the field current has decayed below 5 % of IFN.
3. Candidate BICO Source Signals
Four signals are commonly considered as the source for the field contactor command. Each has a distinct semantic meaning in the DCM state machine:
| Signal | Name | True When… | Suitable for Field Contactor? |
|---|---|---|---|
| r53010.04 | Drive running / no fault active | Operating state ON (no OFF1/OFF2/OFF3, no fault) | Yes — preferred for "field follows enable" |
| r53195.0 | Field sequence control: contactor close command | Field current > setpoint threshold, no fault, line contactor closed | Yes — preferred for "field follows current" |
| r53210.2 | Field reversal: forward direction | Field direction = forward (only meaningful in 2Q field-reversal) | Conditional — only in 2Q reversal |
| r53081.0 | Field on (independent of armature state) | Field firing pulses enabled and not blocked by n < nmin | Yes — used when field must persist at standstill |
3.1 r53010.04 — Drive Ready / Running
Bit 04 of status word r53010 indicates the drive is in operating state "ON" and no shutdown command is active. This signal is the cleanest choice when the field contactor should be released in lockstep with the enable command. During a fault (F30001, F30002, F06100, etc.) the bit resets and the field contactor opens. The field pulses are also blocked at this moment, so the contactor opens under no current — a safe condition.
3.2 r53195.0 — Field Sequence Output
This signal is the explicit "close field contactor" command from the field sequence control state machine. It remains true while field current is established, even if the armature is stopped. It releases on: line contactor open, OFF1/OFF2 with extended delay, or after the field current has decayed below threshold p50395.
3.3 r53210.2 — Field Direction Forward
Bit 2 of r53210 indicates the commanded field direction. It is not a contactor close command; it is a polarity selector used in 2Q drives with reversing contactors. Using it as a sole source for the field contactor is incorrect because the signal does not account for enable, fault, or current state.
3.4 r53081.0 — Field Active
This is the "field on" status bit used in older 6RA70 firmware. It indicates that the field firing pulses are enabled. It is independent of n < nmin when p50082 = [4] (field continuously on) is set. This makes r53081.0 a useful source when the field must be maintained during a no-speed condition, but it requires careful parameterization to avoid dropouts at low speed.
4. Configuration Parameters
The behavior of the field contactor and the field firing pulses is controlled by four primary parameters in the DCM expert list:
| Parameter | Description | Values | Effect |
|---|---|---|---|
| p50082 | Field operating mode | [1] Field on during run [3] Field continuously on [4] Field on with delay-off |
Selects when field is energized relative to drive run state |
| p50097 | Field pulses in case of fault | [0] Block pulses on fault [1] Enable pulses during fault |
Determines if firing pulses survive a fault trip |
| p50071 | Source for field contactor command (BO 50771) | BICO source: r53010.04, r53195.0, r53081.0, etc. | Selects the logical signal that closes the field contactor |
| p50094 | Delay time for auxiliary systems | 0 to 600 s (default 60 s) | Run-on time when p50082 = [4] before field contactor opens |
4.1 p50082 — Field Operating Mode
Setting p50082 = [1] energizes the field only while the drive is in operating state ON. The field de-energizes on OFF1, OFF2, OFF3, or fault. Setting p50082 = [3] keeps the field energized as long as the line contactor is closed and the electronics power supply is present, regardless of the operating state — this is the configuration used when the motor is heated by field current in standby. Setting p50082 = [4] adds a configurable run-on (p50094) after the drive goes to OFF, used for cooling fans and field-heated holding.
4.2 p50097 — Field Pulses in Case of Fault
By default, a fault trip blocks both armature and field firing pulses. When p50097 = [1] is set, the field pulses remain enabled during a fault, but the armature pulses are still blocked. This configuration is used when dynamic braking is required: the motor acts as a generator, the armature current decays through the field, and the kinetic energy is dissipated as heat in the armature resistance. Field pulses surviving a fault do not imply the field contactor remains closed — the contactor command is independent and is driven by p50071.
4.3 p50071 — BO 50771 Source
The parameter p50071 is the BICO source for Binector Output BO 50771, which in turn is wired to the digital output driving the field contactor coil (typically DO 0 on the Control Unit, or DO on a TM15). The default source in most DCM firmware revisions is r53010.04, which is the conservative choice: contactor follows the enable state.
4.4 p50094 — Auxiliary Systems Delay
Used only when p50082 = [4]. Specifies the run-on time (in seconds) the field remains on after the drive goes to OFF1. Default is 60 s. After this delay, the field contactor opens and (if p50097 = [0]) the field pulses are blocked.
5. Decision Matrix: Selecting the Correct Source
Use the following matrix to select the BICO source for p50071:
| Application Requirement | Drive Topology | p50082 | p50097 | p50071 Source | BO 50771 Behavior |
|---|---|---|---|---|---|
| Field follows enable, drops on fault | 2Q or 4Q | [1] | [0] | r53010.04 | Closes on ON, opens on OFF/fault |
| Field persists in fault for dynamic braking | 4Q (anti-parallel) | [1] | [1] | r53010.04 | Opens on fault; field pulses survive |
| Field follows current threshold (sequence controlled) | 2Q or 4Q | [1] or [3] | [0] or [1] | r53195.0 | Closes when field current > threshold |
| Field persists at standstill, no field contactor | 4Q | [3] | [0] | — (no contactor) | Hardware link omitted |
| 2Q field reversal with reversing contactor | 2Q | [1] | [0] | r53195.0 + r53210.2 (via AND/OR logic in free blocks) | Closes only in correct polarity |
| Field on with run-on for cooling fan | 2Q or 4Q | [4] | [0] | r53081.0 | Closes while line contactor is closed, opens p50094 s after OFF |
6. Recommended Parameterization for "Field On During Fault"
The most common requirement in hoist, elevator, and large mill drives is to maintain field excitation during a fault so that dynamic braking functions correctly. The recommended parameter set is:
p50082 = 1 ; Field on during run (release on OFF)
p50097 = 1 ; Field pulses remain enabled during fault
p50071 = r53010.04 ; BO 50771 source = "Drive running / no fault"
p50094 = 60 ; Auxiliary delay = 60 s (only relevant if p50082 = 4)
p50395 = 0.05 ; Field contactor open threshold (5% of I_FN)
With this configuration:
- During normal operation: the field contactor is closed, the field is energized, and the motor is controllable.
- On OFF1: the field contactor opens after the current decays below p50395. The field pulses are blocked.
- On OFF2 / OFF3: the field contactor opens immediately. The field pulses are blocked (r53195.0 resets).
- On fault (F30xxx, F06xxx): if p50097 = 1, the field pulses remain enabled. The field contactor (driven by r53010.04) opens. Dynamic braking still functions because the field is still present and the motor acts as a generator into the armature circuit.
- On line supply loss: the field contactor opens and the field pulses are blocked. Dynamic braking is not possible because the armature has no DC link support; the motor will coast.
7. The "Field On with p50082 = 4" Pattern
If the requirement is to keep the field contactor closed for a defined period after a fault (e.g., to allow a cooling fan to dissipate armature heat), use p50082 = [4] with a long p50094. In this mode:
p50082 = 4 ; Field on with delay-off
p50094 = 120 ; 120 s delay after OFF
p50097 = 1 ; Field pulses during fault
p50071 = r53081.0 ; "Field on" status (independent of operating state)
With p50082 = [4], the field contactor (via r53081.0) remains closed for p50094 seconds after the drive leaves operating state ON. This is the correct pattern when auxiliary systems (fans, pumps) must run on after the drive is stopped. Note: r53081.0 will drop if n < nmin in some firmware revisions, even with p50082 = [4]. Verify the actual state by reading r53081.0 in the trace during a controlled ramp-down to zero speed.
8. 2-Quadrant vs 4-Quadrant Considerations
The choice of field contactor source depends heavily on the drive topology:
| Aspect | 2Q (Single Bridge) | 4Q (Anti-Parallel) |
|---|---|---|
| Field polarity | Reversed for negative torque | Fixed |
| Field contactor required? | Yes — for reversal | Not required; field is permanently wired |
| Recommended p50071 source | r53195.0 (sequence control) + r53210.2 (direction) combined via free blocks | r53010.04 or r53195.0 (no reversal needed) |
| Dynamic braking on fault | Possible in both directions; field reversal contactor must not switch during braking | Always possible in current direction; field does not change |
| Contact welding risk | Higher — contactor opens under load during reversal fault | Lower — contactor only opens at zero field current |
9. BO 50771 Wiring Procedure
The Binector Output BO 50771 is the internal logic signal that drives the field contactor output. The wiring is:
- Open STARTER or the SINAMICS DCM commissioning tool (DriveMonitor or SIMOTION SCOUT). Connect to the drive via PROFIBUS or Ethernet.
- Navigate to Expert List → Field → p50071.
- Read the current BICO source. The default in firmware V1.4 and later is r53010.04.
- To change the source, click the "BICO" button next to the parameter field and select the desired signal (e.g., r53195.0).
- If using a free interconnection block (e.g., AND of r53195.0 and NOT r53210.2 for 2Q reversal), configure the free block first and point p50071 to its output.
- Download to the drive (Copy RAM to ROM).
- Cycle the electronics power supply to activate the new wiring.
- Verify with the trace function: trigger a controlled ON, monitor r53010.04, r53195.0, r53081.0, and the digital output state. All three should transition within 50 ms of each other.
10. Verification Procedure
After parameterization, verify correct operation with the following steps:
- Visual check: Manually command the contactor via STARTER (Control Panel → Field on). Listen for the contactor closure, measure the coil voltage, and confirm with a multimeter that the contactor main contacts are closed.
- Current ramp test: Apply a small setpoint (5 % of rated field current). The field current should ramp to the setpoint within the field time constant (typically 0.5 s to 5 s). Use the trace to record p50050 (field current actual) and the BO 50771 status.
- Fault trip test: Force a non-critical fault (e.g., trip the line contactor auxiliary contact). With p50097 = 1, verify the field current remains at the setpoint for at least 1 second after the fault. With p50097 = 0, verify the field current decays to zero within 100 ms.
- OFF1 test: Command OFF1. The field contactor should open only after the field current has decayed below p50395. Use a clip-on ammeter on one of the field leads to measure the current at the moment of contactor opening — it should be less than 5 % of IFN.
- OFF2 test: Command OFF2. The field contactor should open within 50 ms. The field pulses are blocked. Verify that the field current decays through the field winding and the freewheel diode, not through the contactor.
- Dynamic braking simulation: With the motor spinning at 50 % of base speed (use a prime mover or residual rotation), command a fault. With p50097 = 1, the armature current should build up as the motor acts as a generator, and the speed should decay exponentially. Without p50097 = 1, the speed will coast down (no braking torque).
11. Common Faults and Their Root Causes
| Symptom | Probable Cause | Correction |
|---|---|---|
| F60072 (field overcurrent) | Field contactor closed before pre-charge complete; inrush into field capacitor | Add 200 ms delay between p50071 (r53195.0) and the contactor coil; check p50340 (pre-charge time) |
| F30001 (overcurrent armature) | Field contactor opened under load; field collapsed, armature overcurrent on remaining flux | Set p50097 = 1 to keep field on during fault; verify p50395 threshold |
| F06100 (line contactor dropout) | r53010.04 used as source but p50097 = 1 keeps field on; contactor chatters | Use r53195.0 as source so contactor follows field sequence, not enable |
| Field contactor chatters at low speed | n < nmin condition in r53081.0 | Set p50082 = 4 or change source to r53195.0 |
| Dynamic braking fails on fault | p50097 = 0 (default) — field pulses blocked on fault | Set p50097 = 1; verify field contactor remains closed |
12. Free Blocks and Custom Logic
For complex requirements (e.g., field on during fault only if certain conditions are met), use the free interconnection blocks in the DCM. Typical free blocks include:
- AND, OR, XOR: Combine r53010.04, r53195.0, r53210.2 with operator inputs.
- RS flip-flop: Latch the field contactor command during a transient fault.
- Timer (pickup / dropout): Add delay between the BICO source and BO 50771.
- Comparator: Compare field current to a threshold and override the contactor command if current is not flowing.
An example "field on during fault for 30 s, then release" logic:
; Free block 1: AND
Input 1: r53010.04 ; Drive enable
Input 2: r53195.0 ; Field sequence OK
Output: AND_1 → r53700.0
; Free block 2: Timer (dropout delay = 30 s)
Input: AND_1
Output: TIMER_1 → r53701.0
; Wire p50071 = r53701.0
; During fault, AND_1 resets to 0, but TIMER_1 holds for 30 s
; After 30 s, the field contactor opens
13. Commissioning Checklist
- ☐ Confirm drive topology: 2Q (single bridge) or 4Q (anti-parallel).
- ☐ Confirm field contactor rating: Ue, Ie, AC-3 duty, coil voltage.
- ☐ Read current p50071 source from the drive before making changes.
- ☐ Select new p50071 source per the decision matrix in Section 5.
- ☐ Set p50082 according to the desired field-on behavior.
- ☐ Set p50097 = 1 if dynamic braking is required during faults.
- ☐ Set p50094 if p50082 = 4.
- ☐ Set p50395 (field contactor open threshold) to 5 % of IFN.
- ☐ Download parameters, cycle electronics power, repeat the verification tests.
- ☐ Document the final parameter set in the drive parameter sheet.
FAQ
Which is the correct BICO source for the field contactor: r53195.0, r53210.2, or r53081.0?
It depends on the topology and application. For 4Q drives where the contactor should follow the enable state, use r53010.04 (default). For 2Q drives with field reversal, use r53195.0 combined with r53210.2 via a free AND block. For applications where the field must persist at standstill, use r53081.0 with p50082 = [4].
Does setting p50097 = 1 keep the field contactor closed during a fault?
No. p50097 = 1 keeps the field firing pulses enabled during a fault, but the field contactor is driven by p50071, which is typically wired to r53010.04. To keep the contactor closed during a fault, wire p50071 to a signal that remains true in fault (e.g., a custom free block) or use r53195.0 with appropriate delay configuration.
How do I keep the field on when the line contactor is opened or the drive trips?
Set p50082 = [3] (field continuously on) and p50097 = [1] (field pulses during fault). The field will remain energized as long as the electronics power supply is present, even if the line contactor is open. Note that the field is fed from the same three-phase line, so if the line is lost, the field will also be lost.
What is p50094 used for?
p50094 sets the run-on time in seconds when p50082 = [4]. After the drive leaves operating state ON, the field contactor and field remain active for p50094 seconds. Default is 60 s. This is used to drive cooling fans, hold motors at field-heated temperature, or maintain dynamic braking capability for a defined period.
Can I use the field contactor for dynamic braking in a 4Q drive?
It is not recommended. In a 4Q drive, the field polarity is fixed and the armature bridge can absorb regenerative energy directly. Adding a field contactor introduces a single point of failure and a risk of contact welding. Keep the field permanently wired in 4Q topologies and omit the contactor unless maintenance isolation is required by local code.