When commissioning a SINAMICS G120 Control Unit CU240E-2 DP with STARTER V4.3 over a USB cable, the project download progresses to 94% of the progress bar, stalls for several seconds, the CU performs an internal reset, and the engineering PC enters a Windows Blue Screen of Death (BSOD). The fault is reproducible on every reconnection attempt and is not cured by unplug/replug cycles alone. This reference documents the field-verified resolution, the four-class root cause analysis, and the diagnostic sequence used to determine whether the failure is host-side (USB driver, STARTER installation, PG/PC interface), firmware-side (parameter set corruption, RAM-to-ROM mismatch), or hardware-side (damaged CU, missing Power Module supply).
1. Problem Statement and Symptom Table
| Symptom | Observed Behavior | Stage |
|---|---|---|
| Download progress | Reaches 94% and stalls for 2-6 s | Final parameter block transfer |
| CU activity | All LEDs extinguish briefly, then restart sequence | Implicit CU reset |
| PC reaction | BSOD (typically DRIVER_IRQL_NOT_LESS_OR_EQUAL or KERNEL_DATA_INPAGE_ERROR) |
USB stack failure |
| STARTER state | Loss of online connection, project goes offline | Post-BSOD |
| Reproducibility | 100% on every download attempt | Deterministic |
The 94% threshold corresponds to the final RAM-to-ROM staging block when the "Copy RAM to ROM" option is enabled. If the CU detects a parameter set that requires a non-volatile save and the host USB stack is unable to commit the pagefile write inside the watchdog window, the CU resets and the kernel driver on the host side faults.
2. Affected Components, Order Numbers, and Firmware
| Component | MLFB / Order Number | Minimum Affected FW | Recommended FW |
|---|---|---|---|
| SINAMICS G120 CU240E-2 DP | 6SL3244-0BB13-1PA1 / 6SL3244-0BB13-1PA3 | V4.4 (legacy) | V4.7 SP3 (HF) or later |
| SINAMICS G120 PM240-2 (any size) | 6SL3210-1PExx-xxxx | N/A | N/A |
| STARTER commissioning tool | 6SL3072-0AA00-0AG0 | V4.3 (problematic) | V4.5 SP1 or V5.x (Startdrive) |
| USB cable (PC to CU) | Standard USB-A to mini-USB | USB 2.0 | Shielded, < 3 m |
| BOP-2 Basic Operator Panel | 6SL3255-0AA00-4CA1 | FW 2.x | FW 4.x |
Reference manuals:
- SINAMICS G120 CU240E-2 Operating Instructions
- STARTER Commissioning Tool Documentation
- SINAMICS G120 List Manual (Parameter List)
3. Root Cause Analysis
The fault is a stack mismatch between the STARTER upload protocol and the CU commissioning state machine. The 94% mark is the last public checkpoint before the final block write that triggers a parameter commit. Four contributing causes have been observed in the field, and they often stack.
3.1 Power Module not connected to the Control Unit
The CU240E-2 requires the 24 V backplane supply from the PM (or from terminals 31, 32 of an external supply) during programming. If the CU is fed only through the USB port, the 5 V logic rail is shared with the USB PHY, and any spike during the parameter commit causes a brown-out on the CU side and a corresponding over-current detection on the host USB port. Siemens Technical Support has confirmed this is the most common root cause and the first item to verify on every field incident.
3.2 USB driver instability in STARTER V4.3
STARTER V4.3 ships with the SiemensUsbDriver v1.5.0.4 stack. The stack is signed for Windows 7 and early Windows 10 builds, but the IRQL handling in the driver does not cooperate cleanly with Windows 10 20H2 and later kernels. The 94% progress window opens an extended DPC, and the host kernel raises IRQL_NOT_LESS_OR_EQUAL. A clean STARTER reinstall registers the correct SiemensUsbDriver v1.6.1.0 and resolves the host-side fault.
3.3 Copy RAM to ROM checked at download time
When "Save parameter set in non-volatile memory" is enabled in the download dialog (STARTER: Load to target system > Additional settings > Copy RAM to ROM), the CU executes p0977 = 1 immediately after the final block. The bulk write to the internal non-volatile memory produces a sustained USB stall. STARTER V4.3 does not release the USB pipe during this window, which is the trigger for the BSOD on hosts whose USB stack is intolerant of multi-second stalls.
3.4 Corrupted parameter set on the CU
If the CU was previously loaded with a project that contains a parameter outside the firmware-allowed range, the commissioning state machine enters a recovery loop on the next download. The 94% mark is the point where the loop collides with the upload protocol. A factory reset (p0970 = 1 with p0010 = 30) clears the state and produces a known-good baseline.
4. Pre-Download Verification Checklist
Before performing a download to the CU240E-2 DP, confirm each row of the following table:
| # | Check | Pass Criterion |
|---|---|---|
| 1 | PM240 / PM240-2 seated on the CU and DC link charged | RDY LED steady green, no F30002 / F30003 |
| 2 | 24 V at terminals 31, 32 of the PM | 22.8 V to 25.2 V DC measured at the terminals |
| 3 | STARTER version | V4.4 SP3 or later; or Startdrive V15.1 or later in TIA Portal |
| 4 | PG/PC interface set to "Device (Starter, Scout)" for S7ONLINE | Confirm in Control Panel > Set PG/PC Interface |
| 5 | USB cable shielded, < 3 m, no ferrule | Visual inspection |
| 6 | "Copy RAM to ROM" unchecked at first download | STARTER dialog verification |
| 7 | CU firmware on the drive matches the STARTER project | Compare p0018 / r0018 with STARTER navigator header |
| 8 | No antivirus or backup software intercepting USB mass storage | Temporarily disable or whitelist the CU USB device |
| 9 | DC link discharged (mains removed > 5 min) | DC link LED extinguished before any CU removal |
5. Resolution: Primary Path (PM Connection plus STARTER Reinstall)
The field-verified resolution is a two-step action:
- Connect the PM to the CU before any download attempt. The PM provides the 24 V backplane power that the CU needs during parameter commits. USB alone is not sufficient for programming.
-
Reinstall STARTER 4.3 (or upgrade to a later version). The fresh install replaces the
SiemensUsbDriverstack and registers the correct S7ONLINE access point.
Procedure:
- Power down the drive, disconnect mains from the PM.
- Wait at least 5 minutes for the DC link capacitors to discharge; confirm the DC link LED is off before handling the CU.
- Confirm the CU is firmly seated on the PM. The two retaining screws must be torqued to 1.5 Nm.
- Reconnect mains, wait for the RDY LED to be steady green.
- From Windows Control Panel, uninstall STARTER. Reboot.
- Reinstall STARTER V4.3 SP3 (or, preferably, V4.5 SP1) from the original Siemens DVD or the official Siemens download. The installer auto-registers
S7ONLINE (STEP7) -> Device (Starter, Scout). - Open STARTER, open the project, click Load to target system. With "Copy RAM to ROM" still unchecked, the download completes in < 30 s on a typical CU240E-2 DP.
- After successful download, manually execute Target system > Copy RAM to ROM from the menu. This is the second-stage save that the original blocked transfer was trying to perform.
6. Resolution: Disable RAM-to-ROM During Download
If the PM is already connected but the BSOD persists, the next suspect is the in-dialog "Save RAM to ROM" flag. Disable it as follows:
- Open the project, right-click the drive in the project navigator, choose Load to target system > Expert > Load.
- In the "Load" dialog, click Additional settings.
- Uncheck Save parameter set in non-volatile memory (Copy RAM to ROM).
- Confirm with Finish.
- When the load completes, manually copy RAM to ROM via the menu bar: Target system > Copy RAM to ROM.
This approach is the second most common field resolution. The third most common is to upgrade STARTER to V4.5 SP1 or to switch to Startdrive in TIA Portal V16 or later, where the USB-PNIC bridge is handled by the Siemens PCU USB driver and the load window is shorter. Reference: Siemens Support Entry 109763120 — Startdrive for SINAMICS G120.
7. PG/PC Interface Access Point Configuration
STARTER uses the S7ONLINE access point. The access point determines which physical device is used for the load. The CU240E-2 DP with USB cable requires the entry "Device (Starter, Scout)". The wrong entry routes the load to a virtual COM port that the CU does not have, which can also produce a hang at 94% but without a BSOD.
To set the access point:
- Open Windows Control Panel.
- Open Set PG/PC Interface (32-bit control panel applet — STARTER V4.x is 32-bit; on 64-bit Windows the applet must be run from
%SystemRoot%\syswow64\control.exe). - Under Access Point of the Application, select S7ONLINE (STEP7) -> Device (Starter, Scout).
- Under Interface Parameter Assignment Used, select the USB TCP/IP entry that points to the CU. If no entry exists, click Properties > New and add the CU USB Ethernet-over-USB interface (default IP 169.254.11.22, subnet 255.255.0.0).
- Click OK, close the applet, restart STARTER.
Reference: Siemens Support Entry 48955385 — Setting the PG/PC Interface for STARTER.
8. Alternative Commissioning via BOP-2
If STARTER cannot be made to load at all, fall back to the BOP-2 Basic Operator Panel (6SL3255-0AA00-4CA1). The BOP-2 communicates with the CU via the diagnostic interface (RJ45) on the front of the CU and does not use the USB stack. Parameter uploads, downloads, and factory resets are possible from the BOP-2 menu tree.
To perform a factory reset from the BOP-2:
- Plug the BOP-2 into the CU RJ45 diagnostic port.
- Navigate to Menu > Parameter > Filter > All parameters.
- Set
p0010 = 30(commissioning filter = factory reset). - Set
p0970 = 1(start factory reset). - Wait for the CU to complete the reset (about 30-90 s; the RDY LED flashes orange during the write).
- Set
p0010 = 0to close the commissioning filter.
After the reset, re-attempt the STARTER download. The 94% hang should no longer occur because the parameter set is back to a known-good state. The BOP-2 also allows you to inspect active faults (Menu > Diagnostics > Active faults) without any USB connection, which is useful for confirming whether the CU is damaged.
9. Factory Reset Procedure via STARTER
If the BOP-2 is unavailable, the factory reset can be initiated from STARTER once a partial online connection is achieved (the connect works, the download does not):
- Open STARTER, go online with the CU (right-click > Go online). This step does not require a download.
- Open the expert list (right-click the drive > Expert list).
- Set
p0010 = 30and acknowledge with the "Apply" button. - Set
p0970 = 1and acknowledge. The CU performs the reset. - Reconnect in STARTER. The connection will drop during the reset and re-establish once the RDY LED returns to steady green.
10. Hardware Damage Indicators
If the PM is connected, the "Copy RAM to ROM" is unchecked, the STARTER version is current, the PG/PC interface is correct, and the factory reset has been performed, and the 94% BSOD still occurs, the CU is likely damaged. The damage is typically on the USB PHY or the 24 V to 5 V regulator. Confirm with the following tests:
| Test | Method | Pass / Fail |
|---|---|---|
| USB enumeration | Plug CU into PC, observe Device Manager | Fail: yellow bang, Code 43, or no enumeration |
| 5 V rail ripple | Scope 5 V at test point TP5 on CU PCB | Fail: > 100 mV pk-pk ripple under load |
| Self-test at power-up | Apply 24 V to PM with no USB, watch LED sequence | Fail: RDY LED never reaches steady green within 10 s |
| PROFIBUS node visibility | Connect to DP master, scan for slaves | Fail: slave not visible or diagnostic alarm "station failure" |
| Error code on BOP-2 | Navigate to Menu > Diagnostics > Active faults | Fail: F30002 (5 V undervoltage), F30003 (24 V undervoltage), F01018 (CU fault) |
Relevant fault codes for a CU240E-2 DP that fails the 94% load test:
| Fault Code | Meaning | Action |
|---|---|---|
| F01018 | Power-on self-test failure | Replace CU |
| F30002 | 5 V DC link undervoltage | Check 24 V supply, replace CU if supply is good |
| F30003 | 24 V undervoltage | Check PM, check wiring to terminals 31/32 |
| A01009 | CU firmware checksum warning | Re-flash firmware, then factory reset |
| F08501 | PROFIBUS communication error | Check DP cable and terminator, not related to BSOD |
| A01007 | Firmware version mismatch | Match STARTER project firmware to CU firmware, reload |
Reference: SINAMICS G120 List Manual — Fault and Alarm List.
11. Verification Tests After Resolution
After applying the resolution, run the following verification matrix:
| Step | Test | Expected Result |
|---|---|---|
| 1 | Power up PM + CU without USB | RDY LED steady green within 10 s |
| 2 | Connect USB, open STARTER, go online | Online connection within 5 s |
| 3 | Load project with "Copy RAM to ROM" unchecked | Load completes at 100% in < 30 s, no BSOD |
| 4 | Manually copy RAM to ROM from menu | Operation completes, RDY LED may flash during write |
| 5 | Power cycle the drive | Parameters retained, drive ready to run |
| 6 | Read back parameter set via STARTER | Matches project (compare expert list checksum) |
| 7 | Issue run command from STARTER control panel | Drive ramps to reference, no faults |
12. Field Notes and Pitfalls
- Do not hot-plug the USB cable. The CU USB port is not designed for hot-plug during an active load. Always stop the load in STARTER (cancel button) before unplugging.
- Do not load a project whose firmware version (
p0018) does not match the CU installed firmware version. Mismatched loads produce A01007 and can corrupt the parameter set, leaving the CU in a state that only a factory reset recovers. - Do not run a third-party backup or antivirus scan during the load. The bulk USB writes look like mass storage activity to backup software, and the backup client may open the file handle at the same time the load is committing the parameter block.
- When upgrading STARTER, always install STARTER before installing the Startdrive add-in. Reverse order produces a registry collision on the S7ONLINE access point and the 94% symptom reappears even on a known-good drive.
- On Windows 11, the legacy STARTER V4.3 requires the 32-bit ODBC drivers to be installed. Without them, the project save produces a silent error that surfaces as a 94% hang on the next load.
- If you must use PROFIBUS instead of USB, the 94% symptom does not appear; the DP stack handles the long write without crashing. The PROFIBUS connection is therefore a useful diagnostic step: if the load works over DP but not USB, the issue is host-side.
- After a successful download over USB, always perform the manual Copy RAM to ROM step before powering off the PM. The download only writes to RAM; without the non-volatile save, the parameters are lost on power cycle.
13. FAQ
Why does the STARTER download stop at exactly 94% on a CU240E-2 DP?
The 94% threshold is the checkpoint just before the final non-volatile parameter commit (Copy RAM to ROM). At this point the CU commissioning state machine opens a sustained USB write window, and the host-side STARTER USB driver stack in V4.3 cannot service the kernel DPC inside the watchdog window, producing a BSOD.
Is it required to connect the Power Module before programming a SINAMICS G120 CU?
Yes. The CU240E-2 requires the 24 V backplane supply from the PM (or from external terminals 31, 32) during parameter commits. USB alone supplies the 5 V logic rail, which is insufficient for the EEPROM write and shares the USB PHY power, producing a brown-out and BSOD.
Can I fix the BSOD by upgrading STARTER to a newer version?
Yes, in most cases. STARTER V4.4 SP3 and V4.5 SP1 include a revised USB driver stack and improved load progress handling. TIA Portal with Startdrive V15.1 or later also resolves the issue for most users.
Does disabling Copy RAM to ROM during the load lose the parameter set?
No. The parameter set is committed to RAM during the load. The Copy RAM to ROM step is the additional non-volatile save. Performing the save manually from the menu after a successful load has the same effect as the in-dialog checkbox.
What fault code on the BOP-2 indicates a damaged Control Unit?
Check for F01018 (power-on self-test failure), F30002 (5 V undervoltage) with the 24 V supply confirmed good, or A01009 (firmware checksum warning) that does not clear after a re-flash. Any of these with a 94% BSOD and a confirmed good PM supply indicates a damaged CU that must be replaced.
Can I use PROFIBUS instead of USB to avoid the BSOD?
Yes. The 94% symptom is specific to the USB stack in STARTER V4.3. Loading over PROFIBUS uses the DP stack, which tolerates the long non-volatile write without crashing. If the load works over PROFIBUS but not USB, the issue is host-side (USB driver, PG/PC interface, or missing PM supply).