SINAMICS G120 PM240 External Braking Chopper Configuration

David Krause18 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

SINAMICS G120 PM240 External Braking Chopper Configuration and 570 V DC Link Diagnosis

Problem Overview

Engineers commissioning a SINAMICS G120 drive train with Control Unit CU240E-2 DP and a 200 kW PM240 Power Module (Frame Size G) frequently report an "abnormal" 540–580 V DC measurement across the external braking chopper terminals during no-motor bench test. The reading, although it triggers a stop-the-line reaction from operators accustomed to 480 V AC systems, is the expected intermediate-circuit (DC link) voltage of a 400 V-class PM240. The real fault is almost always one of three things: a measurement point error, a missing line-voltage entry, or a brake-chopper parameter set that has not been commissioned for the external unit. This reference explains the DC link physics, the parameter set that controls the brake chopper, and the commissioning sequence that separates a normal DC link reading from a true chopper failure.

The drive in question consists of:

  • Control Unit: CU240E-2 DP (PROFIBUS variant, order number 6SL3244-0BB13-1PA0 or equivalent)
  • Power Module: PM240 200 kW, 400 V 3-phase, Frame Size G (6SL3224-0BE38-8U..)
  • External Braking Chopper: 100 kW / 185 A braking unit connected to the DC bus terminals
  • Status: Bench test, no motor on the inverter output side

DC Link Fundamentals

The PM240 is a voltage-source inverter (VSI). The 3-phase AC mains is rectified to produce the DC link voltage that the IGBT bridge inverts back to variable-frequency AC. The DC link is the energy-storage reservoir between the rectifier and the inverter; without it, the inverter cannot commutate at low speed and the line-side harmonics become unacceptable.

For a 400 V 3-phase supply, the ideal no-load DC link voltage equals the peak line-to-line voltage:

V_dc(ideal) = V_LL × √2 = 400 V × 1.4142 = 565.7 V DC

Under load, the source impedance, the diode drops, and the DC link capacitor ripple reduce the average value to approximately 540 V DC. During regenerative braking, the DC link rises above the rectified mains because the motor acts as a generator pumping current back into the bus. The brake chopper is the controlled discharge path: it switches a power resistor across the DC bus when the bus voltage exceeds a fixed threshold, dissipating the regenerative energy as heat.

The expected DC link range for a 400 V-class PM240 is:

Operating Condition Expected V_dc (r0027) Status
Mains off, control power only 0 V Normal
Mains on, no load, no motor 565–580 V DC Normal
Mains on, motor motoring at rated load 525–555 V DC Normal
Regenerative braking, chopper idle 600–700 V DC Normal transient
Chopper active (threshold exceeded) ~774 V DC (clamped) Normal during braking
DC link overvoltage fault threshold >800 V DC Fault F30004 trips

A 570 V DC reading at the chopper terminals during a no-motor test is therefore not a fault. It is the no-load DC link, sitting at the peak of the rectified mains. Confirm with the diagnostic parameter r0027 (DC link voltage actual) read on the IOP panel, STARTER, or TIA Portal Startdrive.

Critical measurement-point guidance. The 570 V DC must be present on the DC bus input terminals of the chopper (DCP/R1 and DCN/R2) whenever the drive is powered. It must not be present on the braking resistor terminals of the chopper output when the chopper is inactive. Voltage on the resistor terminals when the chopper IGBT is OFF indicates a shorted IGBT module inside the chopper — that is a real fault and requires replacement.

SINAMICS G120 PM240 Frame Size G Architecture

The 200 kW PM240 resides in Frame Size G (FSG). This is the largest frame in the PM240 family and is the first frame where the internal brake chopper transistor is not provided. FSG drives must use an external braking unit. The DC bus terminals (DCP, DCN) on FSG are heavy busbars, not stud terminals, sized for 1000 A continuous.

The frame layout is documented in the Siemens Industry Online Support portal under the SINAMICS G120 PM240 operating instructions. The relevant sections cover:

  • Power Module connection overview (DCP, DCN, U/T1, V/T2, W/T3, PE)
  • Minimum cable cross-section for the DC bus (≥ 95 mm² Cu at 200 kW, 105 °C rated)
  • Cooling air requirements (FSG requires forced-air cooling with a 24 V DC fan)
  • Touch-safe shrouding for the DC bus

For FSG, the wiring sequence is:

  1. Confirm mains is locked out and the DC link is discharged (wait ≥ 5 minutes after power-off; the DC link LED on the CU must be off).
  2. Connect the external brake chopper DC input cables between the PM240 DCP and DCN busbars and the chopper DC+ / DC- terminals.
  3. Connect the braking resistor cables between the chopper output terminals and the resistor element.
  4. Connect the chopper's fault/control signalling cable (typically a 24 V digital input signalling "chopper healthy") to a free DI on the CU240E-2.
  5. Verify PE bonding on the chopper chassis and resistor housing.

External Braking Chopper Topology

An external braking chopper is a self-contained unit containing:

  • DC bus input (DCP, DCN) — wired in parallel with the PM240 DC link
  • IGBT switching element — pulsed at low duty to control resistor current
  • Braking resistor output (R+, R-) — wired to the external resistor
  • Control logic / power supply — derives gate drive from the DC bus, monitors the threshold
  • Fault relay or transistor output — wired back to the CU digital input

The chopper is electrically parallel to the DC link. When the DC link voltage exceeds the chopper's internal threshold (typically 760–780 V DC for 400 V class), the chopper IGBT begins to pulse, switching the braking resistor across the bus. This clamps the DC link at the threshold and dissipates the regenerative energy as heat in the resistor.

Two design philosophies exist:

Chopper Type Threshold Setting Drive-Side Parameter Fault Signalling
Self-contained (third-party or Siemens) Internal potentiometer or DIP switch p1230 = 0 (internal disabled) DI on CU240E-2 via p2100 mapping
Drive-controlled (uses p1231 as threshold) Driven from p1231 p1230 = 1, p1231 = threshold DI from chopper fault contact

For the user's 100 kW / 185 A third-party chopper, the self-contained design is assumed. The chopper's own threshold is set on the chopper hardware; the drive's role is to:

  1. Disable the (non-existent on FSG) internal chopper.
  2. Wire the chopper's fault output to a digital input.
  3. Map the digital input to fault code F06902 so the drive trips on a chopper-side fault.
  4. Enable the Vdc controller so the drive limits the DC link rise by reducing the inverter's regen torque.

Expected DC Link Voltage by Line Class

The PM240 supports both 400 V and 480 V AC input. The activation threshold p1231 is auto-calculated from p0210 and the unit's voltage class. The two major variants:

Parameter 400 V class (3-ph 380–480 V) 480 V class (3-ph 480 V nominal)
p0210 (line supply voltage) 400 480
r0027 no-load typical 565–580 V DC 678–695 V DC
r0027 loaded typical 525–555 V DC 635–665 V DC
p1231 brake chopper threshold 774 V DC (auto) 967 V DC (auto)
F30004 overvoltage trip >800 V DC >1000 V DC

The 570 V DC reported in the source is therefore consistent with a 400 V class PM240 with mains on, no load, and the Vdc controller inactive (because there is no motor connected to demand a regen event). If the user ever sees 695 V DC under the same conditions, the drive is set to the 480 V class and p0210 = 480 was entered by mistake.

Brake Chopper Parameter Set

The SINAMICS G120 brake chopper parameter family is p1230 through p1245, with status read-back in r0027, r1238, and r1239. The relevant entries:

Parameter Description Default External Chopper Setting Comment
p0210 Drive unit line supply voltage 400 Verify = actual mains Wrong entry shifts all derived thresholds
p0212 Power unit configuration Auto 0 (FSG no internal chopper) Do not override auto
p1230[0...n] Brake chopper activation 0 0 (disabled) or 3 (external with DI monitoring) 0 = internal off, 3 = external w/ fault input
p1231 Brake chopper activation threshold (read-only) 774 V (400V class) Auto-calculated; do not overwrite Derived from p0210
p1232[0...n] Brake chopper pulse enable 0 0 (no drive-side pulsing) External chopper pulses itself
p1233 Brake chopper pulse duration — — Internal use only
p1234 Brake chopper pulse frequency — — Internal use only
p1235 Brake chopper max continuous power Auto Set to 100 kW if internal; 0 if external Protects internal IGBT; for external set to 0 unless used for monitoring
p1237 Brake chopper switch-off threshold (read-only) p1231 - 5 V Auto —
p1240[0...n] Vdc controller configuration 1 1 (enable) or 0 (disable) 1 enables Vdc_min and Vdc_max controllers
p1245[0...n] Brake chopper switch-on level (read-only) p1231 Auto —
r0027 DC link voltage actual — Monitor 540–580 V at no load Primary diagnostic
r1238[0] Brake chopper current actual — 0 A when chopper idle Read during braking test
r1239[0...2] Brake chopper status word — Bit 0 = active, Bit 1 = fault —

For an external chopper application, the drive-side commissioning values are:

p0210 = 400         ; (or 480 if 480 V class)
p1230[0] = 0        ; internal chopper disabled (FSG has none)
p1232[0] = 0        ; drive does not generate brake pulses
p1235 = 0           ; no internal IGBT thermal model used
p1240[0] = 1        ; Vdc controller enabled
p2100 = 722.0       ; fault source for F06902 = DI 0 (adjust to actual DI)
p2101 = 724         ; fault source inverted = 0 (active high fault)

The mapping in p2100 and p2101 is the often-missed step. Without this, a chopper hardware fault will not surface as a drive fault. The drive continues to push the bus, the chopper saturates, and the bus climbs to F30004 overvoltage trip — by which point the resistor has been over-stressed.

Commissioning Procedure

  1. Verify the drive rating and chopper sizing. The 200 kW PM240 with a 100 kW chopper is a common mismatch used when the load's peak braking power is < 100 kW. Confirm the load's worst-case regen does not exceed 100 kW for more than the chopper's rated duty cycle. If the load can demand 200 kW of regen (a free-falling vertical axis for example), the chopper is undersized and the Vdc controller will not save it.
  2. Set p0210 to the actual line-to-line voltage. For 380–415 V class, use 400. For 440–480 V class, use 480. This single parameter sets the auto-derived chopper threshold p1231 and the Vdc controller bands.
  3. Disable the internal chopper. FSG does not have an internal chopper, but set p1230[0] = 0 explicitly to remove the drive-side pulsing logic. The drive will not pulse the (non-existent) internal IGBT.
  4. Enable the Vdc controller. Set p1240[0] = 1. The Vdc_max controller will then actively reduce the inverter's regen torque when the DC link approaches p1231, providing a smooth hand-off to the external chopper.
  5. Map the chopper fault input. Wire the chopper's fault contact to a free digital input (e.g., DI 0 on the CU240E-2). Map it via p2100[0] = 722.0 and set the inversion in p2101[0] so that an open contact (chopper fault) trips F06902.
  6. Save to EEPROM. p0971 = 1 or copy RAM to ROM via STARTER / Startdrive / IOP.
  7. Apply mains and check r0027. With mains on, no motor, no enable: r0027 should read 565–580 V DC for 400 V class. This is the no-load DC link and is the value the user is reading at the chopper input terminals. There is no fault.
  8. Verify chopper idle. r1239[0] bit 0 = 0 (chopper not active), bit 1 = 0 (no fault). r1238[0] = 0 A. The voltage on the braking resistor terminals of the external chopper should be 0 V DC (chopper IGBT is open).
  9. Perform a controlled braking test. With a motor connected, accelerate to a known speed, then command a fast stop. Monitor r0027, r1238, and r1239 in the trace. The DC link should rise to ~774 V (or 967 V for 480 V class), the chopper should engage (r1239[0] bit 0 = 1), and the resistor current should peak at the chopper rating (185 A × duty factor). The Vdc controller should clamp the peak just above p1231 and the chopper should regulate around it.
  10. Verify fault path. Manually trip the chopper (open the fault contact). The drive should immediately post F06902 and coast to stop. Reset only after the chopper is healthy. This proves the safety path end-to-end.
Warning. Step 9 requires a real mechanical load. Never command a fast stop with a vertical axis unless a mechanical back-up brake is engaged. The chopper does not hold position — it only absorbs energy during a controlled deceleration.

Verification Parameters

After commissioning, monitor the following signals continuously for the first 10 operating cycles:

Signal Expected at Idle Expected During Braking Fault Indication
r0027 DC link voltage 540–580 V DC Clamped at p1231 ± 5 V >800 V DC = F30004
r1238[0] chopper current 0 A 0–185 A pulsed Continuous > 200 A = overload
r1239[0] bit 0 active 0 1 (chopper pulsing) Stuck = fault
r1239[0] bit 1 fault 0 0 1 = trip to F06902
Resistor terminal voltage 0 V DC Pulsed 0–774 V Stuck high = shorted IGBT
Resistor surface temperature Ambient Rising during braking, falling after Continuous high = undersized

The combination of r0027 not exceeding p1231 and r1239[0] bit 0 toggling only during regen events is the canonical proof that the chopper is correctly parameterized.

Fault and Warning Codes

Code Type Cause Remedy
F06901 Fault Brake chopper IGBT overcurrent / short Inspect chopper, check resistor insulation, verify DC bus polarity
F06902 Fault External brake chopper fault (via DI) Check chopper status, reset after healthy
F06903 Fault Brake chopper ground fault Insulation test on resistor and cabling
A06901 Warning Brake chopper active — informational Expected during regen; no action
A06902 Warning Brake chopper I²t pre-warning Reduce regen duty or upsize chopper
F30004 Fault DC link overvoltage Chopper failed to engage; check wiring and p1230
A50002 Warning DC link overvoltage warning threshold Chopper undersized or Vdc controller disabled
F30005 Fault DC link undervoltage Mains dip; check input fuses
F30007 Fault DC link voltage monitoring Hardware fault on CU; replace

The most common code on FSG is F30004 when a third-party chopper has been wired but not mapped. The drive does not know the chopper exists, the bus rises above 800 V DC, and the IGBT bridge self-protects by tripping. The fix is the p2100 mapping plus verifying p1240[0] = 1.

Troubleshooting Matrix

Symptom Likely Cause Diagnostic Remedy
570 V DC across chopper DC input, no fault Normal no-load DC link r0027 = 565–580 V DC None — drive is healthy
570 V DC across resistor terminals, chopper idle Shorted chopper IGBT Isolate chopper, megger test IGBT Replace chopper module
F30004 on first regen attempt Chopper not engaging Check p1230, p1235, external threshold setting Enable Vdc controller, set p1235 = 0, adjust external threshold below 800 V
F06902 on every enable Chopper fault contact wired normally-closed incorrectly Verify p2101 inversion Adjust p2101 to match contact logic
r0027 climbs to 800 V and trips on every decel Chopper threshold set too high (e.g., 850 V on 400 V class) Measure chopper threshold with scope on DC bus Set external chopper threshold to 760–780 V DC
r1238 shows continuous 100 A at idle Chopper IGBT partially shorted Disconnect resistor, measure IGBT C-E resistance Replace chopper
Resistor smokes during first braking Chopper undersized for the regen power Calculate E = 0.5 × J × ω² per stop Upsize chopper and resistor to peak regen power
A06902 I²t warning under cyclic braking Duty cycle too high Check stop frequency and inertia Reduce stop rate, use a larger resistor, or add a regenerative line module
DC link 0 V with mains on Pre-charge contactor not closing or DC bus fuse blown Check F3/F4 fuses in PM240, check 24 V supply to pre-charge Replace fuse, verify 24 V to pre-charge coil

Field-Proven Caveats

From repeated commissioning of PM240 FSG systems with external choppers, the following caveats avoid the most common pitfalls:

  • Do not measure at the resistor terminals with a standard DMM while the drive is running. The PWM pattern from the chopper can give misleading RMS readings. Use an oscilloscope with a 1000 V DC / high-bandwidth differential probe if a resistor-side measurement is required.
  • Frame Size G is air-cooled with a 24 V fan. A missing or failed fan is a common cause of "drive trips after 20 minutes" because the chopper overheats and trips F06901. Check the fan before anything else.
  • Wire the DC bus in a tight, equal-length loop. The stray inductance of the DC bus cable couples to the IGBT collector. A 1-metre difference between DCP and DCN paths can add 200 nH and cause a 50 V overshoot on every regen pulse. Use twisted or co-ax arrangement.
  • PE bond the chopper chassis to the drive PE bar, not to the building steel. A floating chassis can develop 100 V common-mode with respect to the drive ground and inject noise into the CU.
  • Set p1235 = 0 for external choppers. The default value of p1235 is the internal IGBT's continuous rating, which is 0 W for FSG. Leaving the default value can trigger false I²t warnings.
  • Verify the line-side voltage class with the order code suffix. PM240-2 has order number suffix letters that indicate voltage class: 0B = 400 V, 0C = 480 V, 0D = 690 V. The p0210 value must match the unit's voltage class, not the actual mains. A 480 V unit on 400 V mains will undervoltage-fault; a 400 V unit on 480 V mains will overvoltage-fault within 50 ms of mains close.

Safety Considerations

DC bus remains lethal for 5 minutes after mains removal. The PM240 FSG stores up to 7,200 µF at 580 V DC, equivalent to 1.2 kJ. Confirm r0027 = 0 V and the DC link LED is off before touching any DC-side terminal. Use a 1000 V DC rated probe with a 10 MΩ input impedance — never a low-impedance solenoid tester.

Additional safety requirements for the chopper installation:

  • The braking resistor must be mounted outside the cabinet on a non-flammable surface, with a minimum 200 mm clearance to any cable or combustible material.
  • Wire the chopper's fault contact through a safety-rated digital input if the axis is a vertical load. A failed chopper on a vertical axis is a free-fall hazard.
  • Use a thermal switch on the resistor, wired to a drive DI mapped to a fault. A resistor that has lost its cooling (fan failure) is a fire risk.
  • Do not bypass the chopper's internal I²t protection with p1235 = 0 on internal-chopper PM240 frames. FSG has no internal chopper so this is a non-issue, but a common error when migrating a 75 kW PM240 (FSF) configuration to 200 kW (FSG).

Document References

The following Siemens documents and tools are required for a proper PM240 FSG commissioning. They should be available in the cabinet's documentation pocket:

Why does my SINAMICS G120 PM240 show 570 V DC across the brake chopper terminals during a no-motor test?

The 570 V DC is the no-load DC link voltage of a 400 V-class PM240 Power Module. With mains on and no motor, the rectifier charges the DC link capacitors to the peak of the line-to-line voltage (400 V × √2 ≈ 566 V), with a small no-load overshoot to 570–580 V. This is normal. Read r0027 on the IOP or Startdrive to confirm; a value between 540 V DC (full load) and 580 V DC (no load) is the expected operating range. The reading is only a fault if it exceeds 800 V DC, at which point the drive trips F30004 overvoltage.

What parameter activates the external braking chopper on a SINAMICS G120 PM240 Frame Size G?

FSG has no internal chopper. Set p1230[0] = 0 to explicitly disable the internal chopper logic, p1232[0] = 0 so the drive does not generate brake pulses, and p1235 = 0 to disable the internal IGBT I²t model. The external chopper controls itself from the DC bus. Enable the Vdc controller with p1240[0] = 1 so the drive actively limits regen torque as the bus approaches the chopper threshold. Map the chopper fault contact via p2100 / p2101 to a digital input so the drive trips F06902 if the chopper fails.

What is the default brake chopper activation threshold for a 400 V-class PM240?

The threshold is parameter p1231 and is auto-calculated from p0210. For 400 V class (p0210 = 400), p1231 = 774 V DC. For 480 V class (p0210 = 480), p1231 = 967 V DC. The parameter is read-only and must not be overwritten. The external chopper's own hardware threshold should be set slightly below p1231 (typically 760–780 V DC) so the chopper engages just before the Vdc controller starts to derate the drive's regen torque.

The drive trips F30004 DC link overvoltage during deceleration. What is the most common cause?

The most common cause on FSG is an external chopper that is wired correctly but not configured in the drive. Without p1230[0] = 0 and the Vdc controller enabled, the drive has no awareness of the chopper and the bus rises past 800 V DC during regen. Set p1240[0] = 1 to enable the Vdc controller, verify the external chopper threshold is set below 800 V DC, and confirm the chopper fault contact is mapped via p2100 so F06902 trips before the IGBT bridge does.

How do I confirm the chopper is regulating correctly during a controlled braking test?

Use the trace tool in Startdrive or STARTER to record r0027 (DC link voltage), r1238[0] (chopper current), and r1239[0] (chopper status word) during a fast stop from a known speed. The expected profile is: r0027 rises to p1231 ± 5 V (774 V for 400 V class), r1239[0] bit 0 transitions from 0 to 1, and r1238[0] shows a pulsed current up to the chopper's rated current (185 A for the user's 100 kW unit). After the stop, r1238[0] should return to 0 A and the resistor temperature should begin to fall. No F06901, F06902, or F30004 codes should be logged.

Back to blog