SINAMICS G120C Setpoint Not Reached: p0640 Current Limit Fix

David Krause19 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Description

A SINAMICS G120C compact inverter driving a 1.8 kW, 400 V, 3.5 A, 60 Hz, 1750 rpm squirrel-cage induction motor in a Bitzer CO2 refrigeration compressor fails to reach its commanded speed setpoint. The drive current saturates at the motor current limit (p0640[0] = 5.25 A, equivalent to 1.5 × motor rated current) and the motor runs at approximately 18 % of rated speed (≈315 rpm). At this reduced speed the self-ventilated motor cannot dissipate the I²R losses, the I²t motor model trips an overtemperature fault (F30011), and the compressor never reaches the process setpoint. Raising p0640[0] above 1.5 × FLA restores normal acceleration. The same root cause and remedy apply symmetrically to both inverters when the two compressors operate in parallel and one is pressurising the common suction header before the second starts.

Key symptom: Drive current clamped to p0640[0], actual speed flat-lining at 18 % of setpoint, motor thermal overload (F30011) within seconds of start, fault clears only after the motor has been off-loaded.
Parameter-naming note: The original incident post lists p640[0]. On the SINAMICS G120C the canonical parameter is p0640[0] (motor current limit, indexed by Drive Data Set). The leading zero is part of the parameter number. This article uses p0640[0] throughout.

Affected Hardware and Configuration

The reported configuration consists of two identical SINAMICS G120C drives wired in a star (Y) motor configuration with the following nameplate and commissioning data:

Item Value Source / Note
Drive SINAMICS G120C, 3 AC 400 V, 3 kW frame (e.g., 6SL3210-1KE21-7AF1) Frame supports motor FLA up to ≈7.3 A at 400 V
Motor type 3-phase squirrel-cage induction, Y-connected Nameplate
Motor rated power 1.8 kW p0307 = 1.80
Motor rated voltage 400 V p0304 = 400
Motor rated current 3.5 A p0305 = 3.50
Motor rated frequency 60 Hz p0310 = 60
Motor rated speed 1750 rpm p0311 = 1750
Power factor 0.78–0.82 typical for 1.8 kW 4-pole p0308 (calculated by quick commissioning)
Compressor Bitzer CO2 (R-744) reciprocating compressor Application
Current limit 5.25 A (1.5 × p0305) p0640[0] = 5.25
Number of drives 2 (parallel compressors) Topology

The published SINAMICS G120C Operating Instructions (09/2017 edition) document the relationship between p0305, p0640[0] and the drive's I²t protection, and confirm that the G120C delivers up to 150 % rated motor current for 60 s and 200 % for 3 s before the I²t power-unit model intervenes (F30005).

Root Cause Analysis: Current Limit vs. Load Torque Envelope

The drive did not reach the speed setpoint because the available torque at the current limit was insufficient to overcome the load torque at the operating point. Two physics-driven constraints apply:

  1. Current-limited torque ceiling. For a given flux (set by V/Hz in open-loop V/f mode or by the magnetising current in SLVC), motor torque is approximately linear in stator current. Clamping current to 5.25 A in a 3.5 A motor caps steady-state torque at roughly 1.5 × rated torque. A Bitzer CO2 compressor starting against a pressurised suction header (≈18–25 bar in subcritical CO2 plants) typically demands 4–6 × rated torque during the first 1–3 s. The required current would therefore be 14–21 A, but the drive is allowed to deliver only 5.25 A.
  2. Stall at 18 % speed. With current at the limit and slip at maximum, the motor's torque curve intersects the load curve at a very low speed. The V/Hz profile produces 0.18 × 60 Hz ≈ 11 Hz of stator frequency, but the rotor cannot follow and slip remains saturated. Shaft power (P = T × ω) collapses to 0.18 of the value achievable at full speed, exactly matching the 18 % shaft power reported.

The thermal consequence is unavoidable: a 1.5 × FLA stator current in a self-ventilated TEFC motor at 18 % speed is dissipating ≈2.25 × rated I²R while moving ≈18 % of rated air through the frame. The motor's I²t time constant (model parameter p0611, default 100 s for a 1.8 kW motor) is consumed in approximately:

t ≈ p0611 × [1 − p0305² / I²actual]⁻¹ ≈ 100 / (2.25 − 1) ≈ 80 s to F30011 trip

This is consistent with the original report: the motor heats up and displays an overtemperature error within a minute or two of being commanded to start.

Diagnostic Parameters and Live Read Values

Connect to the drive via the BOP-2 (basic operator panel), IOP-2 (intelligent operator panel), or Startdrive / STARTER over PROFINET, USS, Modbus RTU, or USB. Capture the following read-only parameters with the drive running and the speed setpoint at 1750 rpm:

Parameter Description Expected (faulty) Expected (corrected)
r0021 Speed actual value (rpm) ≈315 (18 % of 1750) ≈1750
r0024 Output frequency (Hz) ≈11 ≈60
r0027 Current actual value (A) 5.25 (= p0640[0]) 2.5–3.5 under load
r0031 Torque actual value (Nm) Below load torque Equal to load torque
r0032 Active power (kW) ≈0.18 × rated ≈1.8 (rated)
r0034 Motor I²t utilisation (%) Rising rapidly → 100 % < 100 %
r0046.4 Status word 2, bit "Current limit reached" = 1 = 0
r0052.3 Status word 1, bit "Fault active" = 1 (F30011) = 0

If r0027 pegs at 5.25 A while r0021 stalls and r0046 bit 4 = "1", the current limit is the active restraint and the corrective action below applies. If r0027 shows a value well below p0640[0] but r0021 still stalls, the restraint is mechanical (compressor seized, jammed suction valve, liquid slug) and p0640[0] alone will not help.

Safety note: Reading r0027 / r0021 at the panel is non-intrusive. Do not bypass the drive's I²t model (p0612) as a way to silence F30011 — the model is protecting the motor and the thermal time constant is real.

Resolution: Raising p0640[0] for Starting Torque Headroom

The remedy is to raise p0640[0] so the drive can deliver the brief, high current required to accelerate the compressor. A value of 2.0–3.0 × p0305 (7.0–10.5 A in this installation) is typical for subcritical CO2 compressor duty. The drive's own I²t model and overload ratings will still bound sustained current and trip on genuine faults.

  1. Confirm drive sizing. Verify that the drive is rated to deliver the new current continuously. For a G120C 3 kW frame (rated output ≈7.3 A at 400 V), setting p0640[0] = 10.5 A is allowed because the drive will only sustain 1.5 × 7.3 = 10.95 A for 60 s, after which F30005 will trip if the overload is not cleared. Read r0209 to confirm the absolute ceiling of the power unit in the field.
  2. Enter commissioning mode. On the BOP-2 navigate to the parameter menu, or in Startdrive / STARTER open the drive offline/online project. Set access level to "Expert" (p0003 = 3) to expose p0640[0] directly. Set p0010 = 1 (Quick Commissioning) only if a full reset is required; otherwise leave p0010 = 0 and write p0640[0] in run state.
  3. Read p0305 baseline. Note p0305 = 3.50 A. Calculate the new limit as 2.5 × p0305 = 8.75 A. This is the recommended starting point for a 1.8 kW CO2 compressor on a 3 kW drive; 3.0 × p0305 (10.5 A) gives additional headroom for cold-start cases.
  4. Write p0640[0]. Set p0640[0] = 8.75 (or 10.50 for headroom). Save to RAM only first (p0971 = 1) for a live test, then copy RAM to ROM (p0977 = 1) once the test passes.
  5. Confirm the maximum current limit ceiling. The SINAMICS firmware will accept p0640[0] values up to the drive's "max current" (typically 2 × Irated,inv). A setting above 14.6 A on a 7.3 A drive will be silently clamped by the firmware — read r0209 (rated power-unit current) to confirm the absolute ceiling.
  6. Re-run the start sequence. With the compressor off-loaded (or with both compressor suction valves open to a vented receiver), command the setpoint and observe r0021, r0027, r0034. r0021 should rise to 1750 rpm within the ramp time (p1120), r0027 should peak at ≈8.75 A for ≈1–2 s and then decay to 2.5–3.5 A.
  7. Test the on-load start. With the second compressor running and the common suction header pressurised to operating pressure, command the corrected drive to start. Confirm r0021 still reaches 1750 rpm, r0027 peaks below 10.5 A, and r0034 stays under 80 %.
  8. Lock the parameters. Run "Copy RAM to ROM" (p0977 = 1) so the value survives a power cycle. Reset any active F30011 fault with the OFF1-OFF2-ON sequence or via the panel / PLC.

For installations requiring different starting behaviours (e.g., unload compressor before start, soft-loading the second machine), the current limit can be kept at a moderate value and a pre-opening suction bypass valve can be sequenced in the PLC, but raising p0640[0] is the lowest-effort and most robust fix.

Verification and Commissioning Checks

  1. Steady-state current. With the compressor running at 1750 rpm and process setpoint achieved, r0027 should be 60–80 % of p0305 (≈2.1–2.8 A in this case). If r0027 sits at >90 % of p0305 indefinitely, the load is heavier than expected — re-check p0304 / p0305 / p0310 / p0311 against the motor nameplate and re-run motor identification (p1900 = 2 for rotating measurement).
  2. Acceleration envelope. Capture r0024 (frequency) during a start from 0 to 60 Hz. The frequency should rise linearly with the ramp (p1120 = 10 s default) and reach 60 Hz at the end of the ramp. Any plateau at low frequency indicates a torque / current limitation.
  3. Thermal model headroom. r0034 (motor I²t utilisation) must stay < 100 % continuously. A reading > 90 % after a start indicates the I²t model is being saturated — either the current limit is set too low (motor takes too long to accelerate) or the load is genuinely too large for the drive.
  4. Fault log. Read the drive's fault buffer (r0945 / r0947 / r0949) and history (r0950). Confirm F30005 (power unit I²t) and F30011 (motor I²t) are absent after a full duty cycle.
  5. Off-load vs. on-load start. Repeat the test with the suction valve closed (off-load) and open (on-load). The corrected p0640[0] value must succeed in both cases. A 2.5 × p0305 setting is generally sufficient; if the on-load start still stalls, the compressor's starting torque demand exceeds the drive's peak current capability and a larger drive is required.
  6. PLC cross-check. If the compressor is controlled by an S7-1200 / S7-1500 over PROFINET, verify in the PLC trace that the drive word PZD2 (current / torque feedback) tracks the setpoint word PZD1 (speed setpoint) during the start. A constant PZD2 with a rising PZD1 confirms the drive is in current limit.

Related Fault and Alarm Codes

The G120C fault and alarm register includes several codes that interact with the current-limit / motor-thermal subsystem. Review each during commissioning:

Code Class Meaning Typical cause
F30005 Fault Power unit I²t overload (drive IGBT / heatsink model) Drive output current above 1.5 × Irated,inv for > 60 s, or > 2 × for > 3 s
F30011 Fault Motor I²t model overload (model-based) Motor current above 1.5 × p0305 with poor cooling (low speed, stalled, blocked rotor)
F30021 Fault Power unit overtemperature (sensor) Heatsink sensor trip; ambient too high, fan failure
F07900 Fault Motor blocked (SLVC only) Detected by sensorless vector model (p1300 = 20 / 22); check r0046 bit 13
A30001 Alarm Power unit I²t warning (pre-fault) Drive is approaching F30005; reduce load or raise p0640[0] only with care
A30015 Alarm Motor I²t warning Pre-fault for F30011; motor is heating
A5091 Alarm Motor temperature sensor warning (PTC / KTY / PT1000) Sensor configured (p0601 ≠ 0) and threshold exceeded
A7901 Alarm Motor speed overshoot p0640[0] set excessively high with no torque limit; load inertia overshoots setpoint
Important: F30011 is a model-based trip and does not require a temperature sensor in the motor. If a PTC, KTY84 or PT1000 sensor is wired to the G120C (via terminals X521.1 / X521.2 on the Control Unit), set p0601 to the matching value (1, 2 or 4) and p0604 / p0605 to the alarm / trip thresholds. With no sensor fitted, leave p0601 = 0 so the I²t model is the only protection.

Compressor-Specific Load Considerations

Reciprocating refrigeration compressors — and CO2 compressors in particular — are torque-dense, high-inertia loads with very different starting profiles from fans, pumps or conveyors:

  1. Locked-rotor torque. Bitzer specifies 2.5–3.5 × rated torque for the LRT of standard 4-pole CO2 compressors, rising to 4–6 × for the heaviest models. This is the torque the drive must deliver in the first 0.5–2 s.
  2. Breakaway torque. CO2 compressors with oil in the crankcase and refrigerant dissolved in the oil may exhibit a static breakaway torque of 4 × FLA, especially in cold installations. Crankcase heaters reduce this, but the drive must still be sized for the worst case.
  3. Suction header back-pressure. In a parallel compressor bank, the second compressor starts against the discharge of the running machine. Subcritical CO2 suction is typically 20–40 bar(g) for low-temperature refrigeration, and discharge-side pressures of 80–100 bar are possible. The torque required to pull suction and compress to discharge is 3–5 × rated. Starting the second compressor "off-load" (suction valve closed) reduces this to 1.5–2 × rated but is rarely practical in a refrigeration process — the suction valve is the process control element.
  4. Discharge valve unloading. Some Bitzer models (e.g., 4FC-3, 4GE-30 series) include capacity-control unloaders that hold the suction valves open during start. If present, the PLC should energise the unloader first, command the drive, and release the unloader only after r0021 = setpoint.
  5. Soft-starter vs. inverter start. Across-the-line starting of a 1.8 kW compressor inrushes 6–8 × FLA from the supply, which is acceptable for a single compressor but causes unacceptable voltage dip when two start in parallel. An inverter with adequate p0640[0] headroom limits inrush to ≈3 × FLA and the supply dip is contained.
  6. Crankcase heater interlock. Permit a drive start only when the crankcase-heater contact is closed (pump-down / cold-cycle protection) — CO2 refrigerant in liquid form entering the suction port is a primary cause of catastrophic liquid slugging and p0640[0] cannot save the compressor from that.

For a CO2 compressor, the recommended V/f mode is p1300 = 0 (linear V/f) with elevated starting boost (p1310 = 50–80 %, p1311 = 30–50 %). Sensorless vector control (p1300 = 20) provides higher starting torque and tighter speed regulation, but requires a one-time motor identification (p1900 = 2) and is sensitive to stator resistance drift (motor warm vs. cold). For a 1.8 kW compressor on a 3 kW drive, V/f with boost is the conservative choice; SLVC is preferable if the compressor has a high load-shock profile (e.g., cycling between loaded and unloaded).

Parameter Reference and Defaults

The following parameters govern motor data, current limit, and thermal protection on the SINAMICS G120C. The "Default" column shows the factory value; check the active value with the panel or Startdrive because commissioning tools frequently overwrite defaults during quick commissioning.

Parameter Description Default Range / Unit
p0003 User access level 1 (Standard) 1–4 (Expert)
p0010 Commissioning parameter filter 0 (Ready) 0–30
p0100 Europe / North America (50 / 60 Hz) 0 (Europe, kW) 0–2
r0209 Rated power unit current (drive-dependent) read-only [A]
p0304 Motor rated voltage 0 10–2000 [V]
p0305 Motor rated current 0 0.01–65535 [A]
p0307 Motor rated power 0 0.01–2000 [kW]
p0308 Motor rated power factor cos φ 0 0.000–1.000
p0310 Motor rated frequency 0 0–650 [Hz]
p0311 Motor rated speed 0 0–40000 [rpm]
p0314 Motor pole pair number 0 0–255
p0335 Motor cooling (0 = self, 1 = forced) 0 0–1
p0601 Motor temperature sensor type 0 (none) 0–14
p0611 Motor I²t thermal time constant 100 (calc from p0307) 0–65535 [s]
p0612 Motor thermal model configuration 2 (I²t + sensor) 0–3
p0625 Motor ambient temperature 20 −40 to 80 [°C]
p0626 Motor overtemperature, stator iron 80 20–200 [K]
p0627 Motor overtemperature, stator winding 80 20–200 [K]
p0628 Motor overtemperature, rotor 100 20–200 [K]
p0640[0] Current limit (motor) 0 (= 1.5 × p0305) 0 to r0209 × 2 [A]
p1080 Minimum speed 0 0–65535 [rpm]
p1082 Maximum speed 1500 0–65535 [rpm]
p1120 Ramp-up time 10 0–650 [s]
p1121 Ramp-down time 10 0–650 [s]
p1300 Open / closed-loop control mode 0 (V/f linear) 0–22
p1310 Voltage boost at low frequency 50 0–250 [%]
p1311 Voltage boost during acceleration 0 0–250 [%]
p1520 Upper torque limit (SLVC only) [Nm]
p1521 Lower torque limit (SLVC only) [Nm]
p1900 Motor data identification 0 0–2
r0021 Speed actual value read-only [rpm]
r0024 Output frequency read-only [Hz]
r0027 Current actual value read-only [A]
r0031 Torque actual value read-only [Nm]
r0032 Active power read-only [kW]
r0034 Motor I²t utilisation read-only [%]
r0046 Status word 2 (bit 4 = current limit reached) read-only

The default value of p0640[0] = 0 is interpreted by the firmware as "use 1.5 × p0305". When the value is non-zero, the firmware uses the written value as the absolute ceiling, in amperes. If a commissioning tool has written 5.25 explicitly, raising the value is the only way to get more headroom.

Best Practices for Parallel Compressor Installations

  1. Size p0640[0] for the on-load case. Set p0640[0] to the maximum current the drive can deliver within its overload rating (1.5 × r0209 for 60 s or 2.0 × r0209 for 3 s), not to a "comfortable" 1.5 × FLA. Compressor inrush against back-pressure can briefly demand up to 2.5 × FLA; sizing for 1.5 × leaves no headroom.
  2. Pre-spin the second compressor. Open the suction valve of the second compressor to atmospheric pressure before commanding the start, then close it once r0021 = setpoint. This reduces the inrush torque from 4–6 × rated to ≈1.5 × rated and makes the start robust with p0640[0] = 1.5 × p0305. The PLC interlock is straightforward.
  3. Sequence the start. Always start the second compressor at least 5 s after the first has stabilised. Back-pressure ramps in 1–3 s after the first compressor starts, and a delayed start lets the discharge pressure equalise.
  4. Monitor r0034 in the PLC. The motor I²t utilisation is a high-resolution, model-based signal that anticipates F30011 by 10–30 s. Trending r0034 over the start cycle is the cleanest way to verify p0640[0] is correctly sized.
  5. Run motor identification on both drives. After commissioning p0304–p0311, run p1900 = 2 (rotating identification) on each drive. The motor data is re-measured at standstill and at 50 % of rated speed, which calibrates the I²t model, the SLVC torque model (if used), and the stator resistance compensation. A drive that has only been quick-commissioned (p0010 = 1) has default motor data, which is conservative for stator current and over-conservative for I²t headroom.
  6. Keep p0601 = 0 for IEC motors without sensors. If the motor has no temperature sensor, leave p0601 = 0. Setting p0601 to a sensor type without a sensor wired will cause a sensor-open-circuit fault at every start.
  7. Log r0027 in the historian. A 1-second sample of r0027 during a start gives a permanent record of the inrush profile. Comparing two consecutive starts on the same drive will detect bearing wear, suction valve leakage, or refrigerant overcharge long before they become field failures.
  8. Re-check the second drive as well. The original report states the problem occurs on both G120C inverters. The most likely reason is that both were commissioned with the same conservative p0640[0] = 1.5 × p0305 default. Apply the fix to both drives, run motor identification on each, and document the final p0640[0] value in the plant asset record.

Following the steps above, the original symptom of "motor runs at 18 % speed, heats up, and trips overtemperature" is fully explained: the drive is delivering the maximum 5.25 A allowed by p0640[0] but the compressor's on-load starting torque exceeds what 5.25 A can produce at 11 Hz. Raising p0640[0] to 2.5–3.0 × p0305 allows the drive to deliver 8.75–10.5 A for the 1–2 s required to accelerate the compressor, after which the motor speed, airflow and thermal dissipation all normalise.

FAQ

Why is the SINAMICS G120C only reaching 18 % of setpoint on a 1.8 kW motor?

The drive is hitting the motor current limit p0640[0] (5.25 A, or 1.5 × 3.5 A FLA) before the motor can accelerate to setpoint. On a CO2 compressor starting against a pressurised suction header the load torque is 4–6 × rated, demanding 14–21 A. The current clamp forces the motor to its torque ceiling, and the slip-speed operating point falls to ≈18 % of rated speed (315 rpm). Raise p0640[0] to 2.5–3.0 × p0305 (8.75–10.5 A) to give the drive the headroom needed for the 1–2 s acceleration.

What is the difference between p0640[0] and p1520 / p1521?

p0640[0] is the absolute stator current limit in amperes, applied in all control modes. p1520 and p1521 are the upper and lower torque limits in newton-metres, applied only in sensorless vector control (p1300 = 20 or 22). In V/f mode (p1300 = 0 / 1 / 2) the torque limit is implicit and is reached first through p0640[0]. For a CO2 compressor in V/f, only p0640[0] is relevant; in SLVC you must also set p1520 / p1521 high enough to deliver starting torque.

Will raising p0640[0] trip F30005 (power-unit I²t) on a 3 kW G120C?

No, provided p0640[0] stays within the drive's overload envelope. A 3 kW G120C frame (r0209 ≈ 7.3 A at 400 V) supports 1.5 × 7.3 = 10.95 A for 60 s and 2.0 × 7.3 = 14.6 A for 3 s. Setting p0640[0] = 10.5 A gives 1.44 × r0209, well inside the 60 s envelope. F30005 will still trip if a real overload persists (e.g., the compressor is mechanically jammed), which is the desired behaviour.

Why does the motor overheat at 18 % speed even though the current is only 1.5 × FLA?

A self-ventilated (TEFC) induction motor at 18 % speed moves ≈18 % of rated cooling air through the frame. With 1.5 × FLA current the I²R losses are ≈2.25 × rated, so the motor is generating heat faster than it can dissipate it. The drive's I²t model (p0611 ≈ 100 s) trips F30011 in roughly 80 s. Raising p0640[0] to 2.5–3 × FLA allows the motor to accelerate to full speed within 1–2 s, after which airflow returns to normal and the I²t model headroom is restored.

Can the same p0640[0] be set differently for the two parallel compressors?

Yes. The G120C supports multiple Drive Data Sets (DDS), and p0640 is indexed p0640[0…n]. Each DDS can be tied to a different control source (digital inputs, fieldbus, fixed setpoint). In a parallel-compressor application with identical motors, however, all DDSs are normally configured identically and the same p0640[0] applies to all starts. If the two compressors have different process duties (e.g., one is a trim / standby unit that starts more often), set p0640[0] in each DDS to match the worst-case starting torque of that compressor.

Back to blog