SINAMICS S120 1FT6132 Encoder Exchange: Drive-CLiQ vs EnDat M24

David Krause20 min read
Motion ControlSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Definition: 1FT6132 Encoder Variant Mismatch

The 1FT6132 is a member of the Siemens SIMOTICS S 1FT6 family of brushless permanent-magnet synchronous servomotors. It is offered in two mechanically identical variants that differ only in the encoder interface electronics. The -4FA1 MLFB suffix designates a motor whose absolute encoder is terminated inside the motor junction box as a DRIVE-CLiQ signal pair; the -4EA1 suffix designates the same motor whose absolute encoder is terminated in an M24 18-pin flange connector using the Heidenhain EnDat 2.1/2.2 protocol. The two motors share the same stator, winding, bearings, and tapered encoder shaft; only the encoder electronics and the connector at the rear of the motor differ.

On the SINAMICS S120 Book Size platform, the -4FA1 variant connects directly to a DRIVE-CLiQ port on the Motor Module or on a hub. The -4EA1 variant cannot connect directly to a DRIVE-CLiQ port because EnDat M24 uses a 17-pin (or 18-pin) M24 connector with 5 V power and differential EnDat clock/data, not the 8-pin DRIVE-CLiQ RJ45-style interface. The -4EA1 motor requires a Sensor Module - SMC20 (cabinet-mounted) or SME20 (external-mounted) - which translates the EnDat stream into the SINAMICS encoder channel format and re-injects it on the DRIVE-CLiQ network.

When a -4FA1 unit fails in service and the only spare available is a -4EA1 unit, the field question is whether the encoder can be transferred from one motor to the other so that the original motor continues to operate on the existing SINAMICS S120 topology. The mechanical, electrical, parameter, and firmware implications of such a transfer are documented below, together with the supported engineering options when a direct encoder swap is not viable.

Engineering note. The -4FA1 and -4EA1 motors are not field-interchangeable at the encoder level. The supported engineering response to a stock mismatch is to adapt the topology (add an SMC20) or to order the correct replacement MLFB through Siemens ASP&A.

1FT6132 Family and Encoder Options

The 1FT6132 belongs to the 132 mm shaft-height segment of the 1FT6 family, with a 192 mm IEC flange and a 6-length (longer) stack. The MLFB structure common to both the -4FA1 and -4EA1 motors is given in the table below. Option code definitions can be revised across catalog editions; verify the option code for the specific motor against the rating plate and the Siemens Product Configurator at siemens.com/Configurator.

MLFB field Value (both variants) Meaning
Series 1FT6 SIMOTICS S permanent-magnet synchronous servomotor, sinusoidal EMF
Shaft height 132 132 mm shaft height, 192 mm IEC flange
Stack length 6 Length code 6 (long stack, higher continuous torque)
Winding S Winding speed code S (per datasheet, 2000-3000 rpm rated region)
Cooling C Forced ventilation via integrated radial blower
Shaft / brake 7 Plain shaft with feather key, no holding brake
Encoder 1 Absolute encoder (typical: 22-bit singleturn or 22-bit + 12-bit multiturn)
Connector family 4 Connector family code (see option list)

The trailing F or E option code in the MLFB defines the encoder interface. The F variant is a Siemens-format DRIVE-CLiQ encoder with 24 V supply and a Siemens electronic rating plate; the E variant is a Heidenhain EnDat M24 encoder with 5 V supply and a Heidenhain catalog number. The two encoders are mechanically interchangeable on the motor but electrically, electronically, and parametrically distinct.

Mechanical Compatibility of the Encoder Mounting

The 1FT6 family uses a tapered (1:10) encoder shaft of standard dimensions across the entire 1FT6 catalog. Both the F (DRIVE-CLiQ) and E (EnDat) option code encoders mount on the same taper and are clamped with the same central screw. The encoder housing O-ring seal and the motor-side mounting flange are identical.

Three mechanical limits apply when a field swap is considered:

  1. Encoder housing diameter and length are identical between the two variants, so no interference occurs in the motor housing.
  2. Encoder central screw: use the Siemens-specified torque value from the 1FT6 installation guide (typically around 5 Nm for the central clamping screw; verify against the 1FT6 Commissioning Guide for the exact value). Do not reuse a screw that has been removed and reinstalled more times than the catalog allows; check the encoder installation manual for the screw-reuse count.
  3. Cable entry and routing: the E variant routes a heavier M24 cable to the SMC20; the F variant uses a 6FX8002 DRIVE-CLiQ cable with a much smaller bend radius. Cable bend radius and EMC separation from the motor power cable must be respected in either configuration.

Electrical Interface: DRIVE-CLiQ vs EnDat M24

The two encoders are electrically incompatible at the connector level. The relevant differences are summarized below.

Interface Connector Power on cable Data lines Cable
DRIVE-CLiQ (F) RJ45-style, 8 pins, IP67 24 V supply + GND, supplied by the SINAMICS Differential serial, full-duplex, 100 Mbit/s 6FX8002-2DCxx-xxxx prefab, up to 100 m, minimum bend radius 75 mm
EnDat M24 (E) M24 17-pin (or 18-pin) flange connector per Heidenhain 5 V ± 5 % regulated, from SMC20/SME20 Differential EnDat clock and data, RS-485 Heidenhain or Siemens extension cable, shield terminated at SMC20; 5 V drop must be checked

A -4EA1 motor cannot be plugged directly into a SINAMICS S120 DRIVE-CLiQ port. It must first connect to an SMC20 or SME20 Sensor Module, which converts the EnDat stream into the SINAMICS encoder channel format. The 5 V supply on the EnDat cable is critical: the cable resistance between SMC20 and the encoder must be checked against the Heidenhain EnDat specification to ensure that the supply at the encoder terminals remains within ±5 % of nominal. Long motor-to-cabinet distances require a 5 V sense return or an encoder with extended supply range; verify with the Heidenhain EnDat 2.1/2.2 manual and the SMC20 manual.

SINAMICS S120 Topology with DRIVE-CLiQ

The SINAMICS S120 Book Size drive system uses a DRIVE-CLiQ ring or star topology. The Control Unit CU320-2 has six DRIVE-CLiQ ports (X100-X105) on its front panel, and each Motor Module Book Size has two DRIVE-CLiQ ports (X200, X201) on its front panel. The encoder is normally connected to the Motor Module X200 port of the drive that controls the motor.

A direct DRIVE-CLiQ encoder (F variant) is a single-cable, single-port solution. An EnDat encoder (E variant) is a two-cable solution: a power/signal cable from the motor M24 connector to the SMC20, and a DRIVE-CLiQ cable from the SMC20 to the Motor Module or to a DMC20 hub in the topology. The SMC20 occupies one DRIVE-CLiQ address on the network and must be considered in the topology when calculating the maximum number of nodes per Control Unit.

CU320-2 supports a maximum of 8 drive objects (depending on firmware) and 24 DRIVE-CLiQ nodes; the Sensor Module consumes one slot in the topology. The DO list and topology should be checked after adding the SMC20 to confirm that the system stays within its limits. The Hub Module DMC20 is required when more than six axis drives are connected and the topology is converted to a star, or when an encoder must connect to a port that is not on a Motor Module - the latter is the typical SMC20 installation.

Parameter Mapping: Replacing a DRIVE-CLiQ Encoder with an SMC20 + EnDat

When the encoder channel is moved from a direct DRIVE-CLiQ connection to an SMC20 + EnDat, the drive object parameters must be updated so that the SINAMICS reads the encoder data through the Sensor Module channel. The relevant parameters are summarized below.

Parameter DRIVE-CLiQ encoder (F) on Motor Module X200 EnDat M24 encoder (E) on SMC20 Notes
p0140 n.def. (encoder on MM) Number of encoder interfaces in the topology For a separate SMC20, p0140 lists it as a drive object on its own
p0141 n.def. Encoder interface component number (e.g. 1 for SMC20 on its own DO) Set to the index of the SMC20 drive object
p0142 n.def. Component number of the Sensor Module Auto-set by topology
p0400[0] 9999 (DRIVE-CLiQ encoder auto-detected) 9999 (auto-detected by SMC20 for EnDat) Leave at 9999 for auto-detect; change only for explicit assignment
p0401 DRIVE-CLiQ encoder type EnDat encoder type Auto-set from electronic rating plate
p0420[0] Encoder catalog number Encoder catalog number Auto-set from electronic rating plate on DRIVE-CLiQ; for EnDat the catalog number is read from the encoder EEPROM via the SMC20
p0421[0] Multiturn resolution in bits Multiturn resolution in bits Auto-set; verify after topology identification
p0423[0] Singleturn resolution in bits Singleturn resolution in bits Auto-set
p0430[0] 9999 (no sensor module) Index of the Sensor Module drive object (e.g. 2 or 3) This is the parameter that assigns the encoder to the Sensor Module channel instead of the Motor Module direct channel
p0431[0] 9999 (no SSI baud rate) 9999 (EnDat uses SMC20 internally) Set to 9999 for EnDat
p0437[0] 9999 (DRIVE-CLiQ reads from electronic rating plate) 0 (EnDat data is read by SMC20 from encoder EEPROM, no Siemens-issued rating plate) Configure to enable diagnostics on the Sensor Module channel

The key parameter change is p0430[0], which routes the encoder evaluation to the Sensor Module drive object. After changing p0430, copy RAM to ROM and power-cycle the Control Unit to clear the parameter consistency check.

Encoder Exchange Procedure

The procedure below covers the case where a -4EA1 (EnDat M24) motor is to be used in a system that was configured for a -4FA1 (DRIVE-CLiQ) motor. The reverse case is symmetric.

  1. Lock and tag out the drive system; verify zero energy at the Motor Module DC link before any mechanical work. Wait 5 minutes after isolation for the DC link capacitors to discharge to safe voltage per the SINAMICS S120 manual.
  2. Document the existing configuration: motor MLFB, encoder type, electronic rating plate contents (drive p0100...p0199 and r0200...r0206), and the encoder evaluation parameters. Save the active drive project from STARTER or Startdrive as a backup, and export the parameter list to a CSV file. Note the DRIVE-CLiQ port on the Motor Module (typically X200) and label the cable.
  3. Disconnect the DRIVE-CLiQ cable from the original motor at the motor side. Cap the connector to prevent contamination.
  4. Install the SMC20 in the cabinet. Mount on a DIN rail or on a flat surface in accordance with the SMC20 manual. Observe the EMC mounting guidelines: bond the SMC20 body to the cabinet backplane with a low-impedance bond (paint-free contact surface, short bonding strap).
  5. Lay a Heidenhain or Siemens extension cable from the motor M24 connector to the SMC20. Terminate the shield on the SMC20 end with a 360° EMC gland; terminate the motor end on the connector shell. Verify the 5 V supply at the encoder end with a multimeter after power-up.
  6. Lay a DRIVE-CLiQ cable (6FX8002-2DCxx-xxxx) from the SMC20 to the Motor Module X200 port or to a DMC20 port. The cable is now on the DRIVE-CLiQ network and the SMC20 will be auto-detected on the next topology identification.
  7. Power up the Control Unit and the Motor Module. Open STARTER or Startdrive and call "Topology → Identify" (STARTER) or "Topology → Read in" (Startdrive). Confirm that the new SMC20 appears in the topology and that the Motor Module sees the EnDat encoder through the Sensor Module channel.
  8. Configure encoder parameters on the drive object: set p0430[0] to the index of the SMC20 drive object, set p0437[0] as needed for diagnostics, and set p0140 if the SMC20 is on a separate drive object. p0140 is automatically set when the topology is identified.
  9. Run automatic configuration and check that the electronic rating plate data is read from the EnDat encoder. Verify that p0420[0], p0421[0], and p0423[0] show the correct resolution.
  10. Save the project to ROM and to the drive. Power-cycle the Control Unit. After the power-cycle, the SINAMICS will read the EnDat encoder data through the SMC20 and the Motor Module will treat it as encoder 1.
  11. Run encoder commissioning: commutating-angle test (p1990 = 1) and, if required, a pole-position identification. The 1FT6 motor has a calibrated absolute encoder, so the commutation angle is read from the encoder and a test run is verification only; however, run p1990 to confirm.
  12. Run a low-speed reference motion at e.g. 50 rpm and confirm with the STARTER/Startdrive trace tool that the actual speed (r0063) and the position actual value (r0481) track the setpoint.
  13. Run a controlled stop and a high-speed test motion within the system speed limits. Verify that no fault F3x, F4x, or F2xxx appears in the fault buffer.

The SMC20 firmware is part of the SINAMICS S120 firmware bundle; no separate firmware update is required. The DRIVE-CLiQ version on the SMC20 should match the version required by the SINAMICS firmware; mismatched versions can result in F01360 (DRIVE-CLiQ component version mismatch) during topology identification. The 1FT6 family is supported by SINAMICS S120 firmware V4.4 and later, and STARTER V4.x or Startdrive V15 in TIA Portal is the commissioning tool. The Siemens Industry Online Support portal is the source for the current firmware bundles and the S120 commissioning manual.

Drive-CLiQ Cable, Connector, and Topology Constraints

A 6FX8002-2DCxx-xxxx prefab DRIVE-CLiQ cable is required between the SMC20 and the Motor Module or hub. The cable is a Cat5e-equivalent, 8-core, shielded, with an RJ45-style industrial plug on each end. Available lengths are 0.5 m, 1 m, 2 m, 3 m, 5 m, 8 m, 10 m, 12 m, 15 m, 20 m, 25 m, 30 m, 40 m, 50 m, 75 m, and 100 m. The minimum bend radius is 75 mm in fixed routing and 125 mm in flexible routing. The cable transmits DRIVE-CLiQ at 100 Mbit/s and the 24 V supply for downstream devices. The total length of all DRIVE-CLiQ cables in a CU320-2 ring is limited to 350 m.

For the EnDat M24 cable between the motor and the SMC20, the Siemens M24 extension cable (e.g. 6FX8002-2EAxx-xxxx for EnDat 2.1/2.2) is recommended. The cable has a 17-pin M24 connector on the motor end and a 17-pin M24 connector on the cabinet end (or a D-sub connector that adapts to the SMC20). For long cable runs, confirm the 5 V drop on the power pair using the cable resistance table in the Heidenhain EnDat specification; the typical 5 V supply is regulated inside the SMC20.

The DMC20 (DRIVE-CLiQ Hub Module Cabinet-Mounted 20) is required when the topology has more than six axis drives on a single CU320-2 or when the SMC20 is mounted far from the Motor Module. The DMC20 has 6 DRIVE-CLiQ ports and is used in a star layout. When inserting an SMC20 into an existing ring, the topology must be re-identified.

Fault Codes and Diagnostics

When the encoder is reconnected through the SMC20, the SINAMICS may report one or more of the faults below. The fault number prefix F3x is for encoder faults; the 3 in 3x indicates the encoder number. A 1FT6 motor has encoder 1 on the drive object, so the fault prefix is F31xxx. The actual fault text is on the drive parameter description in STARTER or Startdrive.

Fault / warning Meaning Typical cause in this scenario First action
F01360 DRIVE-CLiQ component version mismatch Sensor Module firmware older than Control Unit Update Sensor Module firmware to the same bundle
F3x117 Encoder hardware error 5 V drop on EnDat cable; encoder cable mis-wired Measure 5 V at the encoder; check pinout
F3x120 Encoder supply fault 5 V supply to encoder out of tolerance Verify cable length and resistance
F3x150 Encoder initialization error Encoder EEPROM read error; EnDat catalog read failed Check EnDat cable clock/data wiring
F31117 Encoder 1 hardware fault EnDat encoder internal error Replace encoder
F31002 Multiturn data invalid Battery buffer missing on multiturn EnDat; encoder power-on sequence issue Verify multiturn battery; check encoder power-on ramp
A3x 0x04xx Encoder warning (signal level, position deviation) EMC issue, cable routing near VFD cable Re-route encoder cable; check shield bonding
F207xxx DRIVE-CLiQ communication error Loose DRIVE-CLiQ connector; cable damage Check connectors; replace cable

Multiturn encoders with 22+12-bit resolution report F31002 if the multiturn data is invalid, often after a power cycle if the encoder battery is missing on battery-buffered multiturn units. Most 1FT6 DRIVE-CLiQ encoders do not use a battery buffer, but Heidenhain EnDat encoders in the E variant may use a buffer for multiturn data. Confirm the encoder order code and the requirement for a buffer battery against the Heidenhain data sheet.

Why the Original Approach of Mechanical Encoder Transfer Fails in Practice

The original question - "Can I exchange the encoder and connection from the new motor with the components from the original" - is mechanically straightforward, but for several reasons it is not a supported field solution:

  1. Calibration of commutation offset. The Heidenhain absolute encoder is calibrated to the rotor during motor manufacture. The commutation offset, the position of the absolute singleturn zero, and (for multiturn) the multiturn reference are stored in the encoder EEPROM and replicated in the Siemens electronic rating plate of the F-variant motor. If the encoder is moved to a different rotor, the offset is no longer correct. Re-calibration requires a Siemens commissioning fixture or a p1990 / p1980 procedure with a pole-position identification. The p1990 procedure is generally not used on 1FT6 because the encoder-motor pairing is guaranteed at the factory.
  2. Siemens electronic rating plate on the F variant. The DRIVE-CLiQ encoder on the -4FA1 motor carries a Siemens-format electronic rating plate that is read on first commissioning. If the encoder from one motor is swapped to another, the electronic rating plate now reports the wrong motor data and the SINAMICS S120 protection limits, Kp/Ki values, and motor equivalent circuit data are no longer correct. The drive could operate but with degraded performance and a loss of safety margin.
  3. Heidenhain catalog number. The E-variant encoder has a Heidenhain catalog number (e.g. ECN 113 or ECN 1325) and an EnDat 2.1 or 2.2 protocol. The F-variant encoder has a Siemens catalog number (e.g. 6FX2001-5xxx) and a Siemens-specific DRIVE-CLiQ interface. The two encoders are not drop-in replacements for each other; they have different connector types, different supply voltages, and different protocols.
  4. Thermal and EMC certification. The 1FT6 family is delivered as a certified motor + encoder pair. Swapping the encoder in the field voids the safety and EMC certification of the motor.

In short, transferring the encoder from one motor to another is mechanically possible but electrically, parametrically, and contractually not supported. The supported approach is to keep the new motor as a complete assembly (encoder + motor) and adapt the rest of the system to match, as described in the section below.

Supported Engineering Alternatives

Given that the in-service motor and the spare motor are physically identical but electrically different at the encoder interface, three supported options exist.

Option 1: Order a Replacement -4FA1 Motor

Order a new 1FT6132-6SC71-4FA1 motor from Siemens with the matching MLFB. The electronic rating plate is pre-loaded with the correct motor data, and the new motor drops into the existing DRIVE-CLiQ topology. This is the recommended path when downtime must be minimized and a long-term spare is required. Contact the local Siemens Industry partner or use the Siemens ASP&A portal to confirm the MLFB and the lead time.

Option 2: Add an SMC20 to the Existing -4EA1 Motor

The -4EA1 motor can be used in a -4FA1 system if an SMC20 (or SME20, SMC30 with EnDat mode, or SMC40 with SSI/EnDat) is added. This is described in the encoder exchange procedure above. The trade-off is a more complex topology and the need for a parameter re-mapping. The topology limit of 24 DRIVE-CLiQ nodes per CU320-2 and the DO limit of 8 per CU320-2 must be respected.

Option 3: Convert the In-Service Drive Configuration

If the drive allows the encoder to be reassigned to encoder 2 (or another free encoder interface), the -4EA1 motor can be used directly. The drive would be configured with p0430[0] for the new SMC20, p0400 set to EnDat 22-bit, and the closed-loop control re-commissioned. This is the cleanest engineering approach when the spare stock is permanent and the machine must continue to operate with the available -4EA1 motor.

Verification and Acceptance Test

After the change, the following verification steps confirm that the system is operating correctly:

  1. Confirm no fault is active in the SINAMICS fault buffer. The fault buffer should be cleared with p3981 = 0 → 1, then 0, after the new commissioning is complete.
  2. Read the encoder actual position in r0481 and the speed actual in r0063; verify that both track the setpoint values r0062 and r0060 in trace mode.
  3. Confirm the encoder type in p0400, the catalog number in p0420, the multiturn resolution in p0421, and the singleturn resolution in p0423.
  4. Run p1990 = 1 (pole-position test) and observe the result. A 1FT6 motor with a calibrated EnDat encoder should not require a re-calibration; the test should pass without an error.
  5. Run a controlled acceleration and deceleration at 50 %, 75 %, and 100 % of the rated motor speed. Monitor the Motor Module DC link current in r0027 and the motor torque in r0080. The current should not exceed the motor rated current on the rating plate.
  6. Run a continuous duty cycle representative of the production duty. Monitor the fault buffer for 24 h to confirm no latent encoder warning reappears.
  7. Save the project to the engineering server and to the drive's CompactFlash card (for SINAMICS S120 with a CU320-2 CF card) so that the configuration is preserved on the next power-up.
Catalog number Description Use case
1FT6132-6SC71-4FA1 1FT6 motor, F option: DRIVE-CLiQ absolute encoder In-service motor or replacement
1FT6132-6SC71-4EA1 1FT6 motor, E option: EnDat M24 absolute encoder Spare in stock
6SL3055-0AA00-5BA2 SMC20 - Sensor Module Cabinet-Mounted for EnDat 2.1/2.2 Required adapter for -4EA1 motor
6SL3055-0AA00-5EA2 SME20 - Sensor Module External for EnDat 2.1/2.2 Alternative to SMC20 for external mounting
6SL3055-0AA00-6AA0 DMC20 - DRIVE-CLiQ Hub Module Star topology or long-distance encoder
6FX8002-2DCxx-xxxx Prefabricated DRIVE-CLiQ cable, lengths 0.5 m to 100 m SMC20 to Motor Module / hub
6FX8002-2EAxx-xxxx Prefabricated EnDat 2.1/2.2 cable with M24 17-pin connectors Motor to SMC20

Confirm the current catalog numbers against the Siemens Product Configurator and the Siemens Industry Online Support portal at the time of order. The SINAMICS S120 Commissioning Manual, the 1FT6 Commissioning Guide, the SMC20 manual, and the Heidenhain EnDat 2.2 Specification (Heidenhain document 297 517-xx) are the primary references for this engineering work.

Frequently Asked Questions

Can I physically swap the encoder between a -4FA1 and a -4EA1 1FT6132 motor?

Mechanically yes, both encoders share the same tapered shaft and housing flange. Functionally no, the DRIVE-CLiQ encoder from a -4FA1 motor has a Siemens electronic rating plate and 24 V interface that is matched to that specific rotor, and the EnDat encoder from a -4EA1 motor has a Heidenhain calibration and a 5 V interface. A swapped encoder will report the wrong motor data and will be out of commutation. Use an SMC20 to adapt the -4EA1 motor to the existing DRIVE-CLiQ topology instead.

Which Sensor Module is required to connect a 1FT6132-6SC71-4EA1 to a SINAMICS S120 Book Size drive?

The SMC20 (cabinet-mounted, order number 6SL3055-0AA00-5BA2) or SME20 (external-mounted, 6SL3055-0AA00-5EA2) is the Sensor Module for EnDat 2.1/2.2 encoders. The SMC20 occupies one DRIVE-CLiQ address and is wired to the M24 connector at the motor via a Heidenhain or Siemens EnDat cable.

What parameter must be changed to route the encoder to the Sensor Module channel?

p0430[0] is the encoder assignment parameter; set it to the drive object index of the SMC20 to move the encoder evaluation off the Motor Module X200 channel and onto the Sensor Module channel. After the change, copy RAM to ROM and power-cycle the Control Unit.

Do I need to redo the commutation angle after the encoder is moved from DRIVE-CLiQ to EnDat on the SMC20?

The 1FT6 absolute encoder is delivered factory-calibrated. As long as the encoder has not been physically moved between rotors, the commutation angle is read from the encoder EEPROM and a p1990 test is verification only. If the encoder is physically moved between motors, a p1990 / p1980 pole-position identification is mandatory and the encoder is no longer guaranteed to be in the calibrated state.

Where can I order a 1FT6132-6SC71-4FA1 replacement motor with the correct DRIVE-CLiQ encoder?

Order through Siemens Industry Online Support or the local Siemens Industry partner portal. The recommended contact for a motor-stock mismatch is Siemens ASP&A. Provide the rating plate data, the current spare motor MLFB, and the in-service motor MLFB so that Siemens can confirm the replacement MLFB and the catalog number of the DRIVE-CLiQ encoder.

Back to blog