SINAMICS S120 Firmware V2.5 SP2: Drive CLiQ SMI Motor Module Update Guide
The SINAMICS S120 drive platform relies on Drive CLiQ as the backplane between the Control Unit (CU310, CU310-2, CU320, CU320-2), Motor Modules (Single/Double Motor Modules), Terminal Modules (TM31, TM120, etc.), SMC/SME encoder modules, and Sensor Modules Integrated (SMI) on the motor side. Each Drive CLiQ node carries its own firmware image. Starting with SINAMICS V2.5, Siemens introduced an automatic firmware update mechanism that reconciles the firmware on every connected Drive CLiQ component with the firmware image stored on the CompactFlash (CF) card of the Control Unit. This article consolidates the field-proven rules for SMI detection, mixed firmware versions, downgrade behavior, CF-card sourcing, and the practical limits of reusing firmware from SIMOTION D packages.
1. Drive CLiQ Topology and SMI Hardware Detection
Drive CLiQ is a proprietary Siemens real-time serial link operating at a fixed baud rate over shielded twisted-pair wiring. Each node reports a unique identifier (component type, article number, serial number, hardware release, firmware version) that is parsed by the Control Unit during topology scan. The SMI (Sensor Module Integrated) is embedded inside the motor connector housing and converts resolver or sin/cos encoder signals into DRIVE-CLiQ frames that the S120 reads as the motor encoder and, where supported, as the electronic nameplate source.
| Component | Typical Article No. | Reports to CU as |
|---|---|---|
| SMI on motor (DRIVE-CLiQ interface) | Integrated (motor-side) | Sensor Module / Motor with electronic rating plate |
| SMC20 (external encoder adapter) | 6SL3055-0AA00-5B.. | Encoder interface |
| TM31 Terminal Module | 6SL3055-0AA00-3A.. | Digital/analog I/O |
| Single Motor Module | 5 kW–200 kW booksize range | Power section (infeed / drive) |
When a motor with an SMI is wired to a Motor Module, the SMI must appear in the online topology under Drive CLiQ topology > Actual topology regardless of firmware version. If it is missing, the problem is hardware or wiring, not firmware. Verify, in order:
- Drive CLiQ cable continuity: pin-out must follow the Siemens 6SL3060 standard (24 V, GND, DATA+, DATA-). Use only Siemens pre-assembled cables (e.g., 6FX5002 series) or pre-fabricated motor-side cables supplied with the motor.
- 24 V supply on the SMI. The motor-side Drive CLiQ connector carries a 24 V feed that powers the SMI electronics. Loss of 24 V prevents the SMI from responding to topology queries, even though the cable data pairs are intact.
- Termination and DRIVE-CLiQ port selection. A star topology with the Control Unit at the hub is mandatory. Daisy chains beyond the documented max length or using passive splitters cause intermittent detection.
- Connectors seated and locking clips engaged. The D-sub style IP20 connector on booksize Motor Modules and the M17/M23 round connectors on motors must be fully torqued/locked.
- Motor module DI/DO status. The SMI requires the Motor Module to be powered up (24 V electronics supply on the Motor Module). A Motor Module with no DC link pre-charge will still report a port, but the SMI handshake may be incomplete.
2. Firmware Compatibility Rules: CU320/CU310 vs SMI
SINAMICS S120 firmware has evolved through a number of major and service pack releases. The Control Unit (CU) and every Drive CLiQ component must be evaluated for compatibility at three levels:
| Level | Rule | Typical Mismatch Symptom |
|---|---|---|
| Major (V2.x, V4.x, V5.x) | Control Unit firmware and component firmware must share the same major release family. V2.5 CU cannot run V4.x components, and vice versa. | F019 topology error, drive object rejected |
| Service Pack (SP1, SP2, HF…) | Service packs within a major release are cross-compatible. V2.5 SP1 CU can communicate with V2.5 SP2 SMI. | Automatic update on next power-up |
| Hotfix (HFf6, HF19, HF24…) | Bug-fix only; fully inter-operable with the same major+SP base. | None — transparent to user |
For the canonical question: a CU320 running V2.5 SP1 HF6 and an SMI shipping from the factory with V2.5 SP2 firmware is a valid configuration. The CU's CF card holds the V2.5 SP1 image; the SMI carries V2.5 SP2. Because both share the V2.5 major release and the CU's CF image is the project's source of truth, the automatic firmware update feature will reconcile the SMI to V2.5 SP1 (or the SP level on the CF) on the next power-up.
3. Automatic Firmware Update Mechanism (V2.5 and Later)
Beginning with SINAMICS S120 firmware V2.5, the Control Unit compares the firmware version of every Drive CLiQ node against the firmware image stored on the CF card. Mismatches are corrected automatically on the next control section power-up (24 V on the CU) provided the following pre-conditions are met:
- The set topology and actual topology match. Siemens STARTER / Startdrive may refuse the auto-update if components are added or removed after the last project download, or if a configured component is physically absent.
- The CF card contains a complete firmware set, including the firmware for downstream Drive CLiQ components. The CF image is the master.
- The CU has booted without active fault. A persistent F01910 topology error halts the upgrade cycle until the topology is corrected.
- The drive objects involved are not in a safety-locked state (e.g., Safety Integrated with active commissioning lock).
During the update, alarm A01016 is raised — Firmware update in progress — and the affected drive is held in a non-operational state. The update typically completes in 30 to 180 seconds per component depending on the size of the firmware delta. After the upgrade, a power-up is required for the new firmware to become active.
4. Firmware Downgrade Behavior at Power-Up
Field experience confirms the following rule: the CF card image is the master in both directions. If the SMI ships with a newer firmware (e.g., V2.5 SP2) than the CF card (e.g., V2.5 SP1), the SINAMICS auto-update will downgrade the SMI to match the CF image. Conversely, if the SMI is older, it is upgraded to match. The Control Unit itself cannot be downgraded this way — the CU firmware is what is on the CF card and that image is the one the CU boots from.
| CU CF-Card Image | SMI at Power-Up | Result on Power-Up |
|---|---|---|
| V2.5 SP1 | V2.5 SP2 | SMI downgraded to V2.5 SP1 |
| V2.5 SP2 | V2.5 SP1 | SMI upgraded to V2.5 SP2 |
| V2.5 SP2 HF6 | V2.5 SP1 | SMI upgraded to V2.5 SP2 HF6 |
| V2.4 | V2.5 SP2 | F019 — major version mismatch, no auto-update |
This is a useful confirmation mechanism: by monitoring r0002 (Drive operating display) and r0017 (component firmware version) after each power-up, the engineer can verify that the live firmware on the SMI matches the project plan.
5. Obtaining SINAMICS S120 Firmware Files
SINAMICS S120 firmware is distributed by Siemens Industry Online Support. The current and historical firmware deliveries for CU310 / CU310-2 and CU320 / CU320-2 are listed in the Siemens support database, for example:
- SINAMICS S120 Firmware Version 2.6 SP2 HF19 for CU320 and CU310 — Siemens Support entry 33124038
- SINAMICS S120 Firmware Version 5.2 SP3 HF24 for CU320-2 and CU310-2 — Siemens Support entry 109780844
Historical V2.5 SP2 builds and the associated drive object packages are accessible via the legacy entry SINAMICS MICROMASTER / Starter distribution (Siemens Support ID 26233208). The firmware download bundle is shipped as a self-extracting archive containing:
-
SINAMICS_S120_CU3xx_2_5_SP2.bin— the CU flash image - Drive object firmware files (
*.upd) for Motor Modules, Active Line Modules, Terminal Modules, encoder modules, and SMI - Release notes describing defect fixes and the SP-level compatibility baseline
Place the firmware files in the appropriate folders on the CF card before inserting it into the CU. The conventional layout is:
/CF Card root
├── FW_UPDATE/ (CU firmware *.bin, *.upd files)
├── OEM/ (vendor-specific files)
├── PROJECT/ (STARTER/Startdrive archive)
└── USER/ (license keys, AOP30 settings, logbook)
Always cross-check the article number of your CF card against the supported list. SINAMICS S120 V2.5 SP2 supports both the legacy 6SL3057-0AA00-2BA0 (2 GB) and the 6SL3057-0AA00-6BA0 (2 GB, V2.5+ recommended) cards. Older V2.4 cards may not have sufficient free space for V2.5 SP2 components.
6. Upgrading CU310 from V2.4 to V2.5 SP2
The CU310 (single-axis Control Unit) follows the same update procedure as the CU320. The recommended sequence is:
- Back up the existing project. From STARTER:
Project > Save to memory cardand additionallyProject > Save & compileto a separate archive location. - Insert the CF card into a card reader on the engineering PC. The CU310 CF card slot is accessible at the front.
- Copy the V2.5 SP2 firmware files into the
FW_UPDATEfolder, preserving the original file structure. - Re-insert the CF card into the CU310 and power up the control section (24 V only). The CU detects the new firmware, raises alarm A01016, and begins the update.
- Wait for the update to complete (typically 60–300 s). The RDY (Ready) LED will flash during the update. A red RDY LED sustained for more than 5 minutes indicates a fault — refer to the SINAMICS S120 List Manual for the LED flash code.
- Perform a second power-up to activate the new firmware and clear alarm A01016.
- Reconnect with STARTER and verify
r0017reports the expected V2.5 SP2 build. The set firmware version in the project must be updated to match.
If the CU310 was running V2.4 firmware, the upgrade to V2.5 SP2 is a major-version step only at the SP level — V2.4 and V2.5 share the same major family. The upgrade is supported and reversible in the field. Be aware, however, that some parameters introduced or retired between V2.4 and V2.5 require a project re-commissioning. The STARTER / Startdrive compare tool will flag any p-parameter differences.
7. Why SIMOTION D Firmware Cannot Be Reused
SIMOTION D is a motion controller that integrates a SINAMICS drive section on the same hardware. While SIMOTION D contains a SINAMICS subsystem, its firmware package is not interchangeable with a stand-alone SINAMICS S120 CU for the following reasons:
- The SIMOTION D firmware image combines the SIMOTION runtime and the SINAMICS drive image in a single signed binary. Extracting only the SINAMICS portion breaks the signature and the resulting file is rejected by the SINAMICS CU bootloader.
- SIMOTION D may include SINAMICS firmware versions (e.g., V4.x or V5.x) that are not compatible with a stand-alone V2.5 SP2 CU. The major version mismatch would prevent the CU from booting.
- License keys, OEM extension files, and technology packages are organized differently in SIMOTION D image containers.
Always obtain the stand-alone SINAMICS S120 firmware from the Siemens Industry Online Support portal and use the official CF-card image. The SIMOTION D package is reserved for SIMOTION D controllers only.
8. SMI-Specific Considerations for Mixed-Firmware Commissioning
When commissioning a motor whose electronic rating plate is read through the SMI, the following additional checks apply:
- Confirm the motor part number, frame size, encoder type, and winding data have been read from the electronic rating plate (parameters
r0108for drive object configuration andp0301,p0304,p0305,p0311for motor data). - If the motor data appears as default values (e.g.,
p0304 = 0), the SMI was not read correctly. Check the Drive CLiQ wiring and the SMI's firmware version, and verify that the auto-update completed. - For motors with DRIVE-CLiQ integrated, the encoder type and resolution are reported by the SMI automatically. Manual entry of
p0400andp0408is not required and may cause conflict if attempted. - Confirm Safety Integrated compatibility when upgrading across major SP boundaries. The safety firmware (if licensed) must also match the new major release.
9. Commissioning Checklist
| Step | Verification | Pass Criterion |
|---|---|---|
| 1. CF card content | List FW_UPDATE folder via card reader |
CU binary + component *.upd files present |
| 2. CU firmware version | STARTER online > r0017
|
Matches project set version |
| 3. Motor Module firmware | STARTER online > component view | Auto-updated to CF image |
| 4. SMI firmware | STARTER online > component view | Auto-updated; matches major release |
| 5. Drive CLiQ topology | Topology > Actual vs Set | All nodes present, no F019 faults |
| 6. Motor data from electronic rating plate | STARTER > Configuration > Motor data | Real values populated, not 0 or default |
| 7. Safety Integrated (if licensed) | STARTER > Safety Integrated > Versions | Safety FW matches CU major release |
10. Troubleshooting Matrix
| Symptom | Likely Cause | Resolution |
|---|---|---|
| SMI not visible in actual topology | Drive CLiQ wiring, missing 24 V to SMI | Check cable, connector, 24 V feed at motor-side Drive CLiQ |
| F01910 topology fault | Set/actual mismatch, or component removed | Re-download project, accept topology, or correct wiring |
| F019 component firmware incompatible | Major version mismatch (e.g., V2.4 SMI in V2.5 project) | Upgrade CU to matching major release, or replace SMI/motor |
| A01016 firmware update loop | Power interrupted during update | Re-flash CF card, re-apply update with stable 24 V supply |
| Motor data shows default 0 values | SMI electronic rating plate not read | Verify SMI firmware match, re-power the drive, re-download project |
| CU does not boot after firmware update | Corrupted CF image or wrong CU binary | Restore CF card from backup image; reformat and re-apply firmware |
| SMI hot-plug not detected | Drive CLiQ port assignment mismatch | Reconnect to designated port, perform topology comparison in STARTER |
11. Field-Commissioning Notes
For a greenfield V2.5 SP2 cabinet build, the most reliable sequence is to apply the CF card image to all components at the panel shop, run a 30-minute soak with no faults, and then perform motor data identification. If a single component repeatedly fails the auto-update, capture r0017 (component firmware version) and the diagnostic buffer entries (DCC logbook, parameter r0947) before contacting Siemens support. The diagnostic buffer reveals whether the failure is due to a power interruption, a corrupt firmware file, or a hardware fault on the Drive CLiQ node.
For brownfield retrofits where existing V2.4 systems are upgraded to V2.5 SP2, perform the upgrade in two steps: first upgrade the CU to a transitional V2.5 build, validate the project, then re-load with the V2.5 SP2 CF image. This minimizes commissioning risk and allows parameter parity checks at each step.
Why is my SMI motor module not detected in the SINAMICS S120 online topology?
The SMI is missing in the actual topology because of a hardware or wiring issue, not a firmware version mismatch. Verify the Drive CLiQ cable continuity, the 24 V supply at the motor-side connector, the connector lock, and the port assignment on the Motor Module. The hardware node must appear before any firmware reconciliation can take place.
Can a CU320 running V2.5 SP1 HF6 control an SMI motor that ships with V2.5 SP2 firmware?
Yes. Both share the V2.5 major release, so service packs and hotfixes are cross-compatible. The automatic firmware update feature (introduced in V2.5) will reconcile the SMI to the V2.5 SP1 image on the CF card on the next power-up, provided the set and actual topology match.
Does the SINAMICS S120 automatically downgrade an SMI whose firmware is newer than the CF card?
Yes. The CF card image is the master in both directions. The Control Unit will downgrade an over-fresh SMI to match the CF image and upgrade an under-fresh SMI. The CU itself, however, is not downgraded automatically — its firmware is the CF card image.
Where can I download the SINAMICS S120 V2.5 SP2 firmware for a CU310?
The firmware is distributed through Siemens Industry Online Support. The historical V2.5 SP2 builds and the related CU320/CU310 files are available under entry 26233208, while the more recent V2.6 SP2 HF19 and V5.2 SP3 HF24 packages are listed in support entries 33124038 and 109780844 respectively. SIMOTION D firmware packages must not be used to extract SINAMICS CU images.
Can I extract SINAMICS S120 firmware from a SIMOTION D firmware image?
No. SIMOTION D firmware combines the SIMOTION runtime and the SINAMICS drive image in a signed binary. Extracting only the SINAMICS portion breaks the signature and the file is rejected by the SINAMICS CU bootloader. Always obtain stand-alone SINAMICS S120 firmware from the Siemens Industry Online Support portal.
How do I know the SMI auto-update completed successfully?
Check r0017 for the SMI's component firmware version via STARTER / Startdrive after the next power-up. Alarm A01016 is raised during the update and is cleared automatically when the new firmware is activated on the following power-up. If A01016 persists across two power-ups, capture the diagnostic buffer (parameter r0947) and the CU logbook for further analysis.