SINUMERIK 840D SL Safe Position Limit MD36934/MD36935 Change

David Krause12 min read
Safety SystemsSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The safe position end limits for a SINUMERIK 840D sl are stored in two machine data words:

  • MD36934 $MA_SAFE_POS_LIMIT_PLUS – positive (upper) safe position end limit per axis
  • MD36935 $MA_SAFE_POS_LIMIT_MINUS – negative (lower) safe position end limit per axis

These MDs are part of Safety Integrated (SI) on the NCK side and are mirrored to the SINAMICS S120 drive-side Safety Integrated parameters P9634 and P9635. Both sides must contain the same value; the drive performs the actual monitoring in its safe position channel (SP) and reports a violation back to the NCK as alarm 27012 with subsequent stop reaction.

Unlike non-safety machine data, these limits are protected by an SI confirmation / acceptance procedure. Editing them directly in the start-up area, modifying the mirrored drive parameter, or skipping the user-agreement (operator confirmation) sequence will leave the axis in a non-safe state and will produce alarms in the 27001/27002/27012 range during the next NCK reset.

This procedure applies to the configuration reported in the source case:

Component Version
CNC SINUMERIK 840D sl
NCU NCU 720.3
NCK software NA 15.3 (SINUMERIK Operate / HMI-Advanced generation)
PCU PCU 50.5
Drive SINAMICS S120 (Safety Integrated extended functions, firmware ≥ 4.7)

The governing document is the Siemens Safety Integrated function manual for 840D sl / S120: SINUMERIK Safety Integrated SINUMERIK 840D sl / SINAMICS S120 (FBSI 4.7 SP2). Use that document as the binding reference for every step below; values and menu paths can shift between NCK SW releases.

Prerequisites Before You Change the Limit

  1. Access level: Log in with Service authority (key switch position 3 on the MCP). The machine data and the SI confirmation dialogs are only visible at this level.
  2. Axis configuration check: Verify in MD36901 $MA_SAFE_FUNCTION_ENABLE that the safe position limit function (bit pattern for SE/SN, SLP) is enabled for the affected axis. If SLP is not active, MD36934/MD36935 are inactive.
  3. Modulo check: If the axis is a modulo rotary axis, confirm whether you are using MD36934/MD36935 (modulo-corrected) or MD36936/MD36937 ($MA_SAFE_POS_LIMIT_PLUS_2 / MINUS_2 for modulo). On a linear axis without modulo only 36934/36935 apply.
  4. Drive firmware: SINAMICS S120 Safety Integrated firmware ≥ 4.7 must be installed; mismatched firmware between NCK and drive side is the most common reason for stop reactions (F01611 / F30611 / F08501) on the drive side after a parameter change.
  5. Backup: Before changing any SI parameter, run a complete series start-up file backup (Startup → Series start-up → Create series start-up) so you can restore the previous safe configuration if an acceptance test fails.
Always treat MD36934 / MD36935 / P9634 / P9635 as a coupled pair. Editing only one side and not the other will produce an SI cross-check error (F01611 / alarm 27005) on the next PO reset.

Parameter Mapping: NCK ↔ Drive

The NCK-side machine data and the drive-side safety parameters must match exactly. The pattern below is the same for every SI limit/cam parameter: Safe_Axis_param_NCK = Safe_Axis_param_Drive.

NCK machine data Description Drive-side mirror
MD36934 $MA_SAFE_POS_LIMIT_PLUS Upper safe position limit (axis units) P9634
MD36935 $MA_SAFE_POS_LIMIT_MINUS Lower safe position limit (axis units) P9635
MD36936 $MA_SAFE_POS_LIMIT_PLUS_2 Modulo upper limit (modulo axes only) P9636
MD36937 $MA_SAFE_POS_LIMIT_MINUS_2 Modulo lower limit (modulo axes only) P9637

On SINAMICS S120, the equivalent parameter numbers come from the Safety Integrated parameter set (r97xx / p96xx range). On a CU320-2 with firmware ≥ 4.7, the mapping is:

  • p9634[0] – Safe position limit, upper (drive SI channel 1)
  • p9635[0] – Safe position limit, lower (drive SI channel 1)

Confirm the index in your project: in a single-encoder SI configuration you use index [0]; in a dual-encoder configuration you must also update index [1].

Procedure A – Axis With Absolute Measuring System (Recommended Path)

Use this path on any axis with an absolute EnDat or DRIVE-CLiQ encoder where the SI absolute position is already valid.

  1. Bring the axis into the planned safe zone. Use JOG with reduced velocity override. Verify the axis position is well inside the current safe limits; you cannot exceed the active limit without tripping 27012.
  2. Withdraw the user agreement. On the SINUMERIK Operate sidebar, open Diagnostics → Safety → User agreement. The screen lists every safety axis (machine name, SI position, user agreement). Set User agreement = NO. The access key must be at position 3 for this toggle. After the toggle the axis is not safe – the drives drop SI monitoring for SLP and only the standard NC limits remain active.
  3. Edit MD36934 and MD36935 for the affected axis to the new mechanical limits. Use the axis units (mm or degrees) matching MD10220 $MA_POSCTRL_GAIN / MD10240 scaling.
  4. Save the NCK area (Startup → Machine data → Save). Confirm any prompt about changing safety-related data.
  5. Update the drive mirror: Open the drive commissioning tool (Starter / Startdrive / SINUMERIK Operate commissioning). Enter the same numeric values into p9634[0] and p9635[0]. Copy RAM → ROM on the drive, then select Save the part of driver (i.e. save the drive-side safety parameters to the CF card).
  6. PO reset (drive): Execute a Power On reset on the drive (or CU). The drive will report an SI cross-check error during boot because NCK and drive have different CRC's; this is expected.
  7. PO reset (NCK): NCK reset from HMI (Startup → Reset (PO)). Several alarms will appear in the alarm bar.
  8. Run the SI confirmation: Startup → Safety → Confirm SI. Click OK for each prompt. The system signs the new SI configuration and computes fresh checksums for both NCK and drive.
  9. Save the drive system again. After SI confirmation, copy RAM → ROM on the drive and Save part of driver a second time so the new SI checksum is persistent across power cycles.
  10. Restore the user agreement: Go back to Diagnostics → Safety → User agreement and set User agreement = YES. The axis is now safe again with the new limits.
Re-activating the user agreement is a non-trivial safety step. The operator is confirming they have physically verified the axis is inside the new safe envelope. Do not script this step or skip the operator presence check.

Procedure B – Axis With Incremental Measuring System

For an axis without an absolute encoder, the safe position is invalidated every time the drive is de-energised. The flow therefore starts with a controlled power cycle.

  1. Move the axis into the new safe zone in JOG using the standard NC limits, before any SI edit. Confirm with the axis on the HMI position display.
  2. Switch OFF the machine (NCK ready off, drive mains contactor open).
  3. Switch ON the machine. The drives initialise with SI inactive. SI position is not valid until referencing completes.
  4. Reference the axis in the conventional (non-safe) way. Once referenced, the SI absolute position is established.
  5. Inspect the SI position on the HMI (Diagnostics → Safety → Axis SI positions) and verify it matches the mechanical expectation. Cross-check on the second channel where fitted.
  6. Edit MD36934 / MD36935 to the new envelope. Save NCK area.
  7. Edit drive mirror p9634 / p9635 to the same values. Save drive part.
  8. PO reset (drive + NCK) in either order, then Confirm SI as in Procedure A steps 7–9.

If the machine has OEM-specific PLC logic that interlocks user-agreement / SI confirmation to a hardware key or guard interlock, the PLC must release that interlock before the HMI button responds. Check the OEM project if Confirm SI is greyed out.

Standalone SI Parameter Change Cycle (Per Field-Proven Pattern)

For any Safety Integrated axis parameter – not just MD36934/MD36935 – the canonical cycle is:

  1. Set Safe_Axis_param_NCK = Safe_Axis_param_Drive (verify bytewise equality, including sign).
  2. Save the drive part (Copy RAM → ROM + Save part of driver).
  3. NCK PO reset.
  4. Wait for the expected alarm list (27001, 27005, 27012, 27013 in some combination – all expected on first boot after an SI edit).
  5. Run Startup → Safety → Confirm SI. Acknowledge each prompt.
  6. Save the drive part again to persist the SI checksum.
  7. NCK PO reset once more.
  8. Verify no SI alarms remain and the axis accepts JOG motion with the new envelope.

This is the cycle the field engineer referred to as Safe_Axis_param = Drive_Axis_param → Reset PO → Confirm → Reset PO. Two PO resets are required because the first reset only loads the new values; the second reset confirms the SI checksum round-trip is consistent.

Alarm Reference (Relevant Alarms on 840D sl)

Alarm Meaning Typical Reaction
27001 STOP F triggered for SI axis – drive transition from operation to safe stop after SI violation Drive pulses cancelled via STOP A after configurable dwell
27002 STOP A triggered – immediate pulse cancellation Axis drives de-energised
27005 SI cross-check error between NCK and drive (different SI limit values) Stop reaction; appears if you edit one side and not the other
27012 Safe position limit (SLP) violated – axis crossed MD36934/MD36935 boundary STOP F → STOP A
27013 SI confirmation pending – changes were made but Confirm SI not yet run Informational, cleared after SI acceptance

In the source case, after MD36934 was edited and a PO reset issued, the user received alarm 27001 with error code 11 and the drive was reported not ready (OFF3 active). Error code 11 in this context maps to safe position limit violation / SI cross-check inconsistent; the user agreement was not withdrawn first, so the axis was still being monitored by the old SLP envelope while the new value was being downloaded, producing the STOP F → STOP A chain. The fix is to follow Procedure A steps 2–9; do not attempt to move the axis until the user agreement is withdrawn.

PLC Signal Reference for SI State

On the PLC side, the NCK exposes the safety state through interface DB31, .. DBX71.x and DB31, .. DBX72.x. The signals most useful during this procedure are:

  • DB31..DBX71.1 – SI safe position limit active
  • DB31..DBX72.1 – SI safe position limit plus actively violated (positive limit)
  • DB31..DBX72.2 – SI safe position limit minus actively violated (negative limit)
  • DB31..DBX71.5 – SI user agreement withdrawn / pending

If your PLC logic OR's any of these into an axis enable or a feed-hold, the axis will not move in JOG even after the user-agreement toggle. Verify the OEM logic before relying on HMI buttons alone.

Verification Checklist After the Change

  1. Alarm bar clear of all 27001 / 27002 / 27005 / 27012 / 27013 entries. Persistent 27013 indicates SI confirmation did not complete.
  2. Diagnostics → Safety → Axis SI positions shows a real, non-zero position for both channels of the affected axis.
  3. Diagnostics → Safety → SI checksums displays the same CRC for both channels; the CRC must also match the value written during SI confirmation.
  4. JOG motion in both positive and negative directions travels up to but not past the new limit. Use a controlled feed override (5–10 %) for this test.
  5. Drive-side, on Starter / Startdrive / AOP30, verify r9710 / r9711 (SI diagnostics) and r9725 (SI motion status) return to Safe after motion completes.
  6. Run the SI acceptance test protocol (machine manufacturer's documentation, typically a checklist of safe functions) and file the signed report with the machine logbook – required for CE / functional-safety audits.

Troubleshooting Matrix

Symptom Most Likely Cause Corrective Action
Alarm 27001 with error 11 immediately after PO reset User agreement not withdrawn before MD36934/MD36935 edit, drive still monitors old SLP envelope Withdraw user agreement, move axis inside envelope, re-edit, run SI Confirm, second PO reset
Alarm 27005 after edit NCK MD36934 ≠ drive p9634, or NCK MD36935 ≠ drive p9635 Re-enter drive values bytewise equal to NCK, save drive, PO reset, Confirm SI
Alarm 27013 persists SI Confirm not completed, or PLC interlock blocks Confirm Run Startup → Safety → Confirm SI end-to-end; check OEM PLC key
Drive reports F01611 SI parameter inconsistency, usually wrong index (channel 1 vs channel 2 on dual encoder) Verify p9634[0]/[1] and p9635[0]/[1] both match MD36934/MD36935
Axis will not move in JOG after withdrawing user agreement OEM PLC feedhold or axis enable still references the SI agreement bits Check DB31..DBX71.5 wiring in OEM PLC; release PLC feedhold before JOG
Limit value keeps reverting after PO reset Drive part not saved (RAM only, not ROM) Copy RAM → ROM and run Save part of driver; verify on subsequent PO reset
SI checksum mismatch on first boot Only one side (NCK or drive) was updated Verify MD36934/36935 = p9634/p9635 numerically; run Confirm SI again

Field-Proven Caveats

  • Two PO resets are not optional. The first reset exposes the mismatch (alarms 27001/27005). The second reset is the post-confirmation reboot; alarms will clear only on this second reset if Confirm SI succeeded.
  • Save the drive part twice. Once before PO reset (to load new values) and once after Confirm SI (to persist the SI checksum). The NCK side keeps MD36934/36935 in the active memory after Save; you do not need to re-enter them after Confirm SI.
  • Never disable SLP only on one channel. If you have a dual-encoder SI configuration, both encoders must agree on the position and both drive-side parameter sets (index [0] and [1]) must be updated.
  • Modulo axes use 36936/36937. On modulo rotary axes, MD36934/MD36935 are not the active SLP parameters unless you are working in non-modulo mode. Verify with MD10210 $MA_INT_INCR_PER_DEG and the axis configuration before assuming 36934/36935 are the right pair.
  • Keep a paper SI acceptance trail. The acceptance test printout from Startup → Safety → SI Acceptance Test is the legal record for the change. File it with the machine logbook.

FAQ

Why does alarm 27001 with error code 11 appear after editing MD36934?

Because the user agreement was not withdrawn before the edit, the drive SI channel was still monitoring the old SLP envelope. The new NCK value disagrees with the drive mirror at boot, producing a STOP F → STOP A chain (alarm 27001, error 11). Withdraw the user agreement, move the axis inside the new envelope, re-edit the NCK and drive sides to match, then run SI Confirm and a second PO reset.

Do I have to edit both MD36934 and P9634?

Yes. NCK and drive-side SI values must match bytewise. Edit MD36934 and MD36935 to the new limits, then enter the same values into p9634[0] and p9635[0] (and index [1] if you have a dual-encoder SI axis). Mismatched values produce cross-check alarm 27005 on the next PO reset.

Which key-switch position is required to change the safe position limits?

Access level 3 (Service / Customer Service), which corresponds to key-switch position 3 on the MCP. Both the MD36934/MD36935 edit and the User agreement toggle require this level.

Can I change MD36934 on an axis with an incremental encoder without withdrawing the user agreement?

No. The safe position is only valid after referencing, and the drive SI channel still enforces the limit on every boot. Follow Procedure B: power cycle, reference, verify SI position, then edit and confirm. Withdrawing the user agreement is also valid on incremental axes and is often simpler than a full power cycle.

How do I clear the persistent 27013 alarm after a Confirm SI run?

Alarm 27013 means SI confirmation did not complete or its checksum was not committed. Re-run Startup → Safety → Confirm SI, accept every prompt, copy RAM → ROM on the drive, run Save part of driver a second time, then NCK PO reset. The alarm should clear on the next boot.

Back to blog