SITRANS FUP1010 Configuration: Clamp-On Flowmeter Field Setup

David Krause19 min read
Process ControlSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SITRANS FUP1010 is a portable, battery-powered, clamp-on transit-time ultrasonic flowmeter used to measure liquid flow in full pipes without breaking into the line. Two piezoelectric transducers are clamped to the outside wall of an existing pipe, transmit and receive ultrasonic bursts diagonally through the pipe wall and the process liquid, and the meter computes volumetric flow from the difference in transit time between upstream- and downstream-propagating acoustic pulses. Because the FUP1010 is non-invasive, it is the workhorse for temporary surveys, spot-checking an existing inline meter, balancing flows across a plant, and verifying pump curves.

This reference walks through the complete field commissioning workflow: kit inspection, pipe and site preparation, transducer selection, couplant application, mechanical mounting, the on-device menu configuration sequence, zero-flow verification, data logging, and the most common fault conditions encountered during portable surveys.

Before starting, the operator must complete the basic product training referenced in the device manual. Untrained operators will produce bad data and may misdiagnose a healthy installation as a faulty one.

Theory of Operation: Transit-Time Clamp-On

Two transducers are mounted on the same or opposite sides of a pipe. Transducer A fires an acoustic burst through the pipe wall, across the flowing liquid, and into transducer B. The transit time downstream (with the flow) is shorter than the transit time upstream (against the flow). The meter measures both transit times, calculates the delta-t, and converts the result to a velocity and then a volumetric flow using the entered pipe area.

The transit-time technique is fundamentally different from the Doppler technique. Doppler meters rely on suspended particles or bubbles to scatter the beam and are tolerant of dirty liquids but unusable on clean water. Transit-time meters rely on a clean acoustic path and are well suited to potable water, raw water, cooling water, and most clean industrial liquids. The FUP1010 is a transit-time instrument.

Two acoustic paths can be configured: a single-path install (one transducer pair, one chord) and a dual-path install (two pairs averaged to suppress swirl and asymmetric profile errors). For portable surveys the single-path configuration is the default and is adequate for the typical ±1% to ±3% accuracy target.

System Components and Kit Contents

Item Function
FUP1010 transmitter Portable battery-powered CPU and graphical display unit. Runs the transit-time algorithm, drives the transducers, and stores logged data.
Clamp-on transducer pair Sends and receives ultrasonic bursts through the pipe wall. Frequency and face size are matched to the pipe OD and wall material.
Mounting set Chain, strap, magnetic frame, or rail that provides repeatable mechanical alignment and a constant coupling force on the pipe OD.
Spacer blocks Pre-machined blocks that snap into the rail and set the axial separation between the two transducers for the selected mounting mode (V, Z, or W).
Acoustic couplant gel Water-based or silicone-based medium that displaces air between the transducer face and the pipe wall.
Calipers or pipe OD tape Used to measure the true outer diameter in two perpendicular axes.
Ultrasonic wall-thickness gauge Used to confirm pipe wall thickness when the schedule is unknown.
Portable transit case Foam-lined case for the transmitter, transducers, spacers, gel, and accessories.

Prerequisites

Confirm the following are on site before powering up the meter:

  • FUP1010 transmitter with a charged internal battery (or fresh cells, depending on the variant).
  • Transducer pair sized for the pipe OD and material. Each transducer carries an index number on its housing or cable label; this index must be entered into the meter.
  • Mounting hardware compatible with the pipe diameter (chain set for 50 mm–600 mm, magnetic frame for steel pipes 100 mm–1500 mm, custom rail for very large or very small pipes).
  • Spacer blocks for the selected mounting mode.
  • Couplant gel rated for the pipe surface temperature. Water-based gel is suitable to roughly 80 °C; high-temperature gel is required above that.
  • Confirmed pipe material (carbon steel, stainless steel, ductile iron, cast iron, copper, PVC, HDPE, GRP, etc.) and lining material and thickness, if any.
  • Confirmed fluid identity (water, seawater, glycol mixture, light oil) and approximate operating temperature.
  • Calipers, wall-thickness gauge, and a marker for laying out the transducer footprint.
A portable survey performed without a wall-thickness gauge and without confirmed pipe material is the single most common cause of systematic error. Always verify pipe data before declaring the meter installed.

Site Survey and Pipe Preparation

Accuracy on a clamp-on install is dominated by the quality of the mechanical and acoustic coupling, not by the transmitter electronics. Spend the time on the pipe first.

  1. Select a measurement section at least 10 pipe diameters upstream and 5 pipe diameters downstream of the nearest flow disturbance (pump, elbow, valve, reducer, tee, strainer). Increase to 20D/10D for severely disturbed profiles.
  2. Avoid sections with external corrosion, flaking paint, weld beads, or heavy surface roughness on the axial run where the transducers will sit. Wire-brush or sand the contact area to bright metal and wipe clean.
  3. Confirm the pipe is full. The FUP1010 cannot measure accurately in a partially filled line. Verify by inspecting a drain, a sight glass, or a downstream open discharge.
  4. Measure the pipe OD in two perpendicular axes with calipers; take the mean. For very large pipes, wrap a circumferential tape around the pipe and divide by π.
  5. Measure or look up the wall thickness. For lined pipes, measure the host pipe wall only; the lining is entered as a separate parameter. Common carbon steel schedule 40 wall thicknesses: 2" = 3.91 mm, 3" = 5.49 mm, 4" = 6.02 mm, 6" = 7.11 mm, 8" = 8.18 mm, 10" = 9.27 mm, 12" = 10.31 mm. For other materials, consult the pipe schedule table.
  6. Note the lining. Cement-mortar-lined ductile iron adds 6 mm–12 mm of acoustic travel and must be declared in the menu.
  7. Identify the fluid, its temperature, and approximate operating pressure. The FUP1010 uses fluid sound speed internally; an unexpected gas phase or two-phase flow will degrade the signal.

Pipe Material Sound-Speed Reference

Sound speed through the pipe wall and the process liquid drives the transit-time calculation. The FUP1010 loads sound-speed constants for indexed pipe and fluid materials; the table below lists the values used internally so the engineer can sanity-check the meter on an unfamiliar service.

Material Longitudinal sound speed (m/s)
Carbon steel ≈ 3230
Stainless steel (austenitic) ≈ 3140
Ductile iron ≈ 3000
Cast iron ≈ 2900
Copper ≈ 2260
PVC ≈ 2380
HDPE ≈ 2400
GRP / FRP ≈ 2500 (varies widely)
Water (20 °C reference) 1480
Seawater (20 °C, 35 ppt salinity) ≈ 1520
50% glycol-water (20 °C) ≈ 1580

A 5% error in assumed wall sound speed or a 1% error in assumed fluid sound speed will move the calculated flow by roughly the same percentage. Always declare the actual pipe and fluid in the menu rather than leaving defaults.

Transducer Selection

Transducer frequency and face size are traded off against pipe size and signal attenuation. Lower frequencies penetrate thick or attenuative walls (ductile iron, cast iron, concrete, lined pipes) at the cost of resolution on small pipes. Higher frequencies give better resolution on small clean pipes but cannot drive thick walls.

Pipe OD range (typical) Recommended transducer family
13 mm – 50 mm (0.5" – 2") High-frequency, small-face clamp transducers; Z-mount
50 mm – 300 mm (2" – 12") Mid-frequency general-purpose transducers; V-mount
300 mm – 1500 mm (12" – 60") Low-frequency large-face transducers; W-mount
> 1500 mm (60"+) Very-low-frequency extended-mount transducers; verify signal strength after mounting
The FUP1010 indexes each supported transducer by part number and frequency. Always select the exact part number installed; the meter loads the correct zero offset and timing constants only when the on-screen index matches the physical transducer label.

Couplant Application

Acoustic couplant is mandatory. Air between the transducer face and the pipe wall attenuates the ultrasonic beam by more than 30 dB and will produce a no-signal condition even on a perfect pipe.

  1. Apply a continuous 3 mm–5 mm bead of couplant along the centerline of each transducer footprint location on the pipe.
  2. The bead must cover the full transducer face but should not squeeze out beyond the edges when the transducer is clamped.
  3. Re-apply couplant if the transducers are repositioned. Dried couplant will not transmit sound.
  4. For hot or cold pipes, use a couplant rated for the surface temperature. Standard water-based gel is good to approximately 80 °C; silicone-based or high-temperature gels are required above that range.
  5. Wipe off couplant at the end of the survey. Water-based gel is mildly corrosive on certain stainless grades if left to dry.

Transducer Mounting Modes

Three geometric arrangements are available. The FUP1010 menu lets the installer select the mode; the meter then calculates the required transducer separation (the spacer length).

Mode Geometry Typical use
V-mount Both transducers on the same side of the pipe; beam reflects once off the far wall Pipes 50 mm–300 mm OD; clean signal path, easiest alignment
Z-mount Transducers on opposite sides; direct through-path Small pipes under 50 mm OD where V-mount geometry collapses
W-mount Transducers on the same side; beam reflects twice off the far wall Large pipes over 300 mm OD, attenuative walls, lined pipes

For the portable test kit, the spacer block snapped into the rail defines the axial separation for the chosen mode. The FUP1010 will display the recommended spacing in mm or inches on screen once the pipe data and transducer have been entered.

Mechanical Mounting Procedure

  1. Lay out the transducer footprint on the pipe using the calculated spacing value from the meter. Mark the upstream and downstream positions with a pencil or tape.
  2. Apply couplant to each footprint location (see couplant section above).
  3. For rail mounting, snap the correct spacer block into the rail. For chain or strap mounting, fix the transducers in the mounting frame at the calculated spacing.
  4. Place the assembly on the pipe and tighten the chain, strap, or magnetic frame until the transducers do not move when the pipe is tapped. The mounting force should be firm but not pipe-deforming.
  5. Confirm that both transducers sit flat on the pipe with no air gap visible at the couplant interface. A small ring of couplant squeezing out at the edges is the desired visual indicator.
  6. Route the transducer cables back to the FUP1010 transmitter, keeping them away from VFD power cables, motor leads, and other sources of common-mode noise.
  7. Plug the upstream transducer into channel 1 upstream (or as marked on the meter face) and the downstream transducer into channel 1 downstream. Reversing them produces a negative reading that is easy to miss.

Device Configuration: Step-by-Step Menu Procedure

The sequence below configures a single channel on the FUP1010. The dual-channel variant allows two independent measurement points on the same meter, selected under Dual channel flow.

  1. Power on the meter. Allow the self-test to complete and the last site configuration to load.
  2. Press Menu.
  3. Navigate to Dual channel flow. If you are using only one channel, leave channel 2 disabled to avoid wasted acquisition time.
  4. Select Setup channel, then choose the channel to configure (Channel 1 or Channel 2).
  5. Choose Full size setup. Full size setup walks through pipe data, transducer selection, and mounting mode in one guided sequence. Use Quick setup only on repeat visits to a previously saved site, where the pipe data and transducer selection are already known to be correct.
  6. Select Channel setup.
  7. Press the right arrow -> to enter the parameter entry view.
  8. Create a site name / size name (for example, "Test1" or a tag number such as "FT-103"). This name is stored with the data log and is required to identify the record during download.
  9. Press the left arrow <- to back out to the channel setup menu.
  10. Enter Pipe data.
  11. Enter the Pipe OD in the configured unit (mm or inches). Use the mean of the two caliper readings.
  12. Enter the Wall thickness in the configured unit. For lined pipes, enter the wall thickness of the host pipe (not including the lining); the lining is entered as a separate parameter below.
  13. Select the Pipe material from the indexed list.
  14. If the pipe is lined, select the Lining material from the indexed list and enter the Lining thickness.
  15. Press the left arrow <- to return to the channel setup menu.
  16. Enter Fluid data. Select the fluid type and enter the operating temperature.
  17. Select Pick / install transducer.
  18. Choose the transducer size from the indexed list. The index number is printed on the transducer cable or housing label. Selecting the correct index loads the frequency, face area, and zero offset.
  19. Choose the mounting mode (V, Z, or W).
  20. Choose the spacing method. Use Track for portable surveys on pipes where the FUP1010 can compute the spacing from the entered pipe data. Use direct numeric entry if a rail micrometer is being used.
  21. Note the displayed spacing. Set the spacer block and physically mount the transducers on the pipe at this distance.
  22. When mechanical mounting is complete, select Install completed on the meter, then choose Install to start acquisition.
  23. Wait for the meter to acquire signal. A successful install shows a stable flow value, a healthy signal strength (typically 50%–100% on the on-screen indicator), and a signal-to-noise ratio above the menu threshold.
If the display reads 0.0 with no flow in the pipe, the meter is functioning correctly and the zero has been captured. This is the expected verification reading. Do not interpret 0.0 at zero flow as a fault.

Menu Tree Reference

Menu level Parameter Notes
Channel setup Site / size name Free-form alphanumeric, stored in the data log header
Pipe data Pipe OD Mean of two perpendicular caliper measurements
Pipe data Wall thickness Host pipe only; lining is separate
Pipe data Pipe material Select from indexed list; affects sound-speed calculation
Pipe data Lining material and thickness Enter if present; common values: cement 6–12 mm, rubber 4–10 mm, epoxy 1–3 mm
Fluid Fluid type Water, seawater, glycol mixtures, oils, etc. The FUP1010 uses this to seed the sound-speed search
Fluid Fluid temperature Used to refine the sound-speed estimate; ±20 °C error is usually tolerable
Transducer Transducer index Must match the physical transducer label
Transducer Mounting mode V, Z, or W (see mounting table above)
Transducer Spacing method Track (calculated) or manual numeric entry
Transducer Spacing distance Calculated value the installer must set on the rail
Install Install completed Confirms the physical install before acquisition begins
Output Units, scaling, damping Engineering units, output scaling factor, response time
Datalog Log interval, log trigger Time-based or event-based logging

Verification and Commissioning

Once the meter shows a stable reading, perform the following checks before logging data.

  1. Confirm signal strength is in the green band on the on-screen indicator. A red or amber reading means the meter is reading through noise and the displayed flow should not be trusted.
  2. Confirm signal-to-noise ratio is above the menu threshold (typically ≥ 30 dB for clean water lines).
  3. With flow stopped, verify the meter reads 0.0 ± the zero stability spec. If the reading drifts, the transducer pair is micro-phonic (vibration coupling); re-clamp with a stiffer mounting or move the install away from the pump.
  4. Compare the live reading to a known reference if available: an existing inline meter, a pump curve at a fixed speed, or a volumetric test.
  5. Trigger the data logger to record the measurement. The FUP1010 stores time-stamped records that can be downloaded to a PC via the communication port.
  6. Document the site configuration, pipe data, and verification readings in the field notebook. This record is the basis for any later re-survey of the same line.

Data Logging and Communication

The FUP1010 stores logged records in internal memory together with the site name, pipe data, and transducer index used at the time of logging. This is critical: a flow value without the configuration that produced it cannot be re-verified.

  • Set the log interval to match the survey purpose. Spot checks use single-shot logging; pump tests use 1 s–5 s intervals; long-term trend surveys use 1 min–15 min intervals.
  • For long surveys, confirm battery capacity supports the full planned duration. The meter's on-screen battery indicator gives a rough estimate; carry a spare charged pack for multi-day deployments.
  • Data export is via the meter's wired communication port. Connect to a PC with the cable specified in the manual, launch the vendor's download utility, select the log file, and export to CSV or the vendor's native format for trending in Excel or a SCADA historian.
  • Erase the internal log after a successful download to free space for the next survey.

Battery and Power Management

The FUP1010 runs from an internal rechargeable battery for true portability. Power-management practices that extend field runtime:

  • Disable the backlight during outdoor surveys in daylight; the backlight is the largest single drain.
  • Disable the second channel if only one measurement point is needed.
  • Reduce the display refresh rate if the menu allows it.
  • Power down during long transits between measurement points.
  • Recharge the battery from a mains adapter or a 12 V vehicle supply using the manufacturer's charger only. Third-party chargers can damage the battery management board.
  • Store the meter at room temperature with a 40%–60% state of charge; long-term storage at full charge or at zero charge degrades the cell.

Troubleshooting Matrix

Symptom Likely cause Action
"No signal" after Install Air gap, wrong transducer index, wrong pipe data, dry couplant, empty pipe Re-gel, re-verify pipe OD and wall thickness, confirm transducer index matches the part label, confirm pipe is full
Signal present but flow reads 0 with flow running Transducers mounted with arrows reversed; flow direction sign wrong in menu Swap upstream and downstream transducers or invert the flow direction sign under channel setup
Reading drifts at zero flow Vibration coupling, partially dried couplant, temperature gradient on the pipe Re-clamp with chain or strap tension, re-apply couplant, allow 5 minutes for thermal stabilization, move away from the pump
Reading 10%–30% low compared to reference Wall thickness wrong, lining not declared, fluid sound speed far from water Re-measure wall thickness with a UT gauge, declare lining material and thickness, set fluid to actual product
Reading unstable or oscillating Insufficient straight run, aerated liquid, suspended particulate Relocate to a calmer section; for aerated water, consider another technology or a deaeration column upstream
Display 0.0 with no flow Normal zero condition No action required; this is the expected verification reading
Signal strength low on lined ductile iron Lining attenuation, wrong mounting mode Switch to W-mount, declare lining in the menu, consider a lower-frequency transducer
Meter will not acquire on plastic pipe Pipe not full, fluid is not water, wrong pipe material index Confirm pipe is full, declare PVC or HDPE explicitly, use W-mount on large plastic lines

Field Best Practices

  • Always bring a wall-thickness gauge to site. Guessing the wall thickness is the most common cause of systematic error.
  • Label the upstream and downstream transducers with tape before mounting. Reversing them produces a negative reading that is easy to miss if the sign is wrong in the menu.
  • Keep the transducer cables away from VFD power cables. VFD common-mode noise can corrupt the receiver front end.
  • For repeat surveys, save the site as a named configuration in the FUP1010 internal memory and recall it on the next visit rather than re-entering pipe data from scratch.
  • For cement-lined ductile iron, the lining adds 6 mm–12 mm of travel time. Entering "no lining" will produce a 5%–15% low reading.
  • For survey work on a pipe of unknown service, take a photograph of the pipe marking (manufacturer, nominal size, schedule) before mounting. Pipe markings are often the only reliable way to confirm the schedule.
  • Always record the signal strength and signal-to-noise ratio with the logged data. A reading with poor signal quality is suspect regardless of how plausible the value looks.

Maintenance and Care

  • Wipe transducer faces with a soft, lint-free cloth after every survey. Residual couplant left to dry on the face will pit the piezoelectric element over time.
  • Inspect transducer cables for cracking, kinking, or shielding damage at every survey. A damaged shield lets noise into the receiver and degrades the signal-to-noise ratio.
  • Recalibrate the FUP1010 against a reference flow rig on the interval specified in the manual; portable meters are typically verified annually.
  • Store the unit in its transit case with foam inserts in place. Dropping a transducer can crack the piezo element without any visible external damage.
  • Update the meter firmware to the version recommended by Siemens when performing a major survey. Firmware updates occasionally improve the transit-time algorithm for difficult pipe materials.

Specifications Summary

The following are typical for the SITRANS FUP1010 portable transmitter family. Always confirm exact values against the device nameplate and the official manual shipped with the unit, and against the Siemens flow measurement product page.

Parameter Value
Measurement principle Transit-time ultrasonic, clamp-on
Channels 1 or 2 (variant-dependent)
Pipe size range Approximately 13 mm to 6000 mm OD, transducer-dependent
Fluid types Water, seawater, glycol mixtures, oils, most homogeneous liquids; not for gases or aerated streams
Flow accuracy (typical) ±1% to ±3% of reading, installation-dependent
Power Internal rechargeable battery, mains adapter for bench setup
Data storage Internal logger, downloadable via the wired communication port
Operating temperature (transmitter) Approximately -10 °C to +50 °C; verify on nameplate
Enclosure Portable IP-rated transit case
Output Wired communication port for PC download; on-board display for local readout

FAQ

What is the minimum straight-pipe run required for an FUP1010 survey?

10 diameters upstream and 5 diameters downstream of the nearest flow disturbance is the working minimum. For severely disturbed profiles (pumps, double elbows) increase to 20D upstream and 10D downstream.

Why does the FUP1010 read 0.0 with no flow in the pipe?

That is the expected verification reading. The meter has captured a clean zero. Confirm signal strength and signal-to-noise ratio are healthy before trusting the zero as a true zero condition.

Is couplant gel required for clamp-on ultrasonic measurement?

Yes. Couplant displaces the air between the transducer face and the pipe wall. Without it, ultrasonic energy is reflected at the air interface and the meter cannot acquire signal.

Can the FUP1010 measure flow on a plastic pipe?

Yes, provided the pipe is full and the fluid is reasonably homogeneous. Enter the pipe material as PVC or HDPE in the pipe data menu and use W-mount if the pipe is large.

What is the difference between V, Z, and W mounting modes?

V-mount places both transducers on the same side of the pipe with one reflection off the far wall and is used on 50 mm–300 mm pipes. Z-mount places them on opposite sides for direct through-path on small pipes under 50 mm. W-mount uses two reflections on the same side for large pipes over 300 mm or for attenuative and lined walls. The FUP1010 calculates the required transducer spacing for the mode selected.

What causes the FUP1010 to read 10%–30% low on cement-lined ductile iron?

Most often, the lining material and thickness have not been entered in the pipe data menu. Cement-mortar lining adds 6 mm–12 mm of acoustic travel time; failing to declare it produces a systematic low reading in that range.

Back to blog