Problem Description
When an S7-300 station equipped with a CP 342-5 communications processor is integrated into a SIMATIC PCS 7 V7.1 multiproject and the Engineering Station (ES) is running STEP 7 V5.5, the download icon (the PLC target-system download shortcut in the LAD/FBD/STL editor and in the block folder) is no longer active for the S7-300 CPU. Under STEP 7 V5.4 SPx the same configuration, the same project structure, and the same CP 342-5 wiring still allow the engineer to select PLC → Download directly to the S7-300 target system.
The visible symptom is one of the following:
- The toolbar download button is grayed out while the S7-300 is shown online reachable in the Accessible Nodes dialog.
- Right-click context menu on the S7 Program node shows Download as unavailable.
- Selecting PLC → Compile and Download Objects reports Target system cannot be identified.
- The Target system / PG-PC assignment dialog (Menu Options → Set PG/PC Interface) lists the CP 342-5 as online-capable, but the project download is refused.
The root cause is the project-type classification of the master project inside the SIMATIC Manager, combined with the way PCS 7 V7.1 protects subordinate S7-300 stations that were inserted as STEP 7 subprojects. The project-type property "PCS 7" versus "STEP 7" controls which download mechanisms are exposed to the editor; in PCS 7 mode the S7-300 is treated as an AS (Automation Station) subordinate to the OS, and the classic single-station download path is suppressed.
Affected Software Versions
| Component | Versions Showing the Fault | Versions Working |
|---|---|---|
| STEP 7 | V5.5, V5.5 SP1, V5.5 SP2, V5.5 SP3, V5.5 SP4 | V5.4 SP3, V5.4 SP4, V5.4 SP5 |
| PCS 7 | V7.1, V7.1 SP1, V7.1 SP2, V7.1 SP3, V7.1 SP4 | V7.0 SP3, V7.0 SP4 |
| CP 342-5 firmware | All released firmware versions (function is host-side, not module-side) | All released firmware versions |
| PC-Adapter USB | STEP 7 V5.5+ integrates the driver natively (no separate install required) | STEP 7 V5.4 required separate PC-Adapter USB driver |
Per the official STEP 7 Compatibility List (Siemens Support, entry ID 109810730), STEP 7 V5.5 and V5.6 integrate the functionality of the PC-Adapter USB directly, so drivers no longer have to be installed manually to operate the adapter. The adapter detection is therefore not the cause of a missing download icon, but it is a frequent red herring during troubleshooting.
Root Cause Analysis
Two interacting mechanisms cause the missing download icon:
- Project-type property in SIMATIC Manager. A PCS 7 multiproject is flagged with the Project type = PCS 7 attribute. Child stations that are pure S7-300 projects inserted into the multiproject inherit PCS 7 protection, and STEP 7 V5.5 enforces a stricter check on whether a single-station LAD/FBD/STL download is allowed. Under STEP 7 V5.4 the check was permissive; under V5.5 it returns download disabled unless the project type is changed to "STEP 7". The menu Project → Properties → Project type does not allow demotion from PCS 7 to STEP 7 in a multiproject that already has an AS-OS coupling.
- NetPro connection topology for cross-station download. The ES does not download directly to the CP 342-5 over MPI/DP; it needs an S7 connection between the ES (the PG/PC in NetPro) and the S7-300 station. If the S7-300 lives in a separate STEP 7 subproject that is referenced from the PCS 7 multiproject, the connection must be created as an S7 connection across projects (cross-project S7 connection in NetPro). When that connection is missing, the Target system object of the S7-300 S7 Program node has no resolvable route, and the download shortcut is greyed out.
The combined effect is that the editor cannot resolve which S7-300 should receive the blocks because (a) the project type forbids single-station download inside a PCS 7 master, and (b) the cross-project S7 connection is not in place to give it an alternate route.
Diagnostic Procedure
- Open SIMATIC Manager with the multiproject that contains the PCS 7 master and the S7-300 subproject.
- Right-click the multiproject root → Properties. Confirm that Project type is PCS 7. Note that you cannot change it from here while AS-OS coupling exists.
- Select the S7-300 station → Edit → Open Object on the S7 Program node. Open the LAD/FBD/STL editor on any block. Observe whether the download icon in the toolbar is greyed out.
- Open Options → Set PG/PC Interface. Confirm the access point S7ONLINE is set to a usable adapter (e.g. PC-Adapter (Auto), TCP/IP → Broadcom NetXtreme ... for CP 443-1 routing, or the CP 5611 / CP 5621 PROFIBUS entry if the ES is on PROFIBUS).
- Open Options → PG/PC Assignment for the S7-300 S7 Program node and check whether a target CPU is assigned. A blank assignment together with a greyed-out toolbar confirms the route is unresolved.
- Open NetPro for the S7-300 subproject (Options → Configure Network). Check whether an S7 connection to the ES (or to the S7-400 AS that sits in the PCS 7 master) is configured. A missing or incomplete connection entry reproduces the symptom.
- From a Windows command line on the ES, run
ping <CP443-1 IP>andping <CP342-5 routed IP>to confirm IP reachability through the S7-400 backplane (when the path is Industrial Ethernet on the OS side, PROFIBUS on the AS side). - Open PLC → Accessible Nodes on the S7-300 subproject. If the S7-300 CPU is listed with its PROFIBUS or Ethernet address, the physical layer is good and the problem is strictly project-side.
Solution A: Re-Structure the Multiproject
This is the solution recommended in the SIMATIC community knowledge base for sites that can separate the S7-300 and S7-400 control layers into different physical/logical projects. The S7-300 then becomes a normal STEP 7 project and the full download icon set is restored.
- In SIMATIC Manager, select the multiproject → File → Multiproject → Adjust → Separate Project from Multiproject. Choose the S7-300 station (or the BHAS4Cent cluster of S7-300 PLCs) and confirm.
- Open the separated project and verify Project → Properties → Project type shows STEP 7. If it still says PCS 7, demote the project type explicitly (this is only possible when the project has no AS-OS coupling artefacts and no CFC/SFC charts).
- Re-insert the separated S7-300 project into a fresh STEP 7 multiproject that also contains the S7-400 master (Insert → Station → SIMATIC 300 Station). This keeps the S7-400 and S7-300 in the same multiproject without forcing the S7-300 to inherit PCS 7 properties.
- Open NetPro and add an S7 connection from the S7-400 to the S7-300 (and from the ES PG to the S7-300). The connection type is S7 connection for MPI/PROFIBUS, and S7 connection (TCP/IP) when the ES reaches the S7-300 over the CP 443-1 routed path.
- Compile NetPro (Network → Save and Compile). Download the connection configuration to the S7-400 first, then to the S7-300.
- Open the LAD/FBD/STL editor on the S7-300. The download icon should now be active. Verify with PLC → Download.
Solution B: Keep the PCS 7 Master and Configure Cross-Project S7 Connections
When the S7-300 must remain inside the PCS 7 multiproject because the S7-300 and S7-400 exchange process data on a shared PROFIBUS segment (for example a shared DP slave such as an ET 200M, a SIMOCODE, or a SINAMICS drive), re-structuring is not an option. The supported path is to keep the multiproject structure and configure the connection correctly in NetPro.
- In SIMATIC Manager, open the S7-300 subproject and the S7-400 subproject side by side.
- Open NetPro for the S7-300 subproject (Options → Configure Network).
- Right-click the CP 342-5 in the S7-300 station → Insert New Connection. In the connection dialog select the partner as (unspecified) and the connection type as S7 connection.
- Open the partner's project (the PCS 7 master) in a second SIMATIC Manager instance. In the S7-400 station select the CP that is the physical gateway to the CP 342-5 (typically CP 443-1 for routed PROFINET → Industrial Ethernet, or the integrated DP interface of the S7-400 CPU if the path is direct PROFIBUS).
- Return to the S7-300 NetPro, double-click the new S7 connection. Set the partner to point at the S7-400 CPU by entering its MPI, PROFIBUS, or IP address manually. Tick Establish an active connection if the S7-300 initiates the data exchange.
- In the S7-400 NetPro confirm that the mirrored S7 connection appears on the CP 443-1 (or DP interface). Save and compile both NetPro instances.
- Download the connection table to the S7-400 first, then to the S7-300.
- Open the LAD/FBD/STL editor on the S7-300 blocks. The download icon will now resolve the target via the cross-project S7 connection.
Refer to chapter 10.8 Networking Stations from Different Projects of the SIMATIC Configuring Hardware and Communication Connections STEP 7 V5.5 manual (entry 18652656 on Siemens Support) for the official procedure. The same procedure is documented in the PCS 7 V7.1 manual PCS 7 Engineering System (entry 27013355).
Solution C: Demote the Project Type in Place (Use With Caution)
For stand-alone S7-300 stations that were inserted as STEP 7 subprojects into a PCS 7 multiproject and that have no AS-OS coupling and no CFC/SFC charts, the project type can be demoted. Do not use this procedure if the S7-300 contains PCS 7 library blocks, SFC instances, or if the OS references the S7-300 program for operator control and monitoring.
- Open SIMATIC Manager with the S7-300 subproject.
- Right-click the S7-300 project → Properties → Project type.
- Change the project type from PCS 7 to STEP 7. Confirm the warning dialog.
- Re-open the LAD/FBD/STL editor. The download icon is restored.
Verification
- In the LAD/FBD/STL editor, open any block on the S7-300. The download icon in the toolbar is no longer greyed out.
- Right-click the S7 Program → Download. The download dialog reports Download to target system completed without error.
- Open PLC → Monitor/Modify on a known tag (e.g.
DB100.DBD0) to confirm the online view is live. - Open PLC → Accessible Nodes. The S7-300 CPU is listed with the correct PROFIBUS or IP address, online status is green.
- From the S7-400 station, perform a PLC → Download on a small modification to verify that the S7-300 ↔ S7-400 data exchange is not broken by the re-structure.
Related PC-Adapter USB Note (STEP 7 V5.5 / V5.6)
Per the official STEP 7 Compatibility List (Siemens Support, entry 109810730):
- The functionality of the PC-Adapter USB (6ES7 972-0CB20-0XA0) is integrated in STEP 7 V5.5 and V5.6.
- No separate driver install is required — Windows Plug-and-Plug enumerates the adapter and the S7ONLINE access point picks it up automatically.
- The PC-Adapter USB appears in Set PG/PC Interface as PC-Adapter (Auto), PC-Adapter (MPI), or PC-Adapter (PROFIBUS).
- USB-C and USB-A variants (6ES7 972-0CB35-0XA0) are supported on the same integrated driver in V5.5/V5.6.
If the download icon is missing but the adapter is recognised, the cause is project-side (Solutions A/B/C above) and not driver-side. A common field mistake is to install the legacy V5.4 PC-Adapter driver on a V5.5 ES, which collides with the integrated driver and can mask the CP 342-5 as reachable while the LAD/FBD/STL editor still refuses to download.
Troubleshooting Matrix
| Symptom | Likely Cause | Confirm With | Fix |
|---|---|---|---|
| Download icon greyed out, accessible nodes shows the CPU | Project type = PCS 7 in S7-300 subproject | Project → Properties → Project type | Solution A or C |
| Download icon greyed out, accessible nodes empty | PG/PC interface mismatch or PC-Adapter driver conflict | Set PG/PC Interface, Device Manager | Re-select S7ONLINE access point; uninstall legacy driver |
| Download fails with SF on CP 342-5 | PROFIBUS segment terminated incorrectly | Diagnostic buffer of CP 342-5 | Enable bus terminators at segment ends; check shield grounding |
| Download works from ES but S7-400 cannot see S7-300 tags | Cross-project S7 connection not compiled / downloaded | NetPro on both projects, Connection status online | Solution B: configure and download S7 connection |
| NetPro refuses to connect the S7-300 to the S7-400 in different projects | Partner address not entered manually; SIMATIC Manager needs a path to the partner project | Insert → Station → Other Station → S7-400 placeholder in S7-300 project | Use "unspecified" partner, fill in MPI/DP/IP address manually |
| Download icon appears after Solution A, but operator screens lose S7-300 tags | S7-300 was an AS for the OS; the S7-300 must stay in the PCS 7 project | WinCC Explorer tag list, OS server assignment | Undo Solution A; use Solution B (cross-project S7 connection) |
| Error "Target system cannot be identified" on download | Multiple S7-300 stations in the multiproject and PG/PC assignment is ambiguous | PLC → Assign PG/PC | Assign target CPU explicitly per station |
| Download works under V5.4, fails after upgrade to V5.5 | V5.5 tightened the project-type check | Compare project archive with V5.4 baseline | Apply Solution A, B, or C |
Field-Proven Caveats
- The CP 342-5 supports PROFIBUS-DP master and slave, not S7 communication in the same way as the integrated MPI/DP interface of an S7-300 CPU. The S7 connection used for download must be terminated on the CP 342-5 module, not on the CPU. Mis-targeting the S7 connection to the CPU MPI/DP interface is a common reason the editor cannot resolve the route.
- When the S7-300 sits behind an S7-400 (e.g. a CP 443-1 on the S7-400 side and a CP 342-5 on the S7-300 side with PROFIBUS between them), the ES download is a routed download. The S7ONLINE access point on the ES must be a TCP/IP access point that can reach the CP 443-1 first; the routed path is then resolved by the S7-400 acting as a router.
- PCS 7 V7.1 with STEP 7 V5.5 introduces a stricter integrity check on the AS-OS connection table. If the S7-300 subproject is not referenced by the OS server, the S7-300 can be safely extracted (Solution A). If the OS references the S7-300 program, use Solution B.
- STEP 7 V5.5 SP3 and later include a project-type sanity check that warns when the S7-300 subproject has CFC/SFC charts. Do not override the warning without removing the charts first.
- The STEP 7 V5.5 SP4 release notes (Siemens Support, entry 109810730) explicitly call out the change in download behaviour for S7-300 stations inside PCS 7 V7.1 multiprojects. The recommended migration path is the NetPro cross-project S7 connection procedure (Solution B above).
Edge Case: S7-300 with CP 343-1 (Ethernet Path)
If the S7-300 is fitted with a CP 343-1 (6GK7 343-1EX11-0XE0 or 6GK7 343-1CX10-0XE0) rather than a CP 342-5, the same symptom can occur, but the fix is simpler:
- Add the CP 343-1 IP address to the ES as a reachable node in Accessible Nodes over TCP/IP.
- In the S7-300 subproject, assign the S7ONLINE access point to the TCP/IP adapter pointing at the CP 343-1.
- The download icon activates immediately — the project-type check is bypassed because the S7 connection terminates on the CP 343-1 directly.
This is the preferred path on greenfield projects. The CP 342-5 path in this article is specifically the legacy PROFIBUS route that surfaces the project-type bug.
Recommended Long-Term Architecture
For sites that have one S7-400 PCS 7 AS and several S7-300 satellite PLCs (e.g. centrifuge package PLCs, MCC PLCs, or skid PLCs from third-party OEMs), Siemens recommends the following:
- Keep the S7-400 in the PCS 7 master multiproject.
- Place each S7-300 in its own STEP 7 subproject and link the subprojects into the multiproject as STEP 7 projects (not PCS 7 projects).
- Use NetPro to create S7 connections from the S7-400 to each S7-300 over PROFIBUS or PROFINET.
- Expose the S7-300 tags to the PCS 7 OS via the S7-400 using Process Tags (PCS 7 V7.1+ supports indirect tag exposure through the AS).
This architecture avoids the project-type collision, gives each S7-300 an independent STEP 7 download path, and keeps the PCS 7 AS-OS coupling isolated to the S7-400.
FAQ
Why is the download icon missing in STEP 7 V5.5 but present in V5.4 for the same S7-300 in a PCS 7 V7.1 multiproject?
STEP 7 V5.5 tightened the project-type check. When the S7-300 subproject inherits the PCS 7 project type from the master multiproject, V5.5 disables the single-station LAD/FBD/STL download shortcut. V5.4 was permissive and allowed the download anyway. The fix is either to demote the S7-300 subproject to a STEP 7 project type (Solution A or C) or to configure a cross-project S7 connection in NetPro (Solution B).
Can I download LAD/FBD/STL to the S7-300 over the CP 342-5 without changing the project structure?
Yes, if you create an S7 connection in NetPro that terminates on the CP 342-5 (not on the CPU MPI/DP interface) and if the partner address (the CP 443-1 or the S7-400 DP interface) is reachable from the ES. The connection is configured as S7 connection with the partner as (unspecified) and the address filled in manually. Compile and download the connection table to both stations before attempting a block download.
Do I need a separate driver for the PC-Adapter USB on STEP 7 V5.5?
No. Per the official STEP 7 compatibility list (Siemens Support, entry 109810730), the PC-Adapter USB driver is integrated in STEP 7 V5.5 and V5.6. Windows Plug-and-Play enumerates the adapter and the S7ONLINE access point picks it up automatically as PC-Adapter (Auto), PC-Adapter (MPI), or PC-Adapter (PROFIBUS). Installing a legacy V5.4 driver on a V5.5 ES can cause conflicts and is not recommended.
What is the order number of the CP 342-5 used in this scenario?
The CP 342-5 PROFIBUS-DP master/slave module for the S7-300 is 6GK7 342-5DA02-0XE0 (electric RS-485) and 6GK7 342-5DF00-0XE0 (fibre-optic). Both variants behave identically for the S7 connection used for download. The CP 342-5 does not provide a separate programming interface — the S7 connection for the ES must terminate on the module itself.
What happens if I demote a PCS 7 S7-300 project to STEP 7 in place?
The project type change in SIMATIC Manager is one-way. If the S7-300 carries CFC/SFC charts, AS-OS coupling, or PCS 7 library blocks, demoting the project type removes the PCS 7 protection and can leave residual artefacts that fail to compile under STEP 7. Always back up the project (File → Archive) before attempting the demotion, and prefer Solution A (separate subproject) or Solution B (cross-project S7 connection) for production systems.