Surge Arresters: Failure Risk Is Managed, Not Avoided

Stefan Weidner10 min read
Other ManufacturerTechnical ReferenceWiring & Electrical
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Surge arresters reduce the probability that a conducted or induced overvoltage will damage essential plant equipment. They do not normally trip a generating unit merely because they are installed. The trip risk appears when a failed arrester becomes a low-impedance fault and its isolation scheme also removes the panel, an essential motor feeder, or a common auxiliary supply.

Follow the surge path from the initiating event to the process consequence: lightning or a grid event produces an overvoltage; the yard, building conductors, earthing system, and panel feeders carry or couple that energy; the arrester diverts it; protective devices clear any arrester failure; the essential boiler fan or turbine hydraulic regulation pump either remains available or trips. For the reported plant, two turbo-alternators export 75 MW into a grid averaging about 500 MW. That export equals 15% of the stated grid load. A 45 MW unit therefore deserves a protection design that treats both surge damage and arrester failure as credible initiating events.

Where can the surge enter the auxiliary system?

Start at the physical layer. Lightning rods protect structures by providing an intended interception and discharge path. Yard arresters limit overvoltages at their installed voltage level and location. Neither function automatically limits the voltage reaching every 400 V or 690 V panel. Transients can enter on power conductors, control cables, instrumentation circuits, communication shields, and bonding paths. Nearby strokes can also induce voltage without a direct strike to the building.

Trace every connection crossing from the yard into a building and from one earthing zone into another. Record the source transformer, feeder route, cable length, shield termination, panel earthing conductor, neutral arrangement, and connected essential loads. Look for long parallel runs, large conductor loops, weak bonds, and separate metal systems joined only through equipment. An arrester cannot compensate for a discontinuous protective conductor or an uncontrolled return path.

Check: the one-line diagram and physical inspection must identify an uninterrupted path from each incoming conductor, through the proposed arrester, to the panel earth or bonding point.

What does the 400 V and 690 V recommendation require?

The lightning study recommends arresters inside the 400 V and 690 V low-voltage panels. Convert that recommendation into defined installation points rather than treating it as a general instruction to place a device somewhere in each enclosure. Mark whether protection is required at the building entrance, transformer secondary, main switchboard, motor-control panel, or directly beside a critical load.

Protection point What it limits Primary design question Acceptance check
Yard or incoming supply High-energy surge entering from the grid or exposed conductors Does its protected zone include the building feeder? Confirm the actual cable and earthing path on the one-line diagram.
400 V or 690 V panel Residual and locally induced voltage at the distribution boundary Can the arrester discharge without opening the complete panel supply? Trace the arrester branch and its disconnecting device.
Critical equipment connection Voltage appearing at a sensitive motor drive, controller, or auxiliary circuit Does conductor length from the panel allow an unacceptable voltage difference at the load? Measure the route and compare the equipment withstand data with the arrester coordination study.

Panel-level protection uses fewer, larger devices and centralizes inspection and spares. Load-level protection can shorten the protected connection and separate critical equipment, but it increases device count, installation work, spare variants, and space requirements. Use layered protection when the panel boundary and the equipment terminals cannot be treated as the same electrical point.

Check: every recommended location must have a stated protected zone and a named downstream load; no location should rely solely on the presence of lightning rods or yard arresters.

How should each arrester be selected?

Do not select a shunt-connected low-voltage arrester from the total motor running current alone. Normal load current does not flow through a parallel arrester. Selection instead depends on the system voltage and grounding arrangement, maximum continuous voltage at the connection, temporary overvoltage exposure, surge duty, protective level, available fault current, required upstream protection, and the withstand level of downstream equipment. If a device contains a series element, its continuous-current rating becomes a separate requirement.

Input Known value Decision it controls
Nominal panel voltage 400 V or 690 V Arrester voltage class; nominal voltage alone is insufficient.
Grounding and conductor arrangement Read from the transformer and one-line diagram Connection mode and voltage seen by each protection path.
Maximum continuous and temporary overvoltage Obtain from the power-system study Whether the arrester remains stable during normal and abnormal system voltage.
Prospective short-circuit current Read at each panel bus Fault withstand and coordination of the arrester disconnect and upstream protective device.
Protected equipment withstand Read from equipment documentation Required protective level after connection and lead effects.
Criticality Boiler fans and turbine hydraulic regulation pumps are identified as essential Need for branch isolation, alarm supervision, redundancy, or load-level protection.

Obtain the permitted backup protective device, connection arrangement, status indication, and end-of-life behavior from the selected manufacturer’s documentation. A device suitable for one grounding arrangement can be incorrectly stressed on another even when the panel voltage label appears compatible.

Check: the approved datasheet and study must agree on voltage, connection mode, available fault current, backup protection, protective level, and downstream withstand.

How can arrester failure avoid a 45 MW unit trip?

An arrester is normally high impedance. During an overvoltage it conducts surge current toward the bonding system, then returns to its nonconducting state. Repeated stress, excessive temporary overvoltage, thermal degradation, or an event beyond its duty can produce an open-circuit loss of protection or a low-impedance failure. The latter can operate a fuse, breaker, or other disconnecting device.

Observed condition Likely mechanism Required response
Arrester status indicates failed, panel remains energized Internal or dedicated disconnect isolated the failed protection element Alarm, replace the device, and record the initiating event.
Dedicated arrester branch opens Low-impedance arrester failure cleared selectively Confirm the essential bus and motor feeders remain energized.
Main panel device opens with arrester failure No selective isolation, excessive fault duty, or incorrect protection coordination Recalculate fault current and revise branch and upstream coordination.
Equipment fails while arresters appear healthy Unprotected entry path, excessive connecting-lead voltage, unsuitable protective level, or lost bonding path Trace the complete surge loop and compare terminal voltage exposure with equipment withstand.
Nuisance operation during normal voltage conditions Incorrect voltage selection, grounding mismatch, or sustained overvoltage Measure system voltage and neutral-to-earth behavior before replacing the device.

The reported concern that any panel arrester failure will trip one 45 MW unit identifies a single-point vulnerability. Put the arrester on a connection that can be isolated selectively, while retaining the manufacturer-required overcurrent protection and conductor arrangement. The dedicated device must clear the arrester fault before an upstream device removes the essential panel. Redundant auxiliaries only reduce unit-trip risk when they do not share the same vulnerable panel, feeder, or protective device.

Check: the protection study must demonstrate that the specified arrester failure path is cleared by its intended disconnect without removing every essential auxiliary needed by the 45 MW unit.

How should the panel connection be installed?

Connection geometry is part of the protection function. Surge current produces voltage across conductor impedance, so long or looped leads raise the voltage appearing at the protected bus. Keep the line-side and earth-side paths direct, avoid unnecessary bends and loops, and bond to the intended panel earth point. Separate the arrester conductors from protected outgoing circuits so diverted current does not couple back into them.

  1. Isolate the panel under the plant switching procedure and prove the required conductors de-energized.
  2. Verify the panel voltage, conductor arrangement, grounding method, and prospective short-circuit current against the approved design.
  3. Mount the arrester and its specified disconnecting or backup protective device at the approved connection point.
  4. Route phase, neutral when applicable, and earth connections exactly as shown in the approved manufacturer arrangement.
  5. Make each surge-current path short and direct, using conductor sizes and terminations from the approved design.
  6. Connect remote status contacts to the plant alarm system when provided, and use an alarm description that identifies the affected panel and loss of surge protection.
  7. Inspect polarity or terminal assignment, torque, bonding continuity, clearances, and enclosure segregation before energization.
  8. Energize the panel, inspect the local status indication, and verify that no arrester branch or upstream protective device operates.

Check: the as-built drawing, conductor inspection, local indication, and alarm point must all identify the same installed device and connection point.

What commissioning tests prove selective operation?

Commissioning must test both protection availability and failure containment. Do not create a real high-energy surge or short an installed arrester. Use the manufacturer’s approved status test, secondary testing of alarm circuits, and protection-study methods for fault selectivity.

  1. Record normal phase-to-phase and applicable phase-to-neutral or phase-to-earth voltages at the panel. Compare them with the approved arrester voltage selection.
  2. Verify protective-conductor and bonding continuity using the site’s approved electrical test method.
  3. Operate or simulate the arrester status contact by the manufacturer-approved method. Confirm the correct control-room alarm, panel identity, and state transition.
  4. Review time-current or protection-coordination results for the calculated fault at the arrester connection. Confirm the dedicated isolation device operates before the upstream device that supplies essential loads.
  5. Test each essential motor feeder and its permissive or standby sequence after the panel work. Include the boiler fans and turbine hydraulic regulation pumps identified as critical.
  6. Restore every test link and alarm bypass, then verify normal indication locally and in the control room.

Check: commissioning is complete only when the device is healthy, its loss is alarmed, its modeled fault is selectively isolated, and every affected essential load passes its functional test.

How should condition and replacement be managed?

Inspect local status indicators and remote alarms at a defined plant interval and after a known lightning or overvoltage event. Look for operated disconnects, discoloration, heating, loose terminations, moisture, contamination, and changes to bonding conductors. Record each device location, product identity, installation date, event exposure, inspection result, and replacement.

One reported high-voltage installation replaced 115 kV polymer arresters every 10 years after consultation with its manufacturers because replacement cost less than testing. That is not a replacement interval for the 400 V or 690 V devices. Set the low-voltage interval from the selected manufacturer’s life, status, testing, environmental, and replacement instructions. Stocking strategy should account for device commonality, replacement availability, enclosure space, and the operational cost of leaving an essential panel unprotected.

Contract penalties and treatment of lightning events depend on the grid agreement and governing authority, not on the presence of an arrester alone. Retain the lightning study, selection calculations, coordination results, commissioning records, inspections, alarms, and replacements as proof that the scheme was designed and maintained.

Check: the maintenance system must show a current status and an approved replacement basis for every arrester protecting an essential panel.

What proves the complete protection path works?

Perform the final review from source to consequence. Confirm that yard protection, building entry paths, 400 V and 690 V panels, panel bonding, arrester branches, downstream critical loads, alarms, and protective-device coordination form one documented scheme. A green local indicator alone proves only the state of that device; it does not prove adequate placement, conductor routing, protective level, or selective fault clearing.

  1. Trace each credible incoming surge path on the as-built one-line and physical installation.
  2. Match every boundary to its assigned protection device and downstream protected zone.
  3. Match arrester voltage and connection data to the measured system and grounding arrangement.
  4. Match the calculated arrester fault to the dedicated disconnect and upstream coordination study.
  5. Verify local status, control-room alarm, maintenance record, and spare availability.
  6. Run the normal and standby functions of the essential auxiliaries, then confirm that all panels remain energized and both surge-protection status and plant alarms are normal.

FAQ

What happens if a surge arrester fails short circuit?

Fault current flows until an internal, dedicated, or upstream protective device opens. The design must make the dedicated arrester isolation operate selectively so the 400 V or 690 V essential panel remains energized.

What happens if the plant has lightning rods but no panel arresters?

Lightning rods provide an interception and discharge path for the structure, but conducted and induced overvoltages can still reach internal power and control conductors. Apply the lightning study’s recommended protection at the defined 400 V and 690 V panel boundaries.

What happens after the panel arresters are installed?

Verify measured system voltage, bonding continuity, healthy local status, the correct control-room alarm, selective arrester isolation in the coordination study, and operation of every affected essential motor feeder; finish by confirming the panels remain energized and all protection indications are normal.

Back to blog