Overview
Siemens LOGO! 8 logic modules accept 0-10 V signals directly on dedicated analog input terminals. A 0-10 V current transducer clamped around a motor supply conductor can be wired straight to a LOGO! AI terminal and evaluated inside LOGO! Soft Comfort (LSC) by an Analog Threshold Trigger block. When the scaled motor current crosses a programmed threshold (for example 1.25 A on a 0-20 A / 0-10 V transducer), the block raises a flag (memory bit / virtual output) that you can route to a physical Q output, a flag relay, or an upstream contactor.
This article documents the complete implementation path for a 0-10 V transducer on a LOGO! 8.FS4 base module programmed with LSC V8.1 or later. It covers hardware selection, transducer wiring, the AI channel mapping, gain/offset scaling math, the Analog Threshold Trigger parameters, hysteresis, the FS4 fail-safe considerations, and an online verification procedure. The same procedure applies to the standard LOGO! 8 (non-FS) modules; FS4 simply adds a second, redundantly-monitored threshold path for safety functions.
Prerequisites
- Siemens LOGO! 8 or 8.FS4 base module, 12/24 V DC variant (e.g.
6ED1052-1MD08-0BA2for the FS4 12/24 RCE variant). The 24 V AC / 100-240 V AC variants do not provide on-board 0-10 V analog inputs; an AM2 / AM2 RTD expansion is required. - LOGO! Soft Comfort (LSC) V8.1 or later. The FS4 functionality requires LSC V8.3+ when safety blocks are used; pure threshold switching from analog input works in V8.1. Download and licensing are available from the Siemens LOGO! 8 system manual support page.
- 0-10 V output current transducer with the motor's full-scale current inside the transducer's primary range (for a 0-20 A / 0-10 V device, the 1.25 A threshold sits at 0.625 V on the analog input).
- 24 V DC supply for the transducer (sourced from the LOGO! sensor supply terminal U or from a separate DIN-rail PSU).
- Ethernet or micro-USB cable for downloading the program to the LOGO! and for online monitoring.
LOGO! 8.FS4 Hardware: Analog Input Channels
The 12/24 V DC base module provides eight digital inputs (I1 through I8). On this variant, terminals I1, I2, I3, and I4 are dual-function and can be software-configured as analog inputs AI1 through AI4 with a 0-10 V range, 10-bit resolution (approximately 9.8 mV / LSB) and a 2.5 kΩ input impedance. Terminals I7 and I8 on the high-speed base modules can additionally be used as AI5 and AI6 (also 0-10 V, but without oversampling). The analog ground reference is the M terminal on the same connector block.
For the 0-10 V current transducer, the most common wiring is:
| LOGO! terminal | Transducer lead | Signal |
|---|---|---|
| AI1 (I1) | Output (Vout) | 0-10 V motor-current image |
| M (ground) | Output ground (GND) | Analog reference |
| U (+24 V sensor supply) | Transducer +V | 24 V supply rail |
Keep the transducer output lead shielded and tie the shield to ground at one end only. The transducer's 4-20 mA variant is not directly supported on the AI terminals and would require a 500 Ω shunt, which negates the purpose of using the AI channel.
Current Transducer Selection and 0-10 V Output Wiring
For motor-current monitoring the typical choices are:
- Closed-loop (compensated) types such as the LEM LA-series or the Honeywell CSLA-series. These provide high accuracy, low offset, and a bipolar output proportional to primary current. They are 4-pendulum devices powered from ±15 V or +24 V; the bipolar output (-10 V to +10 V or -5 V to +5 V) must be shifted into the LOGO! 0-10 V window if the application monitors only unidirectional load current.
- Open-loop Hall-effect types with a built-in 0-10 V amplifier, e.g. the Phoenix Contact MCR-SL-CUC-100 or the Wago 855-4xx series. These run from a single 24 V supply and produce a 0-10 V output proportional to 0 to IPN and are the simplest match for a LOGO! AI input.
For a 0-20 A / 0-10 V transducer clamped around a single motor phase, the relation between measured current I and analog voltage VAI is linear:
V_AI = 0.5 V per ampere (since 10 V / 20 A = 0.5 V/A)
A 1.25 A threshold therefore corresponds to:
V_th = 1.25 A × 0.5 V/A = 0.625 V
This is the voltage the LOGO! AI channel will see at the trip point. If the transducer is a three-phase summation type (SUM of three phases / 0-10 V for 0-50 A), scale accordingly and label the assumption explicitly; the math changes.
Scaling the Transducer Output: Gain and Offset in LSC
LOGO! Soft Comfort stores the AI reading as a raw integer 0-1000 (each LSB = 10 mV) when AI mapping = 0-10V. The Analog Threshold Trigger block accepts thresholds in that 0-1000 range, so a 1.25 A threshold on a 0-20 A / 0-10 V transducer is:
Threshold_AI = (1.25 A / 20 A) × 1000 = 62.5 ≈ 63 LSB
If the application uses a different full-scale current, the more general form is:
Threshold_AI = (I_trip / I_fullscale) × 1000
For a non-ideal transducer with a residual offset V0 at I = 0 and a span error, apply gain and offset blocks upstream of the comparator:
AI_scaled = (AI_raw − offset) × gain
For most open-loop Hall transducers, the offset is below 1 LSB after warm-up and a unity-gain path is acceptable. Use a Gain block (LSC category: Analog → Math) for trim.
Configuring the Analog Threshold Trigger (Block 211) in LSC V8.1
- Open LSC and create a new project. Select the LOGO! 8.FS4 target hardware so the editor enables the analog AI inputs and the safety palette.
- Drag an Analog Threshold Trigger block (block number 211) from the Analog category onto the diagram.
- Connect AI1 to the Ax input of the block.
- Open the block properties and set the parameters listed below.
| Parameter | Value for 1.25 A / 0-20 A / 0-10 V | Notes |
|---|---|---|
| On threshold | 63 (≈ 0.63 V) | Where the output flips high |
| Off threshold | 50 (≈ 0.50 V / 1.0 A) | Hysteresis to prevent chattering |
| Sampling time | 500 ms (default 200 ms) | Smooth motor ripple |
| Gain | 1.0 | Default; adjust only if transducer is mis-calibrated |
| Offset | 0 | Default |
The block emits a Boolean that is 1 whenever the (gain × AI − offset) is greater than the on-threshold, and remains 1 until the input falls below the off-threshold. The difference between on and off threshold is the hysteresis band; choose at least 5 % of full scale to absorb in-rush tail-out and supply noise.
Routing the Trigger Output to a Memory Bit and a Physical Output
The Boolean at the output of block 211 can drive:
- A flag (M / memory bit) by tying it to a flag relay block (LSC: Special → Flag). Flags M1 to M27 are retained in RUN-to-STOP transitions; M8 to M27 are retained across power-cycle on the LOGO! 8 base module.
- A digital output Q1-Q4 directly. Q outputs on the 12/24 RCE variant are relay, rated 5 A / 250 V AC or 5 A / 30 V DC resistive.
- An output of an AM2 / DM8 expansion if all four base-module outputs are in use.
A typical wiring inside LSC looks like:
AI1 → [Analog Threshold Trigger] → B001 → [Flag M8] → Q1 (relay) → indicator lamp / shunt-trip coil
If the threshold must latch (sticky) until operator reset, follow the threshold output with an RS (Set/Reset) latch block from the Logic category. Wire a momentary digital input (e.g. I5) to the reset input and a normally-closed stop button to the set so that the latch can be force-cleared.
Hysteresis, Debounce, and Stability
Without hysteresis, the comparator will toggle on every sample where the AI value lands within the noise envelope of 0.63 V. A 4 mV/LSB AI quantization on a 0.5 V/A transducer corresponds to 8 mA around the 1.25 A trip, which is small but not negligible. Recommended practices:
- Use a hysteresis band of at least 5-10 % of full scale. For the 0-20 A device, that is 1.0-2.0 A wide; here we picked 0.25 A (50 LSB) which is a reasonable balance between response and stability.
- Increase the threshold-trigger Sampling time to 500 ms or 1 s for steady-state applications; the LOGO! will average a moving window of 4 samples at 250 ms intervals.
- Place a Wiping relay (off-delay) block in series with the threshold output when the load is intermittent (e.g. a pump) so brief transients do not trip the output.
- For the FS4 safety path, use the dedicated Analog Threshold Trigger for Safety block (palette appears only when the project target is FS4) and wire the AI to a redundantly-monitored second threshold path. The two thresholds are cross-checked in firmware; a discrepancy > 5 % latches a safe-state fault.
FS4 (Fail-Safe) Considerations
The FS4 variant is a Category 4 / SIL 2 / PL d capable logic module. The base unit is ordered as 6ED1052-1MD08-0BA2 (12/24 RCE F) and ships with two distinct firmware domains:
- Standard domain – the regular LOGO! 8 instruction set, including the analog threshold trigger described above.
- Safety domain – a subset of blocks (ES, AS, MS, F-BOOL, F-AN, ED) certified for safety functions up to SIL 2 / PL d. The safety blocks run in a redundant, time-sliced manner and cross-check the standard domain.
To use the threshold for a safety-rated function (e.g. safe stop on motor over-current), place the F-AN (Analog Safety Threshold) block from the safety palette and connect AI1 to its input. The block accepts the same 0-1000 raw scale. The output is a safety-flag (F-flag) that can only energise the safety-domain portion of Q1 (the only output the safety domain can directly control on the FS4 base). For non-safety signalling, the regular Analog Threshold Trigger (211) is sufficient and is the path described in this article.
Downloading and Online Verification
- Connect the LOGO! to the PC over Ethernet (preferred) or micro-USB. In LSC, choose Tools → Transfer → PC → LOGO!.
- Click Online Test (the goggles icon). The editor switches to a live view: AI1 displays the live integer 0-1000, the threshold trigger block shows its Boolean in colour (red = 0, green = 1), and each connected output indicates coil state.
- Drive the motor from rest to 1.25 A. The threshold block should turn green the moment AI1 passes 63 LSB, and the connected Q1 should energise.
- Reduce the motor load to 1.0 A. Q1 should de-energise when AI1 falls below 50 LSB, confirming hysteresis.
- Force a step change with the menu Tools → Simulation: inject a constant at AI1 of 0.625 V to confirm the block trips even without a transducer connected.
- If the project is deployed on an FS4 base unit, also exercise the safety path: open LSC's Safety View and verify the F-AN block acknowledges the same trip within 100 ms; the diagnostic log should remain empty.
Acceptance Checklist
- AI1 reads 0 LSB with the motor de-energised and the transducer clamped to its supply (no primary current).
- AI1 reads the expected LSB for a known load, e.g.
I × 50on a 0-20 A / 0-10 V transducer. - Threshold triggers within ±2 LSB of the programmed value when the load is ramped slowly.
- Output de-energises within the programmed hysteresis band on ramp-down.
- Power-cycle retention: the program comes back up with the threshold armed; the M-flag state survives because it is in the retained flag area (M8-M27).
Troubleshooting Matrix
| Symptom | Likely cause | Remediation |
|---|---|---|
| AI1 always reads 0 | Transducer is unpowered, or the +24 V sensor supply terminal U is not jumpered from the LOGO! power | Measure 24 V between the transducer +V and GND. Confirm the U/M terminal block on the LOGO! is fed from the same 24 V rail that powers the base module. |
| AI1 reads 1000 at zero current | Wrong terminal mapping; the AI channel is actually a digital input pulled up | Verify in Tools → Hardware Catalog that the target is the 12/24 V DC variant. The 230 V AC variant has no AI capability on I1-I4. |
| Threshold chatters (relay pumps) | Hysteresis too small, or AI sample time too short for the load | Widen on/off spread to ≥ 5 % of full scale, raise sampling time to 500 ms-1 s, add a wiping (off-delay) relay. |
| LSC V8.1 will not open the FS4 project | FS4 features require LSC V8.3+ | Upgrade LSC. Pure analog threshold switching from AI1 (no safety blocks) still works in V8.1. |
| Threshold does not fire even with high current | Threshold value set too high (e.g. operator entered 1000 LSB) | Recompute Threshold = I_trip / I_fullscale × 1000. For 1.25 A / 20 A this is 63, not 1000. |
| Q1 energises immediately on power-up | FS4 fault state, or output coil wired to an uninitialised M-flag | Clear the project, transfer again, and observe the LOGO! display. A flashing 'F' or 'S' in the status line indicates an FS4 domain fault; see the LOGO! display diagnostics menu. |
| AI1 reads correctly but threshold is sticky after a trip | An RS latch was placed after the threshold without a reset path | Add a digital input wired to a normally-open reset pushbutton and connect it to the latch's R input. |
| Threshold fires with 0-10 V supply but real motor load is well below 1.25 A | Transducer is summing three phases, or the wrong ratio is configured | Confirm transducer datasheet full-scale value and re-derive the LSB threshold. For a 0-50 A three-phase-sum transducer, 1.25 A total corresponds to 25 LSB, not 63. |
Alternative Threshold Blocks and Variant Notes
Beyond block 211, the LOGO! analog palette offers:
- Analog Comparator (block 212) – provides both an upper and a lower threshold with a single Boolean output, useful when you need a window comparator (e.g. trip if 0.5 A < I < 1.25 A).
- Analog Watchdog (block 213) – trips when the AI value leaves a defined band, then stays tripped until acknowledged. Useful as a latched over-current.
- Analog Max/Min (block 214 / 215) – holds the highest / lowest AI value since last reset; pair with a wiping relay to capture in-rush peaks.
- Analog Amplifier (block 223) – applies gain and offset without the threshold function; useful for scaling a 0-5 V transducer to the 0-1000 domain before a downstream threshold.
On the older LOGO! 6 and 7 generations the AI terminals were I7 and I8 and the AI mapping was 0-10 V / 4-20 mA switchable; the same procedure applies with the appropriate I/O rename. On the LOGO! 8 base modules without an FS designation, the safety palette is greyed out and the regular Analog Threshold Trigger is the only legal path.
FAQ
What LSB value should I enter for a 1.25 A threshold on a 0-20 A / 0-10 V transducer?
Use 63. The LOGO! AI channel maps 0-10 V to the integer range 0-1000, so 1.25 A is (1.25 / 20) × 1000 = 62.5, rounded to 63. Apply a hysteresis of 10-25 LSB to prevent contactor chatter.
Do I need the FS4 variant to switch a memory bit from an analog threshold?
No. The regular LOGO! 8 (12/24 RCE) is sufficient. The FS4 variant is only required if the over-current trip is part of a safety-rated function such as a SIL 2 / PL d safe stop, where the F-AN safety block and the safety domain of Q1 must be used.
Which LSC version is the minimum for this project?
LSC V8.1 supports the standard Analog Threshold Trigger (block 211) on LOGO! 8 base modules. For the FS4 safety palette and the F-AN block, upgrade to LSC V8.3 or 8.4 and select the FS4 target hardware in the project wizard.
Can I use a 4-20 mA transducer instead of a 0-10 V device?
Yes, but the LOGO! AI terminals are voltage-mode only. Convert the loop signal with a 500 Ω precision resistor to 2-10 V, or use a dedicated AM2 RTD expansion (which supports 0-10 V only). Better practice: pick a 0-10 V transducer from the start.
Why does my threshold block chitter at exactly the trip current?
The AI quantization is approximately 9.8 mV per LSB, and supply noise plus transducer ripple pushes the reading back and forth across a sharp threshold. Widen the off-threshold to at least 5 % of full scale below the on-threshold, or add an off-delay wiping relay to filter short transients.