TP 270 10" HMI Image Update: Resolving WinCC flexible OS Issues

David Krause11 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

TP 270 10" HMI Image Update: Resolving WinCC flexible OS Issues

The Siemens TP 270 10" touch panel relies on a runtime image (operating system) that is delivered with, and versioned against, a specific release of WinCC flexible (or its predecessor, ProTool). The most common field issue is the apparent absence of a required image version, for example V7.1.1.0, after installing a WinCC flexible service pack. This reference documents the exact source of the image file, the official transfer/update paths, and the corrective steps when the expected image is missing from the images directory of the engineering station.

Engineer field-note: The image is not a stand-alone downloadable artifact. It is bundled with the WinCC flexible installation media. If the expected .img file is not present, the engineering tool is either the wrong service-pack level, was installed without the HMI option, or the panel requires an update from a different version source. Treat the symptoms in the order documented below before requesting media.

1. TP 270 10" Hardware Context

The 6AV6 545-0BA15-2AX0 (TP 270 10") and 6AV6 545-0BC15-2AX0 variants are members of the SIMATIC TP 270 family of touch panels. They run a Windows CE-based runtime, load a compressed image during boot, and expose a serial (MPI/PROFIBUS DP) plus optional Ethernet interface. The image carries the boot loader, the CE kernel, the WinCC flexible Runtime, and the communication stacks for OPC, S7-MPI, S7-PROFIBUS, and PROFINET (where fitted).

Parameter Specification
Display 10.4" TFT, 256 colors, 640 x 480 px
Processor Intel StrongARM SA-1110, ~206 MHz
Memory 16 MB Flash, 16 MB RAM (expandable)
Interfaces 1x RS-232/RS-485 (MPI/PROFIBUS), 1x USB (host), 1x Ethernet (option)
Operating System Windows CE 3.0 / HMI image (V6.x and V7.x lines)
Configuration Tool ProTool/Pro V6.0 SP2+ or WinCC flexible 2004/2005/2007/2008
Image Lineage Image V6.x (ProTool) and Image V7.x (WinCC flexible)

2. Image Version Architecture and Why "7.1.1.0" Is Specific

The runtime image on the TP 270 is identified by a four-segment version string, for example V07.01.01.00. Each segment maps deterministically to the engineering tool release that produced it:

Image Version Engineering Tool Service Pack Level
V06.00.00.00 ProTool/Pro V6.0 SP2 Base
V06.00.02.00 ProTool/Pro V6.0 SP3 SP3
V07.00.00.00 WinCC flexible 2004 HF1
V07.00.00.01 WinCC flexible 2004 SP1 SP1 + HF
V07.00.01.00 WinCC flexible 2005 Base
V07.00.01.01 WinCC flexible 2005 SP1 SP1
V07.01.00.00 WinCC flexible 2005 SP1 + HF3 SP1 + HF3
V07.01.01.00 WinCC flexible 2005 SP1 + HF7 SP1 + HF7
V07.01.02.00 WinCC flexible 2007 Base
V07.01.02.01 WinCC flexible 2008 SP1 SP1

The version V7.1.1.0 (the 07.01.01.00 level) is delivered exclusively by WinCC flexible 2005 SP1 with Hotfix 7 installed. Lower service packs produce older image revisions; higher revisions (for example WinCC flexible 2007) generate image 07.01.02.00 and will refuse to down-flash a panel from 07.01.02.00 to 07.01.01.00 without an explicit cross-version restore step.

3. Why the Image File Is "Missing" in the WinCC flexible Folder

Three root causes account for the field observation that the expected image is not visible at <install_path>\WinCC flexible\Images:

  1. Wrong service-pack level installed. The engineering station was set up with WinCC flexible 2005 SP1 base or with an earlier hotfix (HF1 through HF6). These levels do not carry image 07.01.01.00 for the TP 270. Verify with Start > Programs > SIMATIC > WinCC flexible > Info; the "About" dialog lists the exact build number, for example WinCC flexible 2005 SP1 HF7 (K1.5.1.0_1.21.0.0).
  2. Custom install omitted the image set. A custom or compact install that selected only the configuration runtime will not place TP270.IMG in the images directory. Re-run the installer with Modify and confirm the option Images for Windows CE panels is enabled.
  3. Image is on the panel itself (pending update). The image does not need to be pre-deployed to disk; WinCC flexible will stream it from the installer source. If the engineer is using a runtime-only PC or a recovery environment, ProSave is the correct tool to apply the image.

4. Prerequisites Before Performing the OS Update

  • Install WinCC flexible 2005 SP1 with Hotfix 7 on the engineering station, or install the matching ProSave build that ships in \WinCC flexible\Support\ProSave.
  • Verify a valid license key is present for the TP 270 panel type under WinCC flexible > Options > License Management.
  • Connect the TP 270 to the engineering PC with a serial MPI/PC adapter (6ES7 972-0CA23-0XA0) or via Ethernet if the -2AX0 Ethernet variant is present.
  • Set the TP 270 transfer mode: Control Panel > Transfer > Enable Serial/Ethernet Transfer = On, or use the panel's manual transfer button at boot (hold the lower-right of the screen during power-up).
  • Stop any active project on the panel. Disconnect from the controlling PLC during the update if the panel is mid-cycle; a power loss during flash write will brick the device.
  • Confirm the supply voltage is stable (24 V DC ±20 %) and that the panel has been powered for at least 60 s before initiating the transfer.
Critical: The image update is destructive. Any project files, recipes, and logs on the panel are erased. Export the project and back up the panel via ProSave > Backup before performing the OS update.

5. OS Update via WinCC flexible (Project-Attached Path)

The straightforward path when a TP 270 project is open in WinCC flexible:

  1. Open the TP 270 project in WinCC flexible 2005 SP1 HF7.
  2. From the menu, select File > Transfer > OS Update (German: Datei > Transfer > Betriebssystem-Update).
  3. In the OS Update dialog, set the connection type (Serial MPI / Serial PPI / Ethernet / USB) and the target address (default MPI 1, address 1 for a fresh panel; address 0 for Ethernet direct).
  4. Click Update OS. The tool enumerates the installed images and offers the bundled 07.01.01.00 for the TP 270. Confirm the panel model and the destination.
  5. The transfer window reports the image write progress in blocks of 64 KB. Typical flash time is 4-7 minutes over MPI at 187.5 kbps; 90-150 s over Ethernet.
  6. When the dialog reports OS Update successfully completed, cycle power to the panel. The first boot may take up to 90 s while the registry is re-built.
  7. Re-transfer the project file using Project > Transfer > Transfer to Target System.

6. OS Update via ProSave (Stand-Alone Path)

ProSave is the correct choice when no project is at hand, when the engineering PC does not have a WinCC flexible install with the correct image set, or when a recovery image must be pushed from a different machine. ProSave lives at <WinCC flexible install>\Support\ProSave\ProSave.exe and is a stand-alone GUI that does not require WinCC flexible to be running.

  1. Launch ProSave as administrator.
  2. In the Device type drop-down, select TP270 10". Set the connection (Serial, Ethernet, MPI/DP, USB).
  3. Click the OS Update tab. The tool lists available image files in its search path; if 07.01.01.00 is not in the default \ProSave\Images directory, browse to \WinCC flexible\Images and select TP270.IMG manually.
  4. Click Update OS. Confirm the warning dialog about data loss.
  5. Wait for the completion banner. Power-cycle the panel.

ProSave is also the only tool that can perform a reset to factory defaults via the Restore tab, which wipes the persistent flash and reloads the bootloader-safe image partition. Use this if the panel will not complete its boot sequence after a failed update.

7. Common Error Conditions and Resolutions

Symptom Probable Cause Resolution
"Image version not compatible with panel" WinCC flexible 2005 SP1 HF7 not installed; older image is being transferred Verify build version, re-run the Hotfix 7 installer, repeat OS update
"No connection to target" over MPI Wrong MPI address, baud rate mismatch, terminator missing Set PG/PC interface to PC Adapter (MPI) at 187.5 kbps; confirm panel MPI address matches the project's transfer settings; fit a 120 Ω terminator at the last node
Transfer aborts at 30-40 % CRC error from poor cable or noise on 24 V supply Replace the MPI cable with a shielded version; check ground reference between PC and panel
"Image file is corrupt" Incomplete download of Hotfix 7, antivirus quarantine Re-download HF7, exclude the WinCC flexible install path from real-time AV scanning, re-install the image
Panel stuck on white screen after update Image written but registry not yet built; first boot not complete Wait 90-180 s. If still white, perform ProSave Restore with the same image
Boot loop, no display Wrong image variant (e.g. OP vs. TP) flashed Re-flash using ProSave and confirm TP270 (not OP270) is selected. Do not power-cycle mid-write
License missing after update Image refresh overwrote the license key partition Re-import the license via ProSave > License tab or via WinCC flexible Options > License Management > Transfer

8. Verifying a Successful OS Update

  1. After the panel reboots, open Control Panel > System > About on the TP 270. The Image Version field must read 07.01.01.00.
  2. Open the project in WinCC flexible and re-compile. The output window should report Target image version: V07.01.01.00 - compatible. A warning such as "Image on target is newer than the one shipped with this WinCC flexible version" indicates the panel is at a higher revision than the engineering tool.
  3. Transfer the project and confirm the boot logo, language switching, alarm view, and tag polling all function as before the update.
  4. For cycle-sensitive validation, monitor the MPI/DP diagnostics: Control Panel > S7-Transfer > Diagnostics should show clean bus statistics with zero retry counters and zero station failures over a 10-minute observation window.

9. Cross-Version Compatibility Matrix for the TP 270

When a plant fleet mixes panels and engineering stations, confirm the image/engineering tool matrix to avoid the situation where the panel carries a newer image than the engineering PC can produce:

Panel Image Compatible WinCC flexible Compatible ProTool Compiles Project?
07.01.01.00 2005 SP1 HF7, 2007, 2008 SP1, 2008 SP2 Not supported Yes
07.01.02.00 2007, 2008 SP1, 2008 SP2 Not supported Yes, but image will be downgraded on next OS update from older tool
06.00.02.00 2004 (with V6 image option), 2005 SP1 ProTool/Pro V6.0 SP3 Yes via V6 option in WinCC flexible

For the canonical Siemens reference on this image family, see the official entry Siemens Support Entry 21742389 - WinCC flexible Image Compatibility TP/OP 270/277. For the OS update procedure on a Windows CE panel using ProSave, see Siemens Support Entry 19701610 - Performing OS update for Windows CE panels.

10. Field-Proven Cautions and Best Practices

  • Never run a WinCC flexible install on a Windows XP/7 PC that has both ProTool and WinCC flexible present with overlapping image directories. The install order matters; ProTool should be installed first when migrating legacy projects, otherwise the older image may overwrite the newer 07.01.01.00.
  • Keep at least one engineering PC per plant with a known-good image set on a labeled, read-only network share. Use this as the canonical source for any ProSave-driven recovery.
  • After a successful update, archive the panel's Backup (created via ProSave) along with the matching WinCC flexible project .hmi file. The pair is the minimum unit to restore the panel to a known state.
  • If the panel is part of a Profinet/Profibus safety chain, plan the update for a scheduled downtime. The flash write is non-atomic from the bus master perspective and may cause the panel to drop from the configuration for 1-2 bus cycles.
  • Do not attempt to install Hotfix 7 over a WinCC flexible 2005 SP1 base that has been patched with a different interim Hotfix (HF1-HF6). Re-install the SP1 base, then apply HF7 in order. The HF7 installer is incremental and assumes a clean SP1 base.

11. Reference Procedure Summary (Command-Line Equivalent)

For engineers who script panel maintenance across a fleet, ProSave supports an unattended mode. The image transfer can be invoked from a Windows command prompt or a PowerShell wrapper:

ProSave.exe /update /device="TP270" /connection=ETHERNET /ip=192.168.0.10 /image="C:\WinCC flexible\Images\TP270.IMG" /autostart

Pair the update with a follow-up project push:

WinCCflex.exe /transfer /project="PlantLine3.hmi" /target=192.168.0.10 /overwrite

Wrap both calls in a batch file with error-level checks to provide a single-touch recovery for panels whose only symptom is a failed previous update.

Where can I download image version 7.1.1.0 for the TP 270 10"?

The image is not distributed as a stand-alone file. It is bundled with WinCC flexible 2005 SP1 + Hotfix 7 at <install>\WinCC flexible\Images\TP270.IMG. Install HF7 over the SP1 base; the image file is created during the install. Do not search for the .IMG on third-party sites - use the Siemens installer or ProSave only.

How do I update the OS of a TP 270 when the panel is in a remote cabinet?

Use ProSave over Ethernet (for -2AX0 variants with the Ethernet option) or MPI/DP. Set the panel in transfer mode, run ProSave, select OS Update, browse to the correct TP270.IMG, and start. ProSave is stand-alone and does not require WinCC flexible to be open, so it can be launched from a service laptop.

Why does the OS Update dialog in WinCC flexible not list image 07.01.01.00?

The dialog only lists images that the installed WinCC flexible version ships with. The build must be WinCC flexible 2005 SP1 HF7 (or later) for image 07.01.01.00 to be present. Open Help > About and confirm the build string; if HF7 is missing, run the hotfix installer from the Siemens support download portal.

Can I downgrade the panel from a newer image (e.g. 07.01.02.00) back to 07.01.01.00?

Yes, but the path must go through ProSave > OS Update with the older TP270.IMG file. WinCC flexible will not auto-downgrade during a project transfer. Always take a ProSave Backup before any cross-version flash.

The TP 270 shows a white screen after the OS update - is it bricked?

Not necessarily. The first boot after a flash write can take up to 180 s while the registry is rebuilt. Wait two minutes; if the display remains white, re-run ProSave OS Update with the same image. Only a panel that fails to respond to a ProSave session over both MPI and Ethernet requires an RMA.