Troubleshooting ArcPro Parameters for OSHA 1910.269 Table 7

Erik Lindqvist2 min read
Other ManufacturerSafety SystemsTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Parameter Set for the 4.0–15.0 kV Row

To reconstruct the first OSHA 1910.269 Table 7 value, use the maximum voltage in the listed range rather than the 4.0 kV lower boundary. The supplied 8,660 V source setting is consistent with converting 15,000 V line-to-line to line-to-ground: 15,000 / √3 ≈ 8,660 V. This relationship is a derived assumption; confirm that ArcPro expects line-to-ground voltage for the selected configuration.

ArcPro input Value Evidence basis
Current 5 kA Table 7 scenario
Source voltage 8,660 V Maximum 15.0 kV range boundary divided by √3
Duration 197 cycles Table 7 scenario
Arc gap 1 in ArcPro does not accept a smaller value
Minimum approach distance 2.14 ft, or 25.68 in Value used for the maximum voltage in the range
Distance to arc 23.68 in 25.68 in − 2 × 1 in
Electrode material Stainless steel Produced the expected 4.0 cal/cm² result in the reported comparison

Calculate the Distance to the Arc

Use the stated relationship between minimum approach distance, arc length, and working distance. With a 1 in arc gap and a 25.68 in minimum approach distance, the ArcPro distance input is:

Distance to arc = MAD − (2 × arc length)
                = 25.68 in − (2 × 1 in)
                = 23.68 in

Keeping the dimensional inputs in inches produced incident energy in cal/cm² in the reported workflow.

Run and Refresh the Material Comparison

  1. Enter 5 kA, 8,660 V, 197 cycles, a 1 in gap, and a 23.68 in distance.
  2. Run the calculation with copper electrodes and record the result. The reported result was 3.5 cal/cm².
  3. Select stainless steel, change another input and restore it to force recalculation, then rerun the analysis. If the result remains unchanged, exit ArcPro completely and repeat the stainless-steel run in a new session.
  4. Verify that the refreshed stainless-steel calculation returns 4.0 cal/cm², matching the expected Table 7 value reported in the evidence.

Interpret the Gap Sensitivity and Software Behavior

The arc-gap choice materially changes the result. A 2.0 in gap produced 6.5 cal/cm² in the reported comparison, versus 3.5 cal/cm² with copper and a 1 in gap. Do not mix the 2.0 in gap with a reconstruction based on ArcPro's 1 in minimum input.

The electrode-material dropdown may not immediately invalidate the previous calculation. Treat an unchanged result after switching from copper to stainless steel as a possible stale calculation, not proof that material has no effect. Force another parameter change or restart ArcPro, then verify the output.

FAQ

What ArcPro voltage duplicates the 4.0–15.0 kV Table 7 row?

Use 8,660 V for the reported reconstruction. It is derived from the maximum range voltage as 15,000 / √3 ≈ 8,660 V, assuming ArcPro expects line-to-ground source voltage.

What arc gap and distance should I enter in ArcPro?

Enter a 1 in arc gap and 23.68 in distance to the arc. The distance is 25.68 in MAD minus twice the 1 in arc length.

Why does ArcPro stay at 3.5 cal/cm² after selecting stainless steel?

The material change may not refresh the calculation. Change and restore another parameter or restart ArcPro; the reported refreshed stainless-steel result was 4.0 cal/cm².