Troubleshooting ET200SP Remote I/O Communication with ET200S CPU

David Krause18 min read
I/O ModulesSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting ET200SP Remote I/O Communication with ET200S CPU

ET200S IM151-8 PN/DP controllers fail to exchange process data with ET200SP IM155-6 PN stations when BaseUnit color coding, slot mapping, or PROFINET device-name assignment does not match the TIA Portal hardware catalog. This field guide documents the diagnostic pattern—RN LED blinking on the IM and Diag LED blinking on every I/O module—and the deterministic resolution path verified on a four-station distributed I/O network programmed in TIA Portal V11.

1. Problem Statement and Diagnostic Symptom

A SIMATIC ET200S-based controller (CPU 6ES7 151-8AB01-0AB0) is configured as PROFINET IO controller with four ET200SP stations (IM 6ES7 155-6AU00-0BN0) acting as distributed I/O. After the hardware is wired and the TIA Portal V11 project is loaded, the controller cannot establish cyclic data exchange with any of the four remote stations.

Observed LED state on every IM155-6 PN:

  • LED RN (RUN) is blinking green at ~2 Hz
  • LED ER is off
  • LED MAINT is off
  • LED LK1 or LK2 is on (physical link present)
  • LED PWR is solid green

Observed LED state on every I/O module:

  • LED Diag is blinking at ~0.5 Hz

This state matches the Siemens diagnostic pattern "station in commissioning / parameter assignment error." The PROFINET connection is physically present (LK lit), but the controller is unable to finish parameter assignment to the slots. Because the symptom appears on all four stations simultaneously, treat the issue as project-wide (TIA Portal configuration) before assuming a per-station hardware fault.

2. Reference Hardware Configuration

The original system uses the following catalog numbers, recorded for cross-reference against TIA Portal hardware catalog entries. Verify every MLFB before commissioning—Siemens re-revisions modules frequently and a V11-era project may not contain the latest article number.

Main panel (ET200S, slot 1 = CPU):

Slot Function MLFB Description
1 CPU 6ES7 151-8AB01-0AB0 ET200S IM151-8 PN/DP CPU, 192 KB work memory, PROFINET IO controller, MRP client
2 PM 6ES7 138-4CA01-0AA0 ET200S PM-E DC24V power module, 2 A load current
3 DI 6ES7 131-4BF00-0AA0 ET200S 8 DI, DC24V, P-type, sourcing input, 3 ms filter
4 DO 6ES7 132-4BF00-0AA0 ET200S 8 DO, DC24V / 0.5 A, P-type
5–10 AI (×6) 6ES7 134-4FB01-0AB0 ET200S 2 AI U/I, 16-bit, ±10 V / 0–20 mA / 4–20 mA, configurable per channel

Remote I/O 1–4 (ET200SP, each starts with one IM):

Station Slot Function MLFB Description
1 1 IM 6ES7 155-6AU00-0BN0 ET200SP IM155-6 PN ST, PROFINET device, max 32 modules per station, 1440 bytes total I/O
1 2 DO 6ES7 132-6BH00-0BA0 ET200SP DQ 16×DC24V/0.5A, P-type, BU type A0 required
1 3 AI 6ES7 134-6DH00-0BA1 ET200SP AI 4×U/I, 16-bit, ±10 V / 0–20 mA / 4–20 mA
2 1 IM 6ES7 155-6AU00-0BN0 (same IM)
2 2 DO 6ES7 132-6BH00-0BA0 (same DO module)
2 3 AI 6ES7 134-6DH00-0BA1 ×1 (4 channels)
3 1 IM 6ES7 155-6AU00-0BN0 (same IM)
3 2 DO 6ES7 132-6BH00-0BA0 (same DO module)
3 3 AI 6ES7 134-6DH00-0BA1 ×2 (two AI modules, 8 channels total)
4 1 IM 6ES7 155-6AU00-0BN0 (same IM)
4 2 DO 6ES7 132-6BH00-0BA0 (same DO module)
4 3 AI 6ES7 134-6DH00-0BA1 ×1 (4 channels)

Compare against the current SIMATIC ET 200SP catalog and product overview when verifying module revisions. The IM155-6AU00-0BN0 is the standard (ST) PROFINET interface, not the high-feature (HF) variant. If your project enables HF-only features (shared device, S2 system redundancy, MRP manager, iPAR server), the configured IM is wrong and the station will reject parameter assignment even with valid slots.

3. LED Diagnostic Reference for IM155-6 PN

The IM155-6AU00-0BN0 has four status LEDs (PWR, RN, ER, MAINT) plus two link LEDs (LK1, LK2). Use the following table to decode observed LED states:

PWR RN ER MAINT LK1/LK2 Meaning First Action
On green Off Off Off Off No PROFINET connection, no L+ on load voltage, or no configuration loaded Check 24 V supply and PROFINET cable
On green Blinking green ~2 Hz Off Off On Station in commissioning mode (no AR established) or firmware update in progress Assign device name; wait for FW update to complete
On green On green Off Off On Station OK, cyclic data exchange active No action; healthy state
On green Blinking green On red Off On Parameter assignment error: module mismatch, BaseUnit mismatch, or wrong GSDML Compare offline/online; verify BaseUnits
On green Off On red Off On No configuration, station failure Recompile and redownload HW config
On green On green Off On yellow On Maintenance demanded (e.g., port error, channel diagnostic pending) Open diagnostic buffer; resolve channel fault
On green Blinking green alternating with PWR Off Off Off Firmware update in progress on IM itself Wait; do not power cycle
Off Off Off Off Off No 24 V supply or polarity reversed Check power supply and fuse

The I/O module Diag LED uses the same pattern:

  • Off: module OK, parameter assignment complete
  • Flashing ~0.5 Hz: module in commissioning state or diagnostic pending (the IM has not finished parameter assignment for this slot)
  • On red: module fault, channel fault, or parameter error (this module specifically failed)

The combined pattern of "RN blinking on IM + Diag blinking on every I/O module" points to a station-wide parameter-assignment error, not an individual module failure. When the cause is a single bad slot, only that module's Diag LED is on solid; the others stay off. Station-wide flashing indicates a structural issue at the IM or the load-group level.

4. Root Cause Catalog

When the symptom set above appears on all four remote stations simultaneously, the most probable causes are ranked by field frequency:

  1. BaseUnit color-coding mismatch (white BaseUnit placed where dark grey is required, or vice versa). Most common field error when migrating from ET200S-style terminal blocks to ET200SP BaseUnits.
  2. PROFINET device name not assigned to the IM155-6. The controller cannot establish an Application Relationship (AR) without a matching name, and the IM stays in the "blinking RN" state indefinitely.
  3. Slot / empty-slot configuration mismatch. A slot is occupied in TIA Portal but empty in the real rack, or the real slot is filled with a different module type or order than the project shows.
  4. Firmware update in progress. The IM and I/O modules flash in sequence during a station-wide firmware update; this is normal behavior and resolves on its own after 2–10 minutes.
  5. GSDML file revision mismatch. The HW catalog in TIA Portal V11 may not contain the exact firmware revision of the physical module, and the wrong version is being loaded—producing a "module does not match expected type" diagnostic event.
  6. Power supply sequencing. The 24 V load voltage (L+) is missing on the first BaseUnit of a load group, or the dark/light BaseUnit wiring is inverted (L+ on the wrong terminal).
  7. Watchdog time too short. If the project sets a PROFINET watchdog of 1–3 ms but the controller and four stations cannot complete the parameter handshake in that window, the controller aborts the AR and reports the IM as failed.
  8. Shared-input / shared-output misconfiguration. The ST variant of IM155-6 does not support shared device. If the project imports HF parameters from a GSDML, the IM rejects them.

If the same symptom appears on all four stations, treat the issue as project-wide (TIA Portal configuration) before checking per-station hardware. Begin with the most common cause (BaseUnit color) and work down the list.

5. BaseUnit Color Coding and Load-Group Construction

ET200SP BaseUnits (BU) are mechanically and electrically distinct. The physical color of the spring-release bar encodes the load-group role:

  • White (light) release bar: BU type A0, B0, C0, D0. Starts a new load group. Provides a new feed-in path for 24 V L+ and 24 V AUX. The first BaseUnit to the right of the IM155-6 must be white.
  • Dark grey release bar: BU type A1, B1, C1, D1. Passes the L+ supply through to the next module. Does not start a new load group. Used for slot gaps and mid-group positions.

The electronic coding of the BaseUnit (the white plastic key on the left side of each BU) is read by the I/O module at insertion. If the I/O module expects a "with AUX" or "with infeed" BaseUnit but the physical slot has a "pass-through" BaseUnit, the module reports a configuration error. TIA Portal V11 enforces this; if the project has a different BU type than the physical rack, the offline/online compare shows a yellow conflict on that slot.

Verification in TIA Portal:

  1. Open Devices & Networks, click the ET200SP station.
  2. Right-click the BaseUnit in the device view, choose Properties.
  3. On the General tab, confirm the BU type matches the physical BaseUnit's part number (printed on the side label).
  4. On the Potential group tab, confirm "New potential group" is checked only on the first white BaseUnit after the IM. All other BaseUnits in the station must show "Continue potential group."
  5. Compile the project (Project → Compile all) and verify the device view shows no yellow or red conflict markers.
Common BaseUnit MLFBs to keep in mind:
  • 6ES7 193-6BP00-0BA0 – BU15-P16+A0+23 (white, type A0, with infeed, 2× 24 V and 1× AUX terminals)
  • 6ES7 193-6BP00-0DA0 – BU15-P16+A0+24 (dark grey, type A0, pass-through)
  • 6ES7 193-6BP00-0BB0 – BU15-P16+A0+2B (white, type B0, wider for 25 mm modules)
  • 6ES7 193-6BP00-0BD0 – BU15-P16+B0+2D (white, type B0, with AUX terminals)
If your TIA Portal slot shows "BU type A0" and the rack has a B0, every I/O module on the affected load group reports a Diag LED error. The fix is a hardware swap, not a software change.

6. System Topology and PROFINET Addressing

The four ET200SP stations hang off the PROFINET port of the ET200S CPU through a managed switch. The typical commissioning topology is:

ET200S CPU Panel 6ES7 151-8AB01-0AB0 IM151-8 PN/DP CPU PM-E + 8DI + 8DO + 6×2AI IO Controller — 192.168.0.1 MRP Client (optional) PROFINET Switch Managed, MRP-capable e.g. SCALANCE XC206-2 ET200SP Station 1 IM 6ES7 155-6AU00-0BN0 DQ16 + AI4 — 192.168.0.11 ET200SP Station 2 IM 6ES7 155-6AU00-0BN0 DQ16 + AI4 — 192.168.0.12 ET200SP Station 3 IM 6ES7 155-6AU00-0BN0 DQ16 + 2×AI4 — 192.168.0.13 ET200SP Station 4 IM 6ES7 155-6AU00-0BN0 DQ16 + AI4 — 192.168.0.14 PROFINET cable, Cat 5e, <100 m

Addressing scheme for the four ET200SP stations:

Station PROFINET Name IP Address Subnet Mask Device Name Role
1 et200sp-io1 192.168.0.11 255.255.255.0 IO Device, slot 1 (IM) + slot 2 (DQ) + slot 3 (AI)
2 et200sp-io2 192.168.0.12 255.255.255.0 IO Device, slot 1 (IM) + slot 2 (DQ) + slot 3 (AI)
3 et200sp-io3 192.168.0.13 255.255.255.0 IO Device, slot 1 (IM) + slot 2 (DQ) + slots 3–4 (2× AI)
4 et200sp-io4 192.168.0.14 255.255.255.0 IO Device, slot 1 (IM) + slot 2 (DQ) + slot 3 (AI)

The IP address is assigned automatically by the controller during the AR setup; you only need to assign the device name. The IM155-6 stores the name in non-volatile memory and retains it across power cycles.

7. Step-by-Step Resolution Procedure

Apply the steps in this order. Each step is independent; if a step's check passes, move to the next.

  1. Power down all four ET200SP stations to clear the IM diagnostic state.
  2. Compare each physical slot's BaseUnit part number against the TIA Portal device view. Replace any mismatched BaseUnit (white vs. dark grey, or A0 vs. B0 mismatch).
  3. Open TIA Portal, select the ET200SP station, and check the Potential group of every BaseUnit. Only the first white BaseUnit to the right of the IM should have "New potential group" enabled. All subsequent white BaseUnits must be changed to "Continue potential group."
  4. Compile the project (Project → Compile all) and verify the device view shows no yellow or red conflict markers on any slot.
  5. Download the hardware configuration to the ET200S CPU (Online → Download to device). Confirm the CPU is in STOP, or stop it manually if the controller permits online download.
  6. Open Online → Accessible Nodes, confirm all four IM155-6 stations appear with their MAC addresses. The MAC is printed on the front of each IM. If a station is missing, check the Ethernet cable and switch port.
  7. Assign PROFINET device names to each station. Verify the name assigned in the dialog matches the name in the project exactly (case-sensitive). For a four-station project, you can also use the PRONETA tool to assign names in batch via a CSV import.
  8. Power cycle each ET200SP station. The RN LED should transition: blinking → solid green within 5–10 seconds. The I/O module Diag LEDs should go off.
  9. If RN is still blinking after power cycle, repeat step 7 with PRONETA to confirm DCP discovery succeeds. Open the controller's diagnostic buffer; a persistent "station failure" entry indicates a GSDML or hardware revision mismatch.
  10. If the I/O module Diag LED is still flashing but the IM RN is solid green, compare the slot mapping. The most common cause is a wrong module order, a missing module between two placed modules, or a wrong BU type on a specific slot.
  11. Verify cyclic data exchange by forcing a sensor input and observing the corresponding process image bit in the CPU. The I/O area is mapped according to the slot order in TIA Portal; document the I-address and Q-address ranges in the project notes.

8. Firmware Update Sequence and Timing

The IM155-6 supports field firmware update via TIA Portal (Online → Firmware update) or via SIMATIC Automation Tool. When a station-wide update runs, the timing sequence is:

t=0 s t=30 s t=60 s t=120 s t=240 s t=300 s IM155-6 update RN blinking ~2 Hz IM reboot PWR + RN alternating DQ16 update Diag flashing per module AI4 update (×4) 30–60 s each Station OK RN solid green Firmware Update Timing (per station)

Expected durations for the module set in this project:

  • IM155-6AU00 firmware: 60–120 s
  • DQ 16×24 V (6ES7 132-6BH00-0BA0): 30–60 s per module
  • AI 4×U/I (6ES7 134-6DH00-0BA1): 30–60 s per module

Total expected time per station: 2–4 minutes for this configuration. If the RN LED continues to blink beyond 10 minutes with no progress indication, the update has stalled. Power-cycle the station and re-attempt the update from the TIA Portal Online menu. If the module is non-responsive, the SIMATIC Automation Tool can recover the IM by forcing a firmware downgrade through the TIA Portal "Update firmware" wizard.

Do not interrupt a firmware update by removing 24 V power. A partial update can leave the module in a non-bootable state. The module must complete the second-stage write to flash before the new firmware is committed. If interrupted, recovery requires either a re-attempt with the same firmware image or, in the worst case, a return-to-factory via SIMATIC memory card.

9. TIA Portal V11 Configuration Caveats

TIA Portal V11 was released in 2012 and predates many current ET200SP module revisions. Known issues with V11 against modern IM155-6 hardware:

  • HW catalog age: the V11 catalog may not contain the latest MLFB. Use "Update catalog" or import the GSDML file from the Siemens support portal before commissioning.
  • Parameter dialog reduction: module parameter dialogs in V11 may show fewer options than the module supports. Parameters set in V14/V15 may not be editable when the project is re-opened in V11.
  • IM155-6 firmware compatibility: the IM155-6 PN ST (6ES7 155-6AU00-0BN0) firmware V3.x is the first revision fully supported in TIA Portal V11 SP2 Update 5. Earlier V11 service packs may reject the device entirely.
  • GSDML import: when importing a GSDML for a module not in the V11 HW catalog, place the GSDML file under C:\Program Files\Siemens\Automation\Portal V11\Data\Hsp\ and restart TIA Portal.
  • Project portability: TIA Portal V11 projects can be opened in V13 SP1 or later, but the device view may be silently re-numbered on upgrade. Always recompile and verify slot mapping after any portal upgrade.

If a project upgrade to TIA Portal V14 or later is feasible, do so. The diagnostic buffer, online compare, and PRONETA integration are significantly improved in newer releases. The V11 release is past its support window and Siemens no longer provides SP updates for it.

10. Verification Checklist

After applying the resolution, confirm the following with TIA Portal online diagnostics and visual inspection:

Item Expected State Verification Method
IM155-6 RN LED Solid green Visual inspection on the physical module
IM155-6 ER LED Off Visual inspection
IM155-6 MAINT LED Off Visual inspection
IM155-6 LK1/LK2 On green, both ports Visual inspection; indicates physical link
I/O module Diag LED Off, every module Visual inspection on each module
PROFINET device name Matches project (case-sensitive) Online → Accessible Nodes → Properties
AR state Established Online → Diagnostics → PROFINET IO → IO Devices
Cyclic data Input values reflect field Online → Monitor/Modify → force a sensor and observe the process image
Diagnostic buffer No "Configuration error" entries Online → Diagnostics → Diagnostic buffer
Submodule status All slots "OK" Online → Diagnostics → Module information
Update time 1 ms (RT) typical, 0.5 ms (IRT) optional Properties → PROFINET interface → IO cycle

11. Troubleshooting Matrix

Symptom Likely Cause First Action
RN blinking, all Diag blinking on all four stations Project-wide BaseUnit or slot mismatch Compare TIA Portal device view against physical racks, slot by slot
RN blinking, LK off No PROFINET link Check Ethernet cable, switch port, port LED on switch
RN off, PWR off No 24 V supply Check power supply, polarity, fuse on first BaseUnit of each load group
RN on green, one Diag on red Single module parameter error Check that slot's module type, MLFB, and BU type in TIA Portal
RN on green, MAINT on yellow Maintenance demanded Open diagnostic buffer, check channel diagnostics (over-range, wire break)
RN blinking, ER on red Station failure (e.g., wrong GSDML revision) Re-import GSDML from Siemens support, recompile, redownload
RN blinking, persists > 10 min after power-up Firmware update stalled or device name wrong Power cycle, retry update, or re-assign device name with PRONETA
All four stations show identical error Project-wide issue (TIA Portal) Recompile, verify all BaseUnit color codes, check device name spelling and case
RN blinking, all modules stop responding after working for hours Watchdog timeout, network storm, or MRP topology change Check switch logs; verify PROFINET watchdog > 3× update time
RN solid green but inputs read 0 Channel-granular diagnostics swapped for process data, or wrong I-address range Check address overview in TIA Portal; verify I-address map in the project

12. Resolution Flowchart

IM155-6 RN blinking + Diag blinking 1. Compare BaseUnit colors (white vs dark grey) White only at first slot after IM 2. Compare slot map: project vs physical rack Module type, MLFB, BU type on each slot 3. Recompile TIA Portal project, download to CPU 4. Assign PROFINET device name to each IM 5. Power cycle stations — RN solid green? Yes: complete. No: check diagnostic buffer.

13. Cross-Platform and Migration Notes

The same diagnostic pattern appears on other Siemens controller families pairing with ET200SP, including S7-1500 CPU 1511/1515/1516 and S7-1200 CPU 1215C/1217C. The IM155-6 PN ST behaves identically regardless of controller. The HF variant (6ES7 155-6AU01-0BN0) adds shared device, S2 redundancy, and MRP client features; if the project is migrated from ST to HF, the HW catalog entry and any HF-only parameters must be updated.

For projects where the ET200S CPU is being replaced with an S7-1500, port the TIA Portal V11 project into V15 or V16 first. The ET200S CPU 151-8AB01 is end-of-life and spare-part supply is constrained. When porting, the ET200S-specific modules (PM-E 6ES7 138-4CA01) require a one-to-one replacement with an ET200SP PM or removal from the slot table.

For brownfield projects where the IM155-6 firmware is older than V3.0, upgrade the IM firmware before commissioning. The V3.0 firmware adds S2 system redundancy support and improved diagnostic buffer depth, both of which simplify field troubleshooting.

14. FAQ

Why does the IM155-6 RN LED keep blinking after I download the hardware configuration?

The IM is in commissioning mode because no PROFINET device name has been assigned, or the assigned name does not match the name in the TIA Portal project. Open Online → Accessible Nodes, identify the IM by its MAC address (printed on the front label), and assign the device name exactly as spelled in the project, including case. Power cycle the station to apply the new name.

Can I use a high-feature (HF) IM155-6 in a project configured for the standard (ST) variant?

Yes, the HF variant is backward compatible with the ST configuration. The reverse is not true: an ST IM will reject HF-only parameters (shared device, S2 redundancy, MRP manager, iPAR server) and report a configuration error. If your project uses HF features, the configured IM in TIA Portal must be the HF variant 6ES7 155-6AU01-0BN0.

What is the difference between a white and a dark grey BaseUnit?

The white BaseUnit starts a new load group and provides 24 V L+ (and optionally 24 V AUX) feed-in terminals. The dark grey BaseUnit passes the L+ supply through to the next slot. The first BaseUnit to the right of the IM155-6 must always be white. Using the wrong color in a slot causes a "Configuration error" diagnostic event and the affected I/O module reports a Diag LED error.

How long does a firmware update take on an IM155-6 with three I/O modules?

Expect 2–4 minutes per station: 60–120 s for the IM155-6 itself, plus 30–60 s per DQ16 module and 30–60 s per AI4 module. If the RN LED continues to blink beyond 10 minutes with no Diag LED activity on any module, the update has stalled. Do not power cycle during an active update—wait for the second-stage flash write to complete.

Why does TIA Portal V11 not show my IM155-6 firmware version in the HW catalog?

TIA Portal V11 was released in 2012 and predates the IM155-6 V3.x firmware. Install TIA Portal V11 SP2 Update 5 or later, or import the latest GSDML file from the Siemens support portal. The GSDML goes under C:\Program Files\Siemens\Automation\Portal V11\Data\Hsp\ and requires a TIA Portal restart to take effect.

Can I have multiple white BaseUnits in one ET200SP station?

Yes, but only one white BaseUnit can be the start of a new load group. Subsequent white BaseUnits must be configured in TIA Portal as "Continue potential group," not "New potential group." A station with three white BaseUnits all marked as new load groups is a common configuration error and produces a station-wide parameter-assignment failure.

Back to blog