Troubleshooting PLCSIM V13 SP1 Online Connection Errors in TIA

David Krause14 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting PLCSIM V13 SP1 Online Connection Errors in TIA Portal

PLCSIM V13 and V13 SP1 ship as the integrated S7-1200/S7-1500 simulator for the SIMATIC TIA Portal engineering framework. When a workstation is upgraded incrementally, or when a project originally created in TIA Portal V12 is opened in V13 without a proper version migration, the simulator produces a small family of startup errors that prevent the virtual CPU from being reached. This reference documents the two error states most often reported after moving to PLCSIM V13 SP1, the root causes that generate them, and the field-proven procedure to bring simulation online again.

Scope: This article applies to SIMATIC STEP 7 Basic / Professional V13 and V13 SP1 with the bundled PLCSIM V13 / V13 SP1. It does not apply to the older standalone PLCSIM V5.x (for S7-300/S7-400) or to the V14+ generation of PLCSIM, which has a different architecture and different error vocabulary.

1. Problem Description

Two correlated symptom patterns are reported on the engineering workstation after a V13 → V13 SP1 update is applied, or when a TIA Portal V12 project is opened in V13 and simulation is started:

  1. Error A — "PLCSIM not installed". The user invokes Start simulation from TIA Portal without first opening PLCSIM manually. The portal raises the dialog and refuses to launch the virtual S7-1200 / S7-1500 CPU.
  2. Error B — "Simulation cannot be started because there is already an online connection to a device". PLCSIM is launched as a separate instance with a new project before Start simulation is triggered from TIA Portal. The portal refuses to take ownership of the already-open instance.

Either error terminates the simulation before the project is downloaded into the virtual PLC. When the engineer attempts to Download to device directly from the project tree, the wizard reports that no compatible target can be found, even though the PG/PC interface is configured to PLCSIM S7-1200/S7-1500.TCPIP.1.

2. Symptom Matrix

Symptom Trigger Pre-condition Likely cause
"PLCSIM not installed" dialog Start simulation invoked from TIA Portal PLCSIM V13 SP1 not previously launched Component registration broken after partial SP1 update
"already an online connection to a device" Start simulation invoked from TIA Portal PLCSIM already opened manually in a separate project Two PLCSIM processes holding the same virtual interface
No downloadable target found Online → Download to device PG/PC interface = PLCSIM S7-1200/S7-1500.TCPIP.1 PLCSIM service not listening on 192.168.0.1
HMI runtime panel never displays Start simulation with HMI in project WinCC RT Advanced / Professional not installed or wrong SP PLCSIM is a PLC simulator only, not an HMI simulator

3. Root Cause Analysis

The combined symptoms above trace back to three independent but interacting root causes. Each must be confirmed before the field fix is applied.

3.1 Partial SP1 update across the TIA Portal stack

PLCSIM V13 SP1 must be installed at the same service-pack level as the TIA Portal host, the WinCC component (if HMI is present), Startdrive, and SIMOCODE ES. Per the official Siemens delivery note for the V13 SP2 generation, "The TIA Portal STEP 7 products (including PLCSIM), Safety, WinCC, Startdrive and SIMOCODE ES must be upgraded to the same version (V13 SP2)". The same rule applies to V13 SP1. When only PLCSIM is patched, the TIA Portal shell cannot locate the registered virtual-CPU service and the call to launch it fails with the "PLCSIM not installed" wording, even though the binaries are physically present on disk.

3.2 Doubled PLCSIM process holding the virtual adapter

PLCSIM V13 / V13 SP1 binds a single Windows TCP/IP interface entry (PLCSIM S7-1200/S7-1500.TCPIP.1) and a single default IP address (192.168.0.1). If a PLCSIM window is already open with its own project, a second Start simulation from the portal cannot acquire the adapter and reports the existing online connection. Closing the orphan instance is required before the portal can re-take ownership.

3.3 Mixed project / portal version (V12 project in V13 portal)

When a project created in TIA Portal V12 is loaded into V13, the portal offers an in-place upgrade. If the engineer continues with the original device-version containers and then attempts PLCSIM download, the portal will not find a downloadable V12 target on the V13 SP1 PLCSIM service. The matching device firmware version must be re-allocated to the V13 portal project before simulation can succeed.

4. PLCSIM V13 Architecture and Boundaries

PLCSIM V13 (and V13 SP1) is a user-mode Windows application that emulates an S7-1200 or S7-1500 CPU. It exposes a virtual Ethernet adapter that the TIA Portal PG/PC interface parameterizes as PLCSIM S7-1200/S7-1500.TCPIP.1, with IP 192.168.0.1 on subnet 255.255.255.0 by default. The supported instruction set, organisational blocks, and diagnostic behaviour are those of the matching firmware version declared in the TIA Portal project.

Critical boundary: PLCSIM V13 / V13 SP1 is a PLC simulator. It does not host the HMI runtime. To simulate an HMI panel (Comfort, KTP, WinCC Runtime Advanced / Professional), a separate WinCC component must be installed and the HMI must be configured to use its own runtime. HMI simulation cannot be started by clicking Start simulation on a PLCSIM instance. If the project tree shows the HMI and the engineer is invoking simulation against PLCSIM only, the HMI panels will never display and the PLC program download will still succeed — that is normal behaviour, not an error.

5. Prerequisites

Before applying the resolution, verify that the workstation carries a coherent TIA Portal V13 SP1 stack:

  • SIMATIC STEP 7 Basic / Professional V13 SP1 (Update 4 or later recommended)
  • PLCSIM V13 SP1, installed from the matching Siemens support package. Reference: Updates for PLCSIM V13 SP1 (Siemens Support, ID 109477180)
  • If an HMI is part of the project: WinCC V13 SP1 in the matching flavour (Basic / Comfort / Advanced / Professional)
  • If SINAMICS drives are present: Startdrive V13 SP1
  • If safety logic is used: SIMATIC Safety V13 SP1
  • Administrator rights on Windows 7 SP1 / Windows Server 2008 R2 (or later supported OS for the SP1 generation)

All components must be patched to the identical service-pack level. Partial patching is the most common cause of the symptom cluster described in Section 1.

6. Step-by-Step Resolution

Apply the following sequence. Each step has a deterministic pass/fail check that should be confirmed before moving to the next step.

  1. Inventory the installed TIA software. Open Start → Control Panel → Programs and Features (Windows 7/Server 2008 R2) and record every Siemens entry. The version column must read V13.0 + SP1 for STEP 7, PLCSIM, WinCC, Startdrive, SIMOCODE ES, and Safety.
    Pass: All entries show identical SP level.
    Fail: Patch the missing components from the Siemens support portal before continuing. Do not skip this step.
  2. Close every orphan PLCSIM window. Use Task Manager → Details to confirm that no S7PLCSIM.exe instance is running. Right-click → End task for any remaining entry.
    Pass: No S7PLCSIM.exe process listed.
  3. Verify the PG/PC interface assignment. Open Start → SIMATIC → PG/PC Interface (the 32-bit applet, even on 64-bit Windows). Set the access point S7ONLINE to the parameterization PLCSIM S7-1200/S7-1500.TCPIP.1. Click Diagnostics and confirm that the virtual adapter reports OK on address 192.168.0.1.
  4. Open TIA Portal only — do not start PLCSIM manually. Launch the TIA Portal V13 SP1. Open the target project. Select the PLC device in the project tree. From the toolbar invoke Start simulation (the play icon on the Online menu). The portal will instantiate PLCSIM and download the project automatically.
    Pass: PLCSIM window opens automatically and the green RUN/STOP LED on the simulated CPU transitions to RUN after download completes.
    Fail (Error A still appears): Component registration is broken. Re-run the PLCSIM V13 SP1 setup in Repair mode, then reboot.
  5. If the project originated in TIA Portal V12, complete the device-version upgrade (Section 7) before retrying Step 4.

7. Upgrading a TIA Portal V12 Project to V13

When a V12 project is opened in V13, the portal prompts for a project upgrade. The PLC device containers, however, retain their V12 device firmware references and must be re-allocated to a V13 firmware before PLCSIM V13 SP1 will accept the download.

  1. In TIA Portal V13 SP1, open the upgraded project. The portal will display the Project upgrade dialog on first open — click Yes to commit.
  2. Navigate to the Project tree → PLC → Device view. For every PLC device in the project, right-click and select Change device / version (or Change device → Device version depending on the SP1 build).
  3. In the dialog, choose the V13 (or V13 SP1) firmware article number for the matching CPU. The article number must correspond to a device version installed by the TIA Portal V13 SP1 hardware catalog. Click OK to commit.
  4. Repeat the change for the HMI devices, drives, and any other station, using the matching V13 SP1 catalog entries. The HMI runtime is not required for PLCSIM-only simulation, but a clean version alignment is required to compile the project.
  5. Compile the project (Project → Compile all). Resolve any residual type mismatches introduced by the firmware change (e.g. optimized-block tag access on S7-1500 must be honored by all clients).
  6. Return to Section 6, Step 4, and start the simulation from the portal without manually opening PLCSIM.
Warning: After a successful version change, save the project as a V13 SP1 project (Project → Save as). Do not revert to the V12 file or re-open the project in a V12 portal — the V12 portal cannot read V13 SP1 containers.

8. PG/PC Interface Configuration Reference

The PLCSIM V13 virtual adapter is the only parameterization that allows TIA Portal to reach a simulated S7-1200 / S7-1500. The following settings are mandatory:

Setting Value Notes
Access point of the application S7ONLINE Used by STEP 7 / TIA Portal for online operations
Interface parameterization used PLCSIM S7-1200/S7-1500.TCPIP.1 Defined by PLCSIM V13 SP1 install
Default IP address 192.168.0.1 Assigned to the virtual adapter by PLCSIM
Subnet mask 255.255.255.0 Hard-coded by PLCSIM
Online connection mode 1 (PG/PC is the only master on the virtual subnet) Default; do not enable routing to physical NIC

If a previous install assigned a real Ethernet NIC to S7ONLINE, simulation cannot be reached. Reset the assignment to PLCSIM S7-1200/S7-1500.TCPIP.1 in the PG/PC interface applet. The change is effective immediately and does not require a Windows reboot.

9. HMI Simulation — What PLCSIM Will Not Do

PLCSIM V13 SP1 does not provide an HMI runtime. If the project contains a Comfort Panel, KTP, or a PC-based HMI, the engineer must install and use one of the following:

  • WinCC Runtime Advanced V13 SP1 for KTP / Comfort / WinCC RT Advanced targets
  • WinCC Runtime Professional V13 SP1 for PC-based SCADA targets
  • The bundled Start simulation on the HMI device in TIA Portal, which uses the WinCC RT simulator (not PLCSIM) to run the panels against the running PLCSIM PLC instance

The recommended workflow for combined PLC + HMI simulation in TIA Portal V13 SP1 is:

  1. Start PLCSIM from the portal (Section 6, Step 4). The simulated PLC is now online.
  2. Right-click the HMI device in the project tree and select Start simulation. WinCC RT starts, establishes a connection to the PLCSIM CPU over the virtual adapter, and the panels become operable.
  3. For WinCC Professional panels with tags served by the simulated S7-1500, the connection in the HMI configuration must reference the simulated CPU's IP 192.168.0.1 with the slot configured for the S7-1500 (slot 1 for the CPU, slot 0 for the PN interface).
Engineering caveat: If WinCC is patched at a different SP level than PLCSIM, the HMI Start simulation command will fail with a connection error even though the PLC simulation runs correctly. Verify the WinCC SP level against the PLCSIM SP level and reconcile them.

10. Verification Procedure

After applying the resolution, perform the following checks in order. Each must pass before declaring the workstation healthy.

  1. PLCSIM launches from the portal. Click Start simulation on the PLC. PLCSIM V13 SP1 window appears within 5–10 seconds. No "PLCSIM not installed" dialog appears.
  2. Project downloads into the virtual CPU. The status bar of the TIA Portal reports Download to device completed without errors. The simulated CPU transitions from STOP to RUN with the green LED active.
  3. Online connection is exclusive. Open Online → Accessible nodes. The simulated CPU is listed once, on 192.168.0.1, with the configured PROFINET device name. No duplicate entries are shown.
  4. Watch table operates. Create a watch table with one tag from the user program, force the value, and confirm the value changes in the simulated CPU using Monitor / modify.
  5. HMI simulation (if applicable). Right-click the HMI device and select Start simulation. The WinCC RT panel opens and reads tags from the simulated PLC.

11. Field Troubleshooting Matrix

The matrix below maps the most common error patterns reported against PLCSIM V13 SP1 installations to their root cause class and the corrective action. Use it as a triage aid when the symptom description in Section 1 does not match exactly.

Observed error / symptom Root cause class Corrective action
"PLCSIM not installed" on Start simulation Partial SP1 update; PLCSIM service not registered Repair-install PLCSIM V13 SP1 from Siemens support ID 109477180; reboot; retry
"already an online connection to a device" Orphan PLCSIM process holding the virtual adapter End every S7PLCSIM.exe in Task Manager; restart portal; retry
No downloadable target listed in the wizard PG/PC interface assigned to a real NIC, not the virtual adapter Open PG/PC interface applet; assign S7ONLINE to PLCSIM S7-1200/S7-1500.TCPIP.1
Project compiles, download fails immediately V12 device firmware retained in a V13 project Apply Section 7 (Change device/version for every station); recompile
HMI panel never appears after Start simulation PLCSIM does not host HMI runtime Use WinCC RT Advanced/Professional Start simulation on the HMI device; align SP levels
Simulated CPU stays in STOP after download OB1 / startup OB missing in project Add OB1 (and OB100 if required) to the user program; recompile; re-download
WinCC RT cannot establish connection to PLCSIM WinCC SP level differs from PLCSIM SP level Patch WinCC to V13 SP1 matching the PLCSIM build
Simulation starts, then disconnects after 30 s Real NIC is bridged to the virtual subnet (proxy ARP enabled) Disable routing/proxy in the PG/PC interface applet; keep the virtual adapter isolated

12. Preventive Checklist

Apply the following controls to the engineering workstation image to prevent recurrence of the symptom cluster:

  • Maintain a single source of truth for the TIA Portal patch level. Whenever a Siemens update is applied, patch STEP 7, PLCSIM, WinCC, Startdrive, SIMOCODE ES, and Safety in the same maintenance window.
  • Use the Siemens Automation License Manager to inventory installed software and to verify the SP level across packages.
  • Do not open PLCSIM manually as a workaround. The portal-driven Start simulation is the only supported entry point on V13 SP1.
  • When migrating a V12 project, perform the device-version change for every CPU and HMI in a single session, then save the project as a V13 SP1 project. Do not retain a V12 backup as the live working copy.
  • Document the PG/PC interface assignment in the workstation handover. PLCSIM S7-1200/S7-1500.TCPIP.1 is the only correct value for SIMATIC S7ONLINE during simulation; restore it after any other engineering work that re-assigns S7ONLINE to a real NIC.

13. Related References and Official Sources

For deeper background on the TIA Portal V13 / V13 SP1 component compatibility matrix and the V13 SP2 trial delivery, refer to the following Siemens support entries. These are the only sources that authoritatively describe which packages must be co-installed and at which service-pack level.

Why does TIA Portal V13 SP1 report "PLCSIM not installed" even though PLCSIM V13 SP1 is on the disk?

Component registration is broken, almost always because PLCSIM was patched to SP1 while the TIA Portal host, WinCC, Startdrive, or SIMOCODE ES remained at V13 without SP1. The TIA shell cannot locate the registered PLCSIM service. Repair-install PLCSIM V13 SP1 from Siemens Support ID 109477180, ensure every TIA component shares the SP1 level, then reboot.

How do I start a combined PLC + HMI simulation in TIA Portal V13 SP1?

Click Start simulation on the PLC first; PLCSIM V13 SP1 opens automatically. Then right-click the HMI device in the project tree and select Start simulation to launch the WinCC Runtime simulator. The HMI runtime connects to the simulated CPU over the virtual adapter at 192.168.0.1. WinCC must be at the same SP1 level as PLCSIM.

Can PLCSIM V13 SP1 simulate a project originally created in TIA Portal V12?

Not directly. When the V12 project is opened in V13, accept the project upgrade, then for every CPU and HMI use Change device / version to re-allocate a V13 SP1 firmware article from the hardware catalog. Recompile the project and then invoke Start simulation from the portal. Save the result as a V13 SP1 project.

Which PG/PC interface parameterization is correct for PLCSIM V13 SP1?

Set access point S7ONLINE to PLCSIM S7-1200/S7-1500.TCPIP.1 in the SIMATIC PG/PC Interface applet. The virtual adapter is assigned 192.168.0.1 / 255.255.255.0 by default. Do not assign a real Ethernet NIC to S7ONLINE during simulation; the accessible-nodes scan will not find the virtual CPU.

Why does "Simulation cannot be started because there is already an online connection to a device" appear?

An earlier PLCSIM instance is still running and holds the virtual adapter. End every S7PLCSIM.exe process in Task Manager → Details, restart TIA Portal, and start the simulation from the portal rather than from a manual PLCSIM launch. The portal-driven start is the only supported entry point that ensures a single, exclusive owner of the virtual CPU.

Back to blog