Troubleshooting Siemens 6SE70 O008 Inhibit-to-Start Fault

David Krause14 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting Siemens 6SE70 O008 Inhibit-to-Start Fault on 6SE7036 Windlass Drives

The SIMOVERT MASTERDRIVES VC / MC family (6SE70 series) is widely deployed in marine winch and windlass duty where the converter is exposed to salt-air humidity, vibration, inductive DC-link transients, and noisy contactor logic. A recurring and often-misread condition on these drives is operating state O008 — frequently described by field engineers as an inhibit-to-start lockout. Unlike alarms (Axxx) and faults (Fxxx), O008 is a state, not a trip event, which is precisely why the main contactor can open and the panel can show "no fault, no alarm" while the drive refuses to release the inverter. This reference explains what O008 actually means on a 6SE7036-0EK60, why it can appear sporadically on a windlass, and how to systematically eliminate the root causes — from control-word DI bounce to the PSU2–IVI flat-ribbon cable, to optional K80 Safe Stop behaviour.

Important: O008 is an operating state, not a fault. The drive will hold the inverter inhibited until the combination of control-word conditions that produced it is removed. Cycling OFF1 alone will not necessarily clear it if bit 03 (Inverter Release) or another source is still low.

1. Problem Definition: Sporadic O008 on 6SE7036-0EK60 Windlass

Reported field behaviour on the 6SE7036-0EK60 (frame size E, typically 360 A three-phase rectified-class output) used in anchor windlass duty:

  • Drive runs normally for 6–8 hours or more, then transitions to O008.
  • Main input contactor drops out; drive remains powered on the electronics side.
  • No Fxxx fault code and no Axxx alarm are stored in the fault buffer.
  • OFF2 and OFF3 are not used (bits 01 and 02 of the control word are hard-wired high or unused).
  • OFF1/ON (bit 00) and Inverter Release / Inverter Stop (bit 03) are wired to digital inputs through an interposing relay.
  • At the moment O008 occurs, the ON signal is still present (bit 00 = 1).
  • Issuing OFF1 (bit 00 = 0) transitions the drive to O009, after which the drive can be restarted.

The transition pattern is the key diagnostic clue: O014 → O008 → (after OFF1) O009 → restart. This sequence maps directly to control-word bit loss rather than a hardware trip.

2. SIMOVERT MASTERDRIVES 6SE70 Operating-State Reference

The 6SE70 platform exposes its current behaviour through the two-digit status word (r001 / r002 by default, parameter set by P654 and P655). The relevant states for the 6SE7036 windlass case are:

Status Name Meaning Typical Cause on Windlass
O000 Run Inverter enabled, output frequency follows setpoint. Normal running.
O008 Inhibit to start (start lockout) Conditions for release not fulfilled; inverter is inhibited. Missing ON, missing Inverter Release, K80 Safe Stop, or PSU2 15 V under-voltage.
O009 Inhibit to stop OFF1 dropped; drive is ramping down, will move to O008 at 0 Hz. Operator commanded stop.
O010 Standstill without run command ON = 0, drive idle. Idle between cycles.
O012 Fault / alarm present Fxxx or Axxx active. Look in fault buffer r047/r049.
O014 Standstill with run command ON = 1 and Inverter Release = 1, but output not yet released (precharge, magnetisation, or another inhibit). State just before O000 in the normal start sequence.

For the windlass case, the O014 → O008 transition (rather than O014 → O000) means a release condition is being revoked at the moment the drive is about to release. That condition is almost always control-word bit 00 (ON/OFF1) and/or bit 03 (Inverter Release/Stop) — wired in the affected cabinet through a relay contact that is bouncing or being de-energised by an upstream interlock.

3. Control Word Bit Mapping on 6SE70

The standard 6SE70 control word (P554 in the standard parameter set) is a 16-bit word assembled from freely-selectable binary sources (BICO). Default mapping with OFF2/OFF3 not used and DI-driven ON / Inverter Release:

Bit Function Typical Wiring on 6SE7036 Windlass Effect if Cleared
00 ON / OFF1 DI via interposing relay Ramp to 0, then O009
01 OFF2 (coast to stop) Hard-wired high / unused Output stage inhibited immediately
02 OFF3 (quick stop) Hard-wired high / unused Fastest ramp to 0
03 Inverter Release / Inverter Stop DI via interposing relay Drive drops straight to O008 while ON remains high
04 Ramp-function generator enable Fixed high Ramp frozen
05 Ramp-function generator start Fixed high Ramp paused
06 Setpoint enable Fixed high Setpoint held at 0
07 Acknowledge (fault reset) DI pushbutton or PLC No reset
08–15 Per configuration Various Platform-specific

The diagnostic giveaway: if bit 03 (Inverter Release) is momentarily lost while bit 00 (ON) remains high, the 6SE70 transitions O014 → O008 and stays in O008 until ON is dropped, even if Inverter Release is restored. This matches the reported field behaviour exactly.

Why OFF1 alone is required to recover: The drive will not return to O000 from O008 while bit 00 = 1. Issuing OFF1 (bit 00 = 0) moves the drive to O009, which is the only path that allows the state machine to re-evaluate the release conditions. The operator's report of "OFF1 clears it" is therefore consistent with bit 03 being the failed source, not bit 00.

4. Root Cause Tree: Why O008 Appears Sporadically

Five causes account for nearly every reported O008 on a 6SE7036 in windlass duty. The ranking reflects probability in marine installations:

# Root Cause Diagnostic Signal Elimination Test
1 Interposing relay bounce on the Inverter Release (bit 03) DI Trace r001/r002 and DI simultaneously; DI bit 03 dips for 1–10 ms Bypass relay; wire DI directly with a clean 24 V source; repeat load cycle
2 Flat-ribbon cable between PSU2 and IVI board (intermittent contact, insulation resistance drop under humidity) Drift of internal ±15 V rail on PSU2; no external DI disturbance Substitute known-good ribbon cable; monitor PSU2 test points TP1/TP2 for < ±14.5 V under load
3 PSU2 board failing under thermal load (regulator drop-out on the +15 V or -15 V rail) TP readings on PSU2 drift with heatsink temperature Replace PSU2 with a verified spare
4 K80 Safe Stop option inadvertently active (A017 reported, OFF2 forced low) A017 in fault buffer, OFF2 (bit 01) momentarily low Verify K80 jumper settings; check 24 V at K80 terminals X9.1/X9.2; disable if not required
5 Electromagnetic interference from main contactor coil or DC-link dump on the DI wiring loom Co-occurrence with contactor pull-in or release Install RC snubber on contactor coil; separate DI loom from motor cables by ≥ 200 mm; add shielded cable

5. Diagnostic Procedure: From Symptom to Root Cause

Follow this sequence before replacing boards. Each step uses a parameter on the 6SE70 that the engineer can read on PMU (parameter display unit) or export via DriveMonitor / STARTER.

5.1 Capture the State Word Trace

  1. Connect DriveMonitor via serial (X104) or PROFIBUS.
  2. Configure the trace function (P778 / P779 in older firmware, or the trace tool in STARTER) on the following signals:
    • r001 — status word 1 (16-bit, contains the Oxxx operating state in the high byte)
    • r002 — status word 2
    • r007 / r008 — active control word 1 / 2
    • P554 sources (especially the bit 00 and bit 03 DI sources)
  3. Set sample time to 1 ms or 2 ms (the 6 ms used in the original incident misses sub-10 ms DI bounce).
  4. Trigger the trace on a status-word edge matching the O008 code.
  5. Run the windlass through repeated anchor drops. Capture at least three full cycles.

Interpretation:

  • If bit 03 of the control word (Inverter Release) drops to 0 for any duration before O008 appears, the suspect is the DI wiring, the interposing relay, or the PSU2/IVI ribbon cable that carries the buffered DI signal back to the control electronics.
  • If bit 00 of the control word (ON) drops to 0 simultaneously with the main contactor de-energising, the upstream interlock is forcing OFF1 — different problem; the drive would pass through O009, not O008.
  • If no control-word bit change is visible at 1 ms resolution, suspect the PSU2 ±15 V supply dipping on the gate-driver / interface board side; the control word registers are correct but the inverter stage is internally inhibited.

5.2 PSU2 Voltage Checks

The PSU2 board on a 6SE7036-0EK60 supplies the control-electronics voltages, including ±15 V, +5 V, and the gating reference for the IGBTs. O008 will be latched if the ±15 V rail sags below approximately ±14 V on a transient basis.

  1. With the drive powered but inhibited, place a DMM (true-RMS, min-hold function) on PSU2 test points:
    • TP1: +15 V (±0.3 V tolerance)
    • TP2: -15 V (±0.3 V tolerance)
    • TP3: +5 V (±0.15 V tolerance)
  2. Repeat while the drive is running at full load for ≥ 1 hour.
  3. If TP1 or TP2 dips to ±14.0 V or below for any duration, the PSU2 is failing thermally or the load on the rail is excessive (a typical cause is a failing IVI board drawing excess current). Replace PSU2 first; if the new PSU2 also sags, replace the IVI board.

5.3 Flat-Ribbon Cable (PSU2 ↔ IVI) Inspection

The ribbon cable between the PSU2 and the IVI (Inverter Interface) board carries the ±15 V, the gating signals, and the inverter-status feedback. On windlass drives subject to cabinet vibration and humidity:

  1. De-energise the drive, wait for DC-link to discharge (verify < 50 V on the DC-link test points).
  2. Inspect the cable for chafe, oxidised contacts, or displaced seating in the connector.
  3. Clean contacts with isopropyl alcohol and re-seat firmly.
  4. If the symptom persists, replace the cable with a known-good unit from another operational 6SE70 of the same generation.
  5. Apply a small amount of dielectric grease at the connector edges if humidity is suspected; do not contaminate the contacts themselves.
Field tip: A failing ribbon cable is one of the most common causes of intermittent O008 on drives that have been in service 8+ years. Cables tend to fail in warm-up or after a thermal cycle, not at cold start — which is exactly the "sporadic, after hours of running" pattern reported.

5.4 K80 Safe Stop Audit

The K80 option card implements Safe Stop (STO equivalent) by forcing OFF2 (control-word bit 01) low and the gate-pulse inhibit. The drive then sits in a Safe Stop condition indistinguishable from a normal user-induced O008.

  1. Confirm whether the K80 is fitted (look for the K80 option label on the front of the electronics tray; consult the Siemens Industry Online Support portal with serial number for ordering data if uncertain).
  2. If K80 is fitted, check alarm buffer for A017 (Safe Stop requested). A017 in the buffer is the smoking gun for K80 involvement.
  3. Verify the 24 V supply at K80 terminals. A drop or interruption on the K80 24 V produces exactly the symptom reported: intermittent O008, no A017 if the drop is sub-baud and not registered, but the drive still locks out.
  4. If the application does not require Safe Stop, the K80 can be disabled by removing the option card or by setting the configuration parameter that bypasses the function (consult the K80 commissioning manual for the firmware-compatible procedure).

5.5 DI Signal Integrity and Relay Contact Audits

If the control-word trace shows bit 03 bouncing but no PSU2 / K80 anomaly, the cause is the DI wiring path. The 6SE70 DI inputs on the customer terminal block (X101, X102 depending on the option card) are typically 24 V IEC 61131-2 type 1, with a guaranteed "1" threshold of 15 V and a "0" threshold of 5 V.

  1. With the drive running, scope the DI terminals at the drive (not at the relay coil) using a differential probe or two-channel scope with a common ground at the drive PE.
  2. Look for dip < 15 V on the Inverter Release input. Even a 1 ms dip is enough to latch O008 if it occurs at the wrong point in the start sequence.
  3. Check relay contact bounce time. Mercury-wetted or solid-state relays have < 0.5 ms bounce; electromechanical relays with a coil-suppression diode only can show 5–10 ms bounce on release. If the relay is the source, replace with a sealed or solid-state unit.
  4. Add an RC snubber (100 Ω + 0.1 µF, 630 V) across the contactor coil if contactor-pickup transient is the trigger.
  5. Re-route the DI loom away from motor and contactor cables. Maintain a minimum 200 mm separation; cross at 90° if unavoidable.

6. Step-by-Step Resolution Path

Run the diagnostic sequence in order. Each step is non-destructive and reversible.

  1. Capture the state and control word trace at 1 ms resolution over a full operating cycle. Identify which control bit, if any, dips at O008 entry.
  2. Measure PSU2 ±15 V rails at TP1/TP2 with min-hold during a 1 hour loaded run. Replace PSU2 if any dip < ±14.0 V is observed.
  3. Inspect and substitute the PSU2 ↔ IVI ribbon cable. A known-good cable from a sister drive is the fastest verification.
  4. Audit the K80 option: confirm fitted/not fitted, check for A017 in the buffer, verify K80 24 V supply integrity.
  5. Hard-wire the Inverter Release DI temporarily with a clean 24 V source, bypassing the interposing relay. Run for 8 hours. If O008 does not recur, the relay or its wiring is the cause.
  6. Replace the interposing relay with a sealed or solid-state equivalent. Add an RC snubber on the upstream contactor coil.
  7. Re-run the trace and verify O008 does not appear over at least three full anchor-drop cycles spanning a full work shift.

7. Verification and Commissioning Acceptance

After corrective action, perform a structured acceptance test before returning the drive to windlass service.

Check Method Acceptance Criterion
State-word trace clean DriveMonitor trace, 1 ms, over 8 h loaded run No transition out of O000 except during commanded OFF1
PSU2 rails stable DMM min-hold on TP1/TP2 +15.0 V ± 0.3 V and -15.0 V ± 0.3 V over the run
DI bit 03 integrity Scope at drive terminal, differential probe No dip < 15 V during run
Fault / alarm buffer clean r047 / r049 No new entries during the test
Operator command response Cycle ON/OFF1 ten times Each cycle: O000 → O009 → O008 → O000
Emergency stop (if K80 fitted) Drop K80 24 V, verify Safe Stop Drive stops per K80 timing; clears on K80 24 V restore + acknowledge

8. Spare-Parts and Documentation References

For ordering PSU2 boards, IVI boards, and ribbon cables, the 6SE70 spares are typically ordered by the option-code part number on the drive's MLFB and the position designation. Cross-reference against the serial number on Siemens Industry Online Support:

  • Siemens Industry Online Support — MASTERDRIVES Compendium (manual collection for 6SE70)
  • Operating instructions for SIMOVERT MASTERDRIVES VC / MC (6SE70) — safety, control-word, status-word, parameter structure
  • Function diagram manual — state machine O000–O255
  • K80 Safe Stop option manual — only relevant if the K80 is fitted and A017 is suspect
  • STARTER / DriveMonitor commissioning manual — trace tool configuration
Safety note: A 6SE7036 retains hazardous DC-link voltage for several minutes after power removal. Confirm < 50 V at the DC-link test points before opening the electronics tray or handling the PSU2 / IVI flat-ribbon cable. Lock and tag the input contactor per local marine safety procedures.

9. Frequently Asked Questions

What is O008 on a Siemens 6SE70 drive?

O008 is operating state 8, "Inhibit to start" (sometimes labelled start lockout). It is not a fault. The drive will hold the inverter inhibited until the combination of release conditions in the control word (typically ON bit 00 and Inverter Release bit 03) is satisfied.

Why does the main contactor open when O008 appears on my 6SE7036 windlass?

Most windlass cabinets wire the main contactor hold-in through the drive's "Inverter Release" output or a status relay that drops when the drive leaves O000. When O008 is entered, that release signal de-energises the contactor coil, opening the line. There is no fault code because the drive is behaving to its logic — it is the upstream condition that caused O008 in the first place that must be diagnosed.

Can I clear O008 with an OFF1/ON cycle on the 6SE70?

Yes, but only if the underlying condition that produced O008 has been removed first. Cycling OFF1 moves the drive through O009, which is the only state from which the 6SE70 will re-evaluate the release conditions. If the cause is still present, the drive will re-enter O008 immediately on the next ON.

Does K80 Safe Stop look identical to O008 on a 6SE70?

Functionally yes — K80 forces OFF2 (bit 01) low and inhibits gate pulses, which latches a state that appears as O008 to the operator. The differentiator is alarm A017 ("Safe Stop requested") in the fault buffer. If A017 is present at the time of the lockout, K80 is the cause.

How do I tell whether the ribbon cable or the PSU2 board is the cause?

Substitute a known-good ribbon cable from a sister drive. If O008 still appears, replace the PSU2 with a verified spare and retest. The cable is the cheaper and more common failure; the PSU2 is more likely if the symptom coincides with heatsink temperature rise or if the ±15 V rails drift on a DMM with min-hold.

What sample rate should I use for the control-word trace on a 6SE70?

Use 1 ms or 2 ms. At 6 ms (a common default) a relay contact bounce of 3–4 ms is invisible, which is why the original incident was inconclusive. The 6SE70 trace function supports sub-millisecond sample rates in newer firmware, but 1 ms is sufficient to catch electromechanical relay bounce.

Is it safe to bypass the interposing relay to test the 6SE70 DI inputs?

Temporarily, yes — for diagnostic purposes only, with a clean 24 V source from a regulated bench supply or a known-good cabinet rail, observing all lockout/tagout procedures. The test confirms whether the relay is the cause. Do not leave the bypass in service; rework the wiring with a sealed relay or a snubber if the bypass solves the issue.

Back to blog