Troubleshooting SIMOCODE PRO V Return Feedback Off in Direct

David Krause11 min read
Motor ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting SIMOCODE PRO V 'Return Feedback Off' Fault in a Direct Online (SMC_DIR) Starter

The SIMOCODE pro V is a modular motor management system from Siemens (SIRIUS family) that combines motor protection, control, and diagnostics over PROFIBUS DP or PROFINET. One of the most common field failures when commissioning a direct online starter in PCS 7 — or a stand-alone S7-1200/S7-1500 environment — is the "Return Feedback Off" alarm. The motor accepts the start pulse, accelerates, then trips after a short delay even though the contactor is closed and the current path is intact. This article explains the root cause, the correct SIMOCODE ES parameterization, and the verification steps required to resolve the fault across all 80 devices in a typical PCS 7 fleet.

1. Problem Description

Engineer symptom log on the affected cabinet:

  • Topology: ~80x SIMOCODE pro V basic units, PCS 7 V9.x, PROFIBUS DP ring to ET 200M / DMF-Local operator panels.
  • Starter type: SMC_DIR (direct online, non-reversing).
  • Sequence: Operator issues Start → contactor closes → motor begins to rotate → 200–500 ms later SIMOCODE raises the Return Feedback Off (RFC) alarm → PCS 7 shows red fault banner → motor coasts to stop.
  • Test: Activating the Jog bit (JOG_ON = 1) starts the motor and keeps it running without the alarm. The control word without the jog only produces a single rising edge.
  • Wiring verification: Confirmed by a Siemens France field engineer — the main power path, PE, and current measurement inputs (IL1/IL2/IL3) are correct.

This exact pattern is a signature of a command-signal level/duration mismatch between the PLC control word and the SIMOCODE "command source." SIMOCODE is a stateful controller; it expects a continuous (maintained) level, not an edge, on the ON command unless the configuration explicitly maps to a different operating mode.

2. Root Cause Analysis

SIMOCODE pro V distinguishes between two physical/control levels for motor start commands:

Mode Behavior When Used Required Feedback
Maintained command (continuous 1-level) PLC must hold the ON bit = 1 for the entire run. Releasing the bit = Stop. Default for PCS 7 faceplate Motor block (FB 186/188 logic), standard S7 driver blocks Contactor feedback (R) must follow the running state. If R does not close within Feedback Off Delay, SIMOCODE trips with RFC.
Pulse / Jog (rising edge) One rising edge = Start. Another rising edge on the same input = Stop. Field jog pushbuttons, handheld operator panels, commissioning Same feedback supervision applies, but the command latch prevents the off event caused by PLC scan jitter.

The behavior the engineer observed — "Jog starts the motor, but the PLC command only produces a rise edge and trips" — means the SIMOCODE was parameterized for a pulsed / jog control input, while PCS 7 (or the S7-1200/1500 driver block) is delivering a maintained (level) control word. The PCS 7 block sets ON = 1 on each cyclic update. If SIMOCODE interprets the same bit as a jog, it sees the rising edge, latches internally, but then evaluates feedback against an expected behavior the wiring cannot satisfy, producing the Return Feedback Off event after the configurable feedback-off delay (default 2 s).

Note: "Return feedback off" is a process-level alarm, not a hardware overcurrent trip. The General Fault (GF) LED on the basic unit may not light if the PCS 7 faceplate interprets the diagnostic bit before the device-level fault is latched. This matches the forum observation: "the fault appears in PCS 7 but the SIMOCODE does not always show a general fault LED." When the GF LED is lit, treat the event as a hard device trip and check contactor wear, mechanical interlock, and current-transformer (CT) ratios.

2.1 Secondary Causes That Can Produce the Same Symptom

  1. Test Position Feedback (TPF) is enabled in SIMOCODE ES → Device configuration → Inputs/Outputs → "Test position feedback." When the DMF-Local operator panel is plugged in or the test bit is asserted, SIMOCODE expects the contactor to be open and trips the running motor.
  2. Feedback Off Delay is set too short for the contactor closure time (typical Q-line contactor closure 30–80 ms, with 100–250 ms contactor-side debounce).
  3. Wrong feedback source assigned in SIMOCODE ES — the input that is wired to the contactor's Auxiliary Normally Open is mapped to a different bit (e.g., a status bit that only follows the ON command).
  4. DMF-Local / DM-F Local operator panel in "Local/Remote" mode with the Local-Hand key switch in a position that asserts a permissive the PLC does not provide.

3. Solution: Configure SIMOCODE ES for a Standard Direct Online Starter (SMC_DIR)

Use the official SIMOCODE pro System Manual (PDF) and the SIMOCODE pro V PN / FDI Programming and Operating Manual (PDF) as the authoritative reference. The block diagram below summarizes the parameter set required for a PCS 7-driven SMC_DIR with maintained commands and a contactor-feedback (R) wired to a digital input on the digital module (DM).

3.1 Step-by-Step SIMOCODE ES Configuration

  1. Open the device in SIMOCODE ES 2007 / TIA Portal (V15+). For PROFINET variants, the device is added under Devices & Networks and parametrized in the device view. For PROFIBUS DP, use the SIMOCODE ES stand-alone tool with a USB-to-PROFIBUS or Ethernet routing path.
  2. Select the starter function block. In the device tree, navigate to Parameter → Function blocks → Motor control → Starter and choose SMC_DIR (Direct Online Starter, non-reversing). Do not select SMC_REV unless the reversing contactor is wired and the feedback interlock is present.
  3. Assign the command source — CRITICAL FIX. Under Parameters → Command sources:
    • Control station 1 = PLC (cyclic) for PCS 7 / S7-1500 drivers.
    • Control station 2 = Field device (DOL / jog pushbutton) if the DMF-Local is wired for hand-operation.
    • Set the command type to "Maintained command (level)". In SIMOCODE ES this is the default; verify it is not set to "Jog (pulse)" or "Jog mode with reversal".
  4. Map the ON / OFF bits to the cyclic PROFIBUS/PROFINET control word. Default for PCS 7 driver block SIMOCODE pro V (V6.0):
    Bit (Control Word) Meaning Value for ON
    Bit 0 ON / OFF (motor ON) 1
    Bit 1 OFF2 (coast to stop, optional) 0
    Bit 2 OFF3 (quick stop, optional) 0
    Bit 3 Enable / Reset 1
    Bit 4 Local/Remote 0 = Remote (PLC)
    Bit 5 Jog 0 (use jog input instead if needed)
  5. Map the return feedback (R) input. Navigate to Parameters → Inputs → Digital inputs. For the contactor auxiliary NO, assign the chosen DM input (e.g., DI0 on the digital module) to "Return feedback closed (R)". The status of this input must follow the contactor state, not the current-transformer threshold.
  6. Disable Test Position Feedback unless the drawer is used. In Parameters → Function blocks → Inputs, uncheck Test position feedback (TPF). Withdrawable motor starters that require test-mode handling should use the dedicated "TPF" function block, not the standard SMC_DIR.
  7. Set the Feedback Off Delay. Default 2.0 s in SIMOCODE ES. For Q-line contactors, set to 3.0–5.0 s to ride through contactor closure and any one-cycle PLC scan jitter when the controller is on the same PROFIBUS cycle as the SIMOCODE.
  8. Enable Motor Current Monitoring. Threshold I > 0.10 × I_e; undercurrent threshold I < 0.05 × I_e for the trip after start (catches belt breakage / coupling shear).
  9. Compile and download. Right-click the device in the project tree → Download to device. Always run a "Download to target device — Stop and restart of the SIMOCODE" so the new command-source mapping takes effect on the next power-up.

3.2 PCS 7 Driver Block Wiring

The PCS 7 Advanced Process Library (APL) block MOT_SPED or MOT_SLOW drives the SIMOCODE pro V via the channel block CH_MOT and the driver block SIMO_3UF7. Confirm in CFC:

  1. SIMO_3UF7.QBAD = 0 (good quality).
  2. SIMO_3UF7.AUX_PRIM wired to the contactor feedback (R) — not to the current bit.
  3. SIMO_3UF7.SP_RPM / SP_SPEED not used for SMC_DIR; leave the speed-related inputs at default.
  4. The faceplate does not need to be set to "Jog" mode. If the operator selected "Jog" by mistake, the local/remote permissive will conflict with the cyclic PLC word and the RFC will recur.

4. S7-1200 / S7-1500 Parameterization via TIA Portal

For a stand-alone S7-1500 connected to SIMOCODE pro V PN over PROFINET, you do not need the special USB-to-PROFIBUS cable. The PROFINET device can be parametrized through the PLC's PROFINET interface as long as SIMOCODE is assigned to the IO controller and the GSDML file (Siemens-DE.0811) is installed. TIA Portal then loads the parameter record into SIMOCODE on every restart of the IO device. The official path is documented in the SIMOCODE pro V PN FDI Programming and Operating Manual, section "Parameter assignment via PROFINET."

5. Verification

  1. Read the diagnostic buffer from the SIMOCODE device via web server (SIMOCODE pro V PN only) or SIMOCODE ES → Online → Diagnostics → Event log. Look for event code 0x102A (Return Feedback Off).
  2. Check the cyclic status word in PCS 7: bit 0 (Running) and the feedback bit from SIMO_3UF7.AUX_PRIM. Both must be 1 within 1.0 s of the start command.
  3. Toggle ON/OFF 20 times in succession from the faceplate. If the motor starts cleanly every time, the original RFC is fixed.
  4. Pull the DMF-Local panel off while the motor is running. If the motor stops and an RFC appears, TPF is incorrectly enabled. Re-check step 3.1.6.
  5. Duplicate the working configuration across the 80 devices. In SIMOCODE ES, right-click the device → Copy, then paste the parameter record into each downstream instance. Always re-flash the firmware record to keep revisions consistent — the supported record versions for PCS 7 V9.0 SPx are listed in the Siemens SIMOCODE product page under "Software & firmware."

6. Quick Configuration Checklist

# Parameter (SIMOCODE ES path) Correct value for SMC_DIR with PCS 7 Common mistake
1 Function block → Starter SMC_DIR Choosing SMC_REV (extra fault logic)
2 Command source 1 PLC cyclic Field device / jog only
3 Command type Maintained (level) Jog / pulse
4 Digital input → Return feedback R Assigned to contactor NO Assigned to current bit
5 Test position feedback TPF Off Left on (drawer default)
6 Feedback off delay 3.0–5.0 s 0.5–1.0 s (too short)
7 Local/Remote switch Remote (PLC) Local (DMF-Local)
8 Control word bit 0 (ON) Maintained 1-level Pulse from faceplate

7. Related Fault Codes

Event code Text in ES Most likely cause First action
0x102A Return Feedback Off Contactor did not close in time, or wrong feedback source Increase feedback off delay, verify wiring
0x1029 Return Feedback On (unwanted) Contactor welded or feedback wired to a different output Inspect contactor, isolate load
0x1024 Test position active TPF active during running Disable TPF or check drawer interlock
0x1100 Overload trip Current above I_e × class Check load, verify motor FLA
0x1101 Thermistor trip PTC above threshold Check motor temperature, wiring

8. Common Pitfalls Across a 80-Device Fleet

  • Per-device copy in SIMOCODE ES is faster than HM-to-device export for a uniform SMC_DIR fleet, but always re-read the parameter view from the device (right-click → Upload from device) before signing off, to catch devices that rejected a partial download.
  • PROFIBUS DP diagnostic addresses must be unique per PCS 7 AS. A duplicated address causes a single device to go offline and can be misread as a contactor fault.
  • Firmware mismatch between basic unit and digital module (e.g., 3UF7011-xA-x-x.xx vs. 3UF7011-xB-x-x.xx) can lock the device in TPF mode. The cross-compatibility matrix is in the system manual linked above.
  • CT orientation: for the SIMOCODE pro V current measuring module, the L1/L2/L3 feed must enter the labeled side (P1) and exit P2. Reversed CTs read zero current → undercurrent trip after the start ramp.

9. Frequently Asked Questions

Why does my SIMOCODE pro V trip with "return feedback off" only when the PLC starts the motor, but works fine in jog mode?

The command source is set to "Jog / Pulse" while the PCS 7 driver block sends a maintained 1-level control word. Switch the command type in SIMOCODE ES to Maintained (level) and assign Control Station 1 to PLC cyclic. The jog bit on the DMF-Local or in the faceplate then becomes a separate, second control station.

Can I parameterize a SIMOCODE pro V PN from TIA Portal through the S7-1500 over Ethernet, or do I need the special USB cable?

Yes. Once the GSDML for SIMOCODE pro V PN is installed and the device is assigned to the IO controller, TIA Portal pushes the parameter record on each restart of the IO device. The special USB cable is only required for direct service access to the basic unit's service port when the PLC is unavailable, per the SIMOCODE pro V PN manual.

What is the default "Feedback Off Delay" in SIMOCODE ES, and what value should I use for a Sirius Q-line contactor?

The default is 2.0 s. For Q-line contactors (closure 30–80 ms) on a PCS 7 cyclic bus, set 3.0–5.0 s to ride through any PROFIBUS/PROFINET scan jitter when the SIMOCODE re-arbitrates after the start command.

My SIMOCODE shows the fault in PCS 7 but the General Fault LED on the device is off. Is the device healthy?

Usually yes. The PCS 7 faceplate can latch a process-level feedback mismatch before the device raises a hard General Fault. Read the SIMOCODE ES event log; if you see event 0x102A "Return Feedback Off" without a hard-trip event, the issue is command-source configuration, not contactor wear.

Does the "Test position feedback" (TPF) function have to be enabled when using a withdrawable motor?

Only if the drawer provides a dedicated TPF input to a digital module input. For fixed direct-online starters (SMC_DIR), disable TPF — leaving it on causes SIMOCODE to expect the contactor to be open during operation, which produces "Return Feedback Off" as soon as the motor starts.

Back to blog