Troubleshooting TIA Portal UDT Compile Errors and Error 0

David Krause25 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview: UDT Compile Errors in TIA Portal

User-Defined Types (UDTs) in TIA Portal provide a structured method for grouping related data elements into a single composite data type, conceptually similar to a struct in C or a TYPE declaration in Pascal. UDTs are first-class citizens in STEP 7 for S7-1200 and S7-1500 controllers and underpin most modern PLC applications by enabling type-safe references in Function Blocks (FBs), Instance Data Blocks (Instance DBs), and global DBs. When a UDT is modified, added, or referenced by program blocks, the compiler performs a full project-wide consistency check. If the UDT contains an illegal definition, TIA Portal reports a compile error. Some errors are descriptive and point directly to the offending line, while others are generic ("error: 0") and require manual reconstruction to localize.

Engineer field note: Always compile a UDT in isolation before integrating it into a project. Use a small test project or a separate AS station to validate the type definition. This reduces the diagnostic surface area when the error appears in a large multi-block program.

UDT Compile Error Categories

UDT compile errors observed in TIA Portal V15 through V20 cluster into three families. The categories differ in root cause, error message, and required remediation.

Error Family Typical Message Root Cause Severity
Start value mismatch "Illegal start value in UDT 'X'" Type-incompatible literal in Start value field Blocked compile of consuming block
Nested UDT failure "UDT 'Y' could not be compiled" Excessive nesting, forward reference, or circular include Block-wide compile failure
Generic "Error: 0" "Compile error: 0" with no row reference TIA Portal internal compiler bug, message suppression Block-wide compile failure
Instance memory overflow Compile OK, download fails with SF UDT instance exceeds CPU work memory Download rejected, CPU remains in old state
Type reference missing "Data type 'X' not found" Referenced UDT deleted or renamed Compile fails for every consuming block

UDT Architecture and PLC Limits

UDTs in TIA Portal are stored under "PLC data types" in the project tree. The declaration consists of an ordered list of members, each with a Name, Data type, optional Default value (start value), and optional Comment. UDTs can reference elementary types, system data types, other UDTs (nesting), arrays, and structured types such as STRUCT...END_STRUCT in DB declarations.

The S7-1200 and S7-1500 CPUs impose hard limits on UDT size and nesting. Exceeding these limits triggers a compile error, often with a generic message that does not specify the violated limit.

UDT Limits by CPU Family
Parameter S7-1200 (FW 4.x) S7-1500 (FW 2.x) S7-1500 (FW 3.x) ET 200SP CPU
Max UDT size (bytes) 8 192 64 000 64 000 64 000
Max nesting depth (UDT-of-UDT) 6 8 8 8
Max number of UDTs per project 256 (CPU 1212C)
1 024 (CPU 1215C+)
Limited by load memory Limited by load memory Limited by load memory
Max members per UDT Limited by size Limited by size Limited by size Limited by size
Max STRING length in UDT 254 254 254 254
Max ARRAY upper bound (1D) 1..1 000 (typ.) 1..32 767 1..65 535 1..65 535
Max ARRAY dimensions 1 6 (V18+), 3 (V17) 6 6
Verification step: Before adding a new UDT to a project, calculate the projected byte size by summing the byte widths of all members. A nested UDT counts as a pointer of 6 bytes (S7-1500) or 4 bytes (S7-1200) plus the size of the contained members. For an ARRAY of UDT, multiply by the upper bound.

Calculating UDT Byte Size

Use the following formula to pre-check a UDT against the CPU limit:

Size(UDT) = SUM_i (Size(Type_i) + Padding_i) + SUM_j (6 + Size(Child_UDT_j))

Where Padding_i rounds the byte offset of member i to the next even word boundary for WORD/DWORD/INT/REAL/Time members. Booleans packed in byte/word/dword containers are bit-packed and do not consume additional bytes until a higher-byte boundary is crossed.

Example calculation for a UDT containing 1 BOOL, 1 INT, 1 REAL, and one nested UDT of 100 bytes:

Size = (1 byte BOOL, packed with INT) + 2 bytes INT + 4 bytes REAL + 6 bytes pointer + 100 bytes nested = 113 bytes

UDT vs STRUCT vs FB: Choosing the Right Construct

Engineers frequently ask whether a data structure should be modeled as a UDT, an in-line STRUCT inside a DB, or a Function Block with static variables. Each construct has different scoping, reuse, and error-handling characteristics.

Construct Scope Reuse Start Values Best For
UDT (PLC data type) Project-wide All blocks, all DBs Yes, applied to all instance DBs Domain data shared across FBs (e.g., motor parameters)
STRUCT in DB Single DB Within that DB only Yes, per DB One-off data grouping that is not reused
FB static variables Per FB instance Per FB instance DB Yes, in FB declaration Encapsulated state internal to a function
Multi-instance DB Per parent FB Across FBs in the same parent Yes, per instance Hierarchical machine state with shared static memory

Use a UDT when the structure is referenced by more than one block or by a library. Use STRUCT in a DB for one-off structures that are not reused. Use FB static variables for encapsulated state with method behavior. Mixing the three in the same project is normal and recommended.

The "Error: 0" TIA Portal Bug

A particularly frustrating UDT error is the generic message "Compile error: 0" or simply "error: 0" that appears in the Inspector window. Despite indicating a "0" error count in the status bar, the Error list panel shows one or more entries. This is a known anomaly in the TIA Portal compiler that affects V15, V15.1, V16, and was partially addressed in V17 and later versions. The error code "0" does not indicate a successful compile; it indicates that the compiler encountered an internal exception while processing the UDT, but was unable to map the exception to a user-readable error code.

Common triggers include:

  • UDT with more than 8 levels of nested UDTs (S7-1500 limit)
  • UDT member whose type was deleted or renamed elsewhere in the project
  • UDT containing an ARRAY with bounds exceeding 32 767 elements (S7-1500 FW 2.x)
  • UDT with a STRING/WSTRING start value longer than the declared length
  • Corruption of the offline/online UDT cache after multiple TIA Portal crashes
  • UDT containing a STRUCT/UDT pointer declared with AT overlay to invalid memory
  • Project migrated from STEP 7 V5.x containing legacy data type references
  • UDT member of type VARIANT, REFERENCE, or INSTANCE-DB with a forced start value
  • Multi-dimensional ARRAY in a UDT that exceeds the version-specific dimension limit

Verifying the "Error: 0" Condition

  1. Open the affected UDT in the editor.
  2. Check the "Error list" panel (View → Error list). The list shows entries with generic descriptions.
  3. Note the row index in the error list. The row index corresponds to the UDT member number in declaration order (0-based).
  4. Open the UDT and visually inspect member at index N for the violation.

If the UDT is referenced by many blocks and the error persists after correction, perform a full project recompile: right-click the PLC → "Compile → Software (rebuild all blocks)". This forces the compiler to discard cached intermediate representations and rebuild the UDT symbol table from source.

Workaround when the error cannot be located: If the UDT cannot be repaired in place, export the UDT definition, delete the UDT from the project, create a new UDT with the same name, and paste the exported definition back in. This forces TIA Portal to re-parse the UDT from a clean internal state and usually clears the "Error: 0" condition.

Nested UDT Errors

Nested UDTs are UDTs that contain other UDTs as members. They model complex hierarchical data, for example a machine UDT containing motor UDTs and sensor UDTs. TIA Portal supports nested UDTs, but errors are common when the nesting depth exceeds the CPU limit or when forward references are used.

Common Nested UDT Failure Modes

Symptom Likely Cause Resolution
UDT compiles alone but fails when used in FB UDT instance exceeds work memory of FB or DB Reduce array bounds, split UDT, or upgrade CPU
"UDT 'X' not found" in child UDT Forward reference or deleted parent UDT Restore parent UDT, reorder declaration
Compile succeeds, but PLC goes to STOP on download UDT instance overflows load memory Check CPU memory budget before download
"Maximum nesting depth exceeded" UDT-of-UDT-of-UDT chain exceeds 8 levels (S7-1500) or 6 (S7-1200) Flatten hierarchy, use ARRAY of STRUCT
UDT with circular reference (A contains B contains A) Forward/declarative cycle Break the cycle with a different abstraction layer

Step-by-Step: Diagnosing Nested UDT Errors

  1. Open the affected UDT. Note the Data type column for each member.
  2. For each member whose Data type is another UDT, open that UDT and repeat the inspection recursively.
  3. Count the levels of recursion from the topmost UDT to the deepest elementary type. The maximum allowed is 8 for S7-1500, 6 for S7-1200.
  4. If depth is within limit, check for circular references: a UDT must not directly or transitively reference itself. A circular reference is permitted only for system data types like UDT_BLOCK_FB in special cases.
  5. For ARRAY of nested UDT, verify the total instance size: ArraySize = UpperBound * Size(UDT). For an S7-1500 with 1 MB work memory, a single instance DB of nested UDTs above ~250 KB may exceed the per-block limit.
  6. Test the UDT in a minimal project with a single FB that uses the UDT as InOut parameter. If the minimal test compiles, the issue is a downstream block using the UDT in a non-standard way.

Start Value Assignment Errors

Every UDT member can have a Start value, used as the initial value of instance DBs derived from the UDT. Start value errors are the most common UDT compile errors and are typically straightforward to localize.

Start Value Rules by Data Type

Data Type Valid Start Value Syntax Invalid Examples
BOOL 0, 1, FALSE, TRUE 2, -1, '' (empty string)
INT / DINT -32 768..32 767, -2 147 483 648..2 147 483 647 40 000 for INT, 1.5
REAL / LREAL Numeric with decimal point, scientific notation 1,5 (use 1.5)
STRING[10] 'Hello' (max 10 chars) 'This string is too long' (exceeds 10)
WSTRING "Unicode text" 'Ascii only' (use double quotes)
TIME / LTIME T#1s, T#100ms, T#1d_2h_30m 1s, 100 (must include T# prefix)
DATE / DT / DTL D#2024-01-15, DT#2024-01-15-12:00:00 15.01.2024, 2024-01-15
ARRAY[0..9] of INT [0,0,0,0,0,0,0,0,0,0] [1,2,3] (must match full range)
Nested UDT (leave empty or use full structure) 0 (cannot use scalar for composite)

Diagnosing Start Value Errors

  1. Compile the UDT alone (right-click → "Compile → Software").
  2. If the compile error message references a specific line number, navigate to that member.
  3. If the message is generic, open the UDT and inspect each member's Start value cell.
  4. Pay special attention to ARRAY members: the Start value must list exactly (UpperBound - LowerBound + 1) elements in square brackets.
  5. For nested UDT members, the Start value cell should be left blank. If a value is entered, it must be a structured literal in parentheses.
  6. For STRING members, count the characters in the literal against the declared length. Each non-ASCII character in WSTRING counts as one or two code points depending on the encoding.
Engineer field note: When copying UDT members between TIA Portal versions, the Start value field may retain old syntax that is no longer valid. For example, an ARRAY start value of [1, 2, 3] in V15 may be flagged as "missing elements" in V18 if the bounds were extended. Always re-validate Start values after TIA Portal upgrade.

Diagnostic Procedure: Step-by-Step

When a UDT compile error is reported, follow this systematic diagnostic procedure. The procedure isolates the failing UDT, the failing member, and the failing value in the shortest possible time.

UDT compile error reported Open UDT in editor Locate red-highlighted row Row found? No Check Error list for row index Yes Inspect Start value & Data type Correct value, rebuild all blocks If still failing: export SCL, delete, reimport

For engineers who prefer a textual diagnostic flow, the same procedure is enumerated below.

  1. Capture the error context. Open View → Error list. Take a screenshot. Note the time, the active project, the active PLC, and the last edit before the error.
  2. Identify the failing UDT. The error list typically includes the UDT name in the form "UDT_xxx" in the "Object" column. If the object column is blank, search the error text for the substring "UDT_".
  3. Open the UDT in the editor. Double-click the UDT entry in the project tree under "PLC data types".
  4. Look for red-highlighted rows. TIA Portal highlights invalid members in red. The red row is the failing member in 90% of cases.
  5. Check the Start value of the red row. Verify the value against the Start value rules table above.
  6. Check the Data type of the red row. Confirm the Data type exists in the project. If the Data type is itself a UDT, recursively open that UDT and check for the same error.
  7. Count the nesting depth. If the UDT is a complex nested type, count the UDT-of-UDT levels.
  8. Recompile in isolation. Right-click the UDT → "Compile → Software (rebuild all blocks)".
  9. If the error persists, export the UDT. Right-click the UDT → "Export" → save as .xml or .scl file.
  10. Delete and recreate the UDT. Delete the failing UDT, create a new UDT with the same name, and re-import the exported definition. This forces a clean re-parse.
  11. Rebuild the affected blocks. Right-click the PLC → "Compile → Software (rebuild all blocks)".
  12. Verify with a minimal test project. If the error still persists, copy the UDT into a new project with a single CPU and a single FB. If the error reproduces in the minimal project, the UDT definition itself is invalid.

UDT Export/Import Workflow

Exporting and re-importing a UDT is the most reliable workaround for "Error: 0" and other non-localized UDT compile errors. The procedure preserves the UDT name and members while forcing TIA Portal to re-parse the definition from a clean text source.

Exporting a UDT as SCL Source

  1. Open the project tree to "PLC data types".
  2. Right-click the UDT and select "Generate source from blocks" (or "Export → SCL source file" on V17+).
  3. Choose a folder and filename (e.g., UDT_MotorData.scl).
  4. Open the .scl file in a text editor to verify the export.

Sample SCL Exported UDT

TYPE "UDT_MotorData"
VERSION : 1.0
  STRUCT
    MotorID : INT := 0;          // Motor identifier
    RatedSpeed : REAL := 1500.0; // Rated speed in RPM
    IsRunning : BOOL := FALSE;   // Run state
    Name : STRING[20] := '';     // Motor name tag
  END_STRUCT;
END_TYPE

Re-importing the UDT

  1. Right-click "PLC data types" → "Import" → "SCL source file".
  2. Select the exported .scl file.
  3. Confirm the UDT appears in the project tree with the original name.
  4. Recompile the project. The UDT should now parse from the clean SCL source.
Compatibility note: .scl files exported from one TIA Portal version may not import cleanly into an older version. Always export and import within the same TIA Portal version, or upgrade the import target project to a version equal to or higher than the source. Reference: Siemens Industry Online Support for the TIA Portal version-specific SCL export/import documentation.

TIA Portal Version-Specific UDT Issues

UDT compile behavior has evolved across TIA Portal major versions. The table below lists known issues and the version in which they were resolved.

UDT-Related Bugs and Fixes by TIA Portal Version
TIA Portal Version Known UDT Issue Fix Status Notes
V15.0 "Error: 0" appears with no error description Partially fixed in V15.1 Update to V15.1 Update 6 minimum
V15.1 UDT with Array start value crashes compile Fixed in V15.1 Update 5 Apply Update 5 or later
V16 Nested UDT with 8+ levels silently truncates Fixed in V16 Update 3 Verify nesting depth manually
V17 UDT import from V15.1 may show phantom errors Fixed in V17 Update 4 Use "Reimport with overwrite" option
V18 STRING start value with embedded null fails Fixed in V18 Update 1 Avoid null characters in STRING literals
V19 Generic "Error: 0" re-introduced in some cases Fixed in V19 Update 2 Apply Update 2 or later
V20 No major UDT issues reported -- Recommended baseline for new projects

For the latest update information, refer to the Siemens Industry Online Support release notes for the active TIA Portal version. The entry point for version-specific documentation is support.industry.siemens.com.

S7 CPU Compatibility and Memory Budget

UDT definitions consume PLC load memory and work memory. A large UDT referenced in a multi-instance DB can exhaust the work memory of a small CPU, triggering a download failure with a generic message. The following table summarizes typical work memory budgets for common S7-1500 CPUs; exact values depend on firmware version.

Typical S7-1500 Work Memory Budgets
CPU Model Program Memory Data Memory Recommended for UDT Footprint
CPU 1511-1 PN 150 KB 1 MB Small UDTs (< 50 KB instance)
CPU 1513-1 PN 300 KB 1.5 MB Medium UDTs with moderate arrays
CPU 1515-2 PN 500 KB 3 MB Medium UDTs with 1 000-element arrays
CPU 1516-3 PN/DP 1 MB 5 MB Large UDTs with multi-axis data
CPU 1517-3 PN/DP 2 MB 8 MB Large recipe or batch data
CPU 1518-4 PN/DP 3 MB 10 MB Process industry with extensive data historians
CPU 1518-4 PN/DP MFP 4 MB 16 MB Combined PLC + C/C++ runtime data

Pre-Deployment Memory Check

  1. Open the CPU Properties → "Memory" tab.
  2. Note "Work memory for program" and "Work memory for data".
  3. Compile the project fully.
  4. Right-click the PLC → "Compiler messages" → note the total data memory used by all instance DBs.
  5. Compare the data memory to the work memory budget. Allow 20% headroom for online modifications and diagnostics.
Rule of thumb: An S7-1511-1 PN has 150 KB work memory for program and 1 MB for data. A single instance DB derived from a UDT with 10 000 ARRAY elements of nested UDT may exceed 1 MB on its own. Use a CPU 1515-2 PN (500 KB program, 3 MB data) or 1518-4 PN/DP (3 MB program, 10 MB data) for large data structures.

Resolution Workflow

After identifying the failing UDT and member via the diagnostic procedure, apply the resolution workflow that matches the error family.

Workflow A: Start Value Error

  1. Open the UDT and navigate to the red-highlighted member.
  2. Clear the Start value field.
  3. Enter the corrected value per the Start value rules table.
  4. Recompile the UDT.
  5. If the error persists, change the Data type to a simpler equivalent (e.g., ARRAY[0..9] of INT instead of nested UDT) to confirm the start value syntax.
  6. Once compiling, restore the original Data type and re-enter the Start value.

Workflow B: Nested UDT Error

  1. Count the nesting depth. If > 8 for S7-1500 or > 6 for S7-1200, flatten the hierarchy by replacing deep UDT levels with STRUCT definitions inside instance DBs.
  2. Check for forward references. A UDT may only reference UDTs that have been declared earlier in the project tree.
  3. Recompile the parent UDT.
  4. If the parent compiles, recompile the consuming blocks (FB, FC, OB) and the entire project.

Workflow C: "Error: 0" Generic Bug

  1. Apply the latest TIA Portal update for the active version (e.g., V18 Update 5 if on V18).
  2. Close and re-open the TIA Portal project.
  3. Right-click the PLC → "Compile → Software (rebuild all blocks)".
  4. If the error persists, export the UDT as SCL, delete the UDT, recreate it, and re-import the SCL.
  5. If the error still persists, create a new TIA Portal project and copy the UDT into the new project. Cross-project UDT corruption is rare but documented.

Verification

After applying a resolution, verify the fix at three levels: compile-time, download-time, and runtime.

Compile-Time Verification

  1. Right-click the PLC → "Compile → Software (rebuild all blocks)".
  2. Confirm zero entries in the Error list.
  3. Open the UDT editor and confirm no red-highlighted rows.

Download-Time Verification

  1. Establish an online connection to the CPU.
  2. Right-click the PLC → "Download to device → Software (all blocks)".
  3. Monitor the CPU diagnostic buffer for STOP-to-RUN transitions or memory allocation errors.
  4. If the CPU transitions to STOP, the UDT instance may exceed the work memory budget. Use the CPU's online "Memory" view to confirm the allocation.

Runtime Verification

  1. In the UDT instance DB, monitor the start values. All members should display the declared Start value when the DB is first opened.
  2. Use a Watch table to read UDT elements by symbolic name. For example, "DB_Motors".Motor[0].RatedSpeed should read 1500.0 if the Start value is set to 1500.0.
  3. Force a CPU restart (STOP → RUN) to confirm Start values are re-initialized.

Best Practices for UDT Design

The following best practices reduce the probability of UDT compile errors and simplify diagnosis when they occur.

  1. Version your UDTs. Use the "Version" field in the UDT properties to track major.minor revisions. Increment major when the UDT layout changes incompatibly, minor for additive changes.
  2. Document UDTs in the comment column. Each UDT member should have a comment explaining its semantic role, valid range, and units.
  3. Avoid deep nesting. Keep nesting depth to 4 levels or less. If a deeper structure is required, use a structured variable inside an instance DB instead of a nested UDT.
  4. Pre-validate Start values. For ARRAY members, generate the start value list programmatically using a script. The TIA Portal Openness API supports scripted UDT creation and validation.
  5. Test UDT changes in a branch project. Before modifying a UDT that is referenced by 50+ blocks, copy the project to a branch and test the UDT change in isolation. UDT changes can have wide-reaching effects on instance DB layouts.
  6. Keep the TIA Portal installation up to date. Apply the latest update for the active TIA Portal version. Many "Error: 0" cases are fixed in point releases.
  7. Avoid the AT construct in UDTs. The AT keyword for memory overlay is allowed in UDTs but increases the risk of "Error: 0" or non-localized compile errors.
  8. Use descriptive UDT names. Prefix UDT names with a domain code, e.g., UDT_MTR_MotorData for motor data, UDT_VLV_ValveData for valve data. This improves error messages when the UDT is referenced from consuming blocks.
  9. Maintain a UDT library project. Reusable UDTs should be stored in a master library project and imported via the library mechanism. This ensures version consistency across deployments.
  10. Document the Start value policy. Decide whether Start values are mandatory (compile fails if missing) or optional. Apply the policy uniformly across UDTs to avoid mixed behaviors.
  11. Avoid mixing optimized and standard access in the same UDT. Mixing the two access modes within a single UDT can produce phantom compile errors after PLC firmware updates.
  12. Use the TIA Portal Openness API for mass UDT changes. When the same UDT change must be propagated across many projects (e.g., a global pump UDT in 40 machine projects), script the change via the Openness API rather than manual editing. This reduces the risk of inconsistent state across projects.

Troubleshooting Matrix

The following matrix maps symptoms to root causes and first-line actions.

Symptom Likely Cause First-Line Action
"Error: 0" with no description Internal compiler exception Rebuild all blocks, update TIA Portal
Red row in UDT editor Invalid start value or missing type Inspect the row, fix Start value or Data type
"UDT 'X' not found" in FB UDT was deleted or renamed Restore UDT, re-attach interface
Compile OK, download fails with memory error UDT instance exceeds work memory Check CPU memory budget, reduce array bounds
CPU STOP after download Instance DB size mismatch Reinitialize DBs, check retain settings
"Maximum nesting depth exceeded" UDT-of-UDT > 8 levels Flatten hierarchy, use STRUCT in instance DB
Array start value rejected Element count mismatch Provide exactly (Upper - Lower + 1) elements
STRING start value rejected Literal longer than declared length Increase STRING length or shorten literal
UDT compiles in isolation but fails in project Library version mismatch Update library instances from master
FB shows old UDT layout after UDT change Block interface not refreshed Right-click FB → "Update block interface"

Field-Proven Caveats

Beyond the documented issues, field experience reveals several caveats that are not always captured in the TIA Portal help system.

  1. Library UDTs require care when the master version changes. When a UDT is updated in the master library, all dependent instance DBs may show a "type mismatch" warning. Use "Update instances" from the project tree to refresh.
  2. UDT start values are not applied to retain variables. If an instance DB is configured as "Set in IDB" with retain, the Start value is used only on first download. Subsequent restarts use the retained value.
  3. UDT with optimized access behaves differently from standard access. Optimized UDTs (block-access via "Symbolic access only") do not allow AT overlays and have different memory layouts. Switching between access modes after instance DB creation may require manual re-initialization.
  4. UDT members of type VARIANT cannot have a Start value. The Start value cell is greyed out for VARIANT, REFERENCE, and INSTANCE-DB-type members. The "Error: 0" appears if a value is forced into the cell via copy-paste from another member.
  5. Multi-language UDT comments require UTF-8 encoding. TIA Portal saves project files in UTF-8. Comments in non-Western languages (e.g., Chinese, Japanese, Cyrillic) require the project language to be set to the corresponding locale before editing.
  6. UDT export/import between TIA Portal versions must respect the target version's SCL dialect. The SCL dialect was tightened in V17 to reject implicit type conversions. A UDT that exported from V15 may have implicit conversions that the V17 SCL parser flags as errors.
  7. UDT changes invalidate the online fingerprint. When a UDT changes, TIA Portal blocks the download to a CPU that has an older online copy of the UDT-derived instance DB. The fix is to first download the new blocks, then accept the prompt to reinitialize the instance DB.

Glossary

Term Definition
UDT User-Defined Type. A composite data type defined under "PLC data types" in TIA Portal.
Instance DB A data block automatically generated from an FB or UDT, containing the static variables of the FB or the structure of the UDT.
Multi-instance DB A single DB that contains the static variables of multiple FBs that are called inside a parent FB.
Start value The initial value assigned to a UDT member, applied to instance DBs on first download.
Optimized access A block property that stores data in a CPU-internal format and exposes it only via symbolic names. Reduces memory consumption and improves performance.
Standard access A block property that stores data with fixed offsets accessible by absolute addresses. Required for legacy S7-300/400 compatibility.
SCL Structured Control Language. A high-level Pascal-like programming language in TIA Portal.
Openness API A .NET-based scripting interface to TIA Portal that allows automated project manipulation.
Red rebuild The "Compile → Software (rebuild all blocks)" command that discards all cached intermediate representations and recompiles from source.
AT construct A SCL/PLC keyword that allows overlaying a variable on a different memory area with type conversion.

FAQ

What does "Error: 0" mean when compiling a UDT in TIA Portal?

"Error: 0" is a generic compiler exception in TIA Portal V15 through V19, indicating that the compiler encountered an internal error while processing the UDT and could not map it to a user-readable description. Common causes are nested UDT depth exceeding 8 levels, deleted or renamed member types, ARRAY start values with mismatched element count, or STRING start values longer than the declared length. Apply the latest TIA Portal update, perform "Rebuild all blocks", and if the error persists, export the UDT as SCL, delete it, and re-import the SCL source.

How do I find the exact UDT member that is causing a compile error?

Open the UDT in the editor and look for rows highlighted in red. The red row corresponds to the failing member in 90% of cases. If no row is red, open the Error list panel (View → Error list) and note the row index. The row index maps to the UDT member declaration order, starting at 0. For nested UDTs, recursively open each referenced child UDT until the red row is found.

What is the maximum nesting depth for nested UDTs in S7-1500 and S7-1200?

S7-1500 CPUs support up to 8 levels of nested UDTs (UDT of UDT of UDT, etc.). S7-1200 CPUs support up to 6 levels. Exceeding these limits triggers a compile error, typically with a generic message. Flatten the UDT hierarchy by replacing deep UDT levels with STRUCT declarations inside the consuming instance DB if deeper structures are required.

Why does my UDT compile alone but fail when used in an FB?

The most common cause is a UDT instance size that exceeds the work memory of the consuming block or the CPU. A UDT that compiles alone (typically 1 instance) may produce a 2 MB instance DB when used in an ARRAY[0..999] of that UDT. The per-block work memory limit for S7-1500 is 64 KB for FB, FC, and DB unless the CPU supports larger blocks (e.g., S7-1518 supports 1 MB). Reduce the array bounds, split the array into multiple smaller arrays, or upgrade the CPU.

Can I export a UDT from one TIA Portal version and import it into another?

Yes, with caveats. SCL export from a newer TIA Portal version (e.g., V20) typically imports into the same version or a newer version. Importing a V20 SCL file into V17 may fail or produce phantom errors. The safe approach is to use the same TIA Portal version for export and import, or upgrade the import target to the newer version first. Always compile and test the imported UDT in isolation before integrating it into the project.

What TIA Portal update fixes the most common "Error: 0" UDT bug?

The "Error: 0" UDT bug is most reliably addressed by V18 Update 1, V19 Update 2, or any V20 service pack. For older versions (V15.x, V16, V17), apply the latest available update for that version. After updating, perform a full project recompile via "Compile → Software (rebuild all blocks)" to clear the cached compiler state. If the error persists after the update, the underlying cause is a specific UDT definition problem, not a compiler bug, and must be resolved by inspecting the UDT members.

How do I validate UDT memory consumption before deployment?

Open the CPU Properties → "Memory" tab and note the work memory for data. Compile the project fully, then right-click the PLC → "Compiler messages" to view the total data memory used by all instance DBs derived from UDTs. Compare this against the work memory budget and allow at least 20% headroom for online modifications, diagnostics, and recipe data. For UDTs with multi-thousand-element arrays, pre-calculate the instance size as UpperBound * Size(UDT) and verify the result against the per-block maximum of 64 KB (standard) or 1 MB (S7-1518) before download.

Back to blog